Asco Series 300 Installation guide

Series 300
2000 - 4000 Amp Pad Mount
Quick Connect Input and Output Power Panels
Florham Park, NJ 07932-1591 www.ascopower.com
DANGER is used in this manual to warn of a hazard
situation which, if not avoided, will result in death or
serious injury.
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
Important:
This manual contains information critical to the proper
installation
and operation of the ASCO Series 300
Quick Connect Power Panels.
Be certain to read and
understand all instructions prior to installation
and
operation.
The ASCO Series 300 Quick Connect Power Panel
must be installed in
conjunction with a transfer switch.
ASCO Series 300 Quick Connect Input Power panels
are listed to UL1008. ASCO Series 300 Quick
Connect Output Panels are listed to UL 891 for
Switchboards.
Limited Warranty
When this ASCO Series 300 Quick Connect Power Panel
is installed and operated
according to the manual’s
instructions ASCO Power Technologies will repair or
replace any of its mechanical or electrical parts if they are
found
to
be defective in material or workmanship within two
year of the
purchase date.
Maintenance
The ASCO Series 300 Quick Connect Power Panels will
require periodic
maintenance. ASCO Power Technologies
recommends annual inspections to keep
the panel in safe
operating condition. ASCO Power Technologies
recommends that
the Pre-Operation and Maintenance
Checklist under Appendix A
serve as a basis for annual
inspection.
Technical Support
ASCO Power Services are available to assist in resolving
issues by calling 1-800-800 2726 (ASCO) or emailing
powerwarranty@ascopower.com. For any other
information, please refer to ascopower.com
381333-476

ASCO Series 300 Quick Connect Power Panel
2www.ascopower.com 381333-476
Table of Contents
Page(s) Section
1 Limited Warranty
1 Maintenance
1 Technical Support
3 Prior to Installation
3 Shipment: Unpacking and Inspection
4 Initial Installation (for Input and Output Panels)
5 Installation – Input Panels
6-8 Set-up
9 Installation – Output Panels
9-11 Set-up
11 Appendix A:
Pre-Operation and Maintenance Checklist
12 Index

ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
3
Prior to Installation: Site Preparation
Prepare installation site according to local codes.
The ASCO Series 300 Quick Connect Power Panels are to be
set on an exterior pad
and secured to a building or secured
to a pad using 3/8“ fasteners
(See Figure 1).
The surface where the ASCO Series 300 Quick Connect
Power Panel is to be
secured must be capable of supporting
the weight of the cabinet as
well as the cable attached to it.
The following should be taken into consideration when
locating the
ASCO Series 300 Quick Connect Power Panel:
–
The ASCO Series 300 Quick Connect Power Panel is
designed for exterior
operation ONLY
–
Identify and meet local codes and local Authority
Having
Jurisdiction (AHJ)
–
Toprevent carbon monoxidepoisoning from improperly
ventilated
generator emissions, the Power Panelmust be
mounted
outdoors only. The mounting location is to be
carefully selected to
allow convenient connection to a
generator, and located a suitable
distance away from any
building openings or HVAC inlets.
–
Proper clearance must be allowed in front of the ASCO
Series 300 Quick Connect Power Panel to allow for
opening of access doors and
attachment of externally
connected cables. This distance should be
no less than
six (6) feet from the face of the panel.
–
While lockprotectionis provided, access by unauthorized
personnel and vandals should be taken into consideration
when
locating this device.
S h i p m e n t : U n p a c k i n g and Inspection
Be careful in the use of sharp object when cutting
packaging
as damage to the outer enclosure
may result.
Perform a visual inspection to ensure the door and all hasps
are in
functioning condition and that the panel integrity is
intact
.
Figure 1
Bottom View
Secure with 3/8” fasteners

ASCO Series 300 Quick Connect Power Panel
4www.ascopower.com 381333-476
Initial Installation
ASCO Series 300 Quick Connect Power Panels are front
heavy
(See Figure 2).
Care must be taken to secure the
device when it is lifted and
moved.
– Please note that the 2000 Amp versions weigh
approximately
2
20 pounds and the 2400-4000 Amp
versions range from
317-360 pounds for aluminum
enclosures. Stainless steel enclosures are approximately
200 pounds heavier at their respective amperage levels.
The installation of the ASCO Series 300 Quick
Connect Power Panel should
be carried out by
qualified personnel in accordance with
local
electrical codes.
The ASCO Series 300 Quick Connect Power Panel
must be installed in
conjunction with a transfer
switch.
The transfer switch shall not have a rating greater
than the
ASCO Series 300 Quick Connect Power
Panel.
Figure 2
Step 1: Fasten the ASCO Series 300 Quick
Connect Power Panel to secure base
1.
Base must be level and plumb to allow for proper
drainage
from ASCO Series 300 Quick Connect Power
Panel weep holes
2.
Fastening onto an external wall using 3/8” fasteners
must be
completed prior to proceeding with any
terminations (See Figure 1
for hole spacing)
Step 2: Installing the Conduit
Conduit to enter through the bottom,rearand sides o f the
unit.
(See
Figure 3)
To maintain TYPE 3R Rating compliance for the
enclosure, proper sealing procedures must be
followed. This
is to include, but not limited to, the use of
proper gaskets.
1.
Remove rear and side panels to expose termination
chamber
2.
Conduit to be sized according to cabling rating
3.
It is recommended that a knockout punch be used to cut
hole for
conduit.
4.
Place the punch on the panel that was removed from the
enclosure and draw the
punch through to the die on the
outside.
Figure 3

ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
5
Installation -Input Panels
This section is for Installation of Input Panels.
For Installation of Output Panels proceed to
Page 9.
Step 3: Wiring the Lug Terminals
Ensure circuit breakers are OFF and the transfer switch is
locked
out from utility power prior to connection.
Failure to install transfer switch will create the potential for
the
generator to energize utility lines and endanger utility
personnel.
Conversely, utility lines may energize the ASCO
Series 300 Quick Connect Power
Panel
and endanger
generator personnel.
The ASCO Series 300 Quick Connect Power Panel
is for use only for
connection of a generator to the
source terminals of a
transfer switch, such that the
inlets are only energized from
the generator.
1.
Pull the cables for the transfer switch to the ASCO
Series 300 Quick Connect Power
Panel
2.
Beginning with the ground, strip and install the cables
in the appropriate compression terminals
The terminals can accommodate #2 to 600MCM, Copper
wire only
3.
Tighten terminal screws to 375 lb-in torque each
4.
If metallic conduit is used, connect ground wire from
ground
bushing on conduit to the ground connection
point in the upper
right quadrant of the panel
5.
Ground conductor must be a minimum of #2 AWG
Conduit shall NOT be relied upon to provide grounding
protection to tap box
6.
Continue to connect the neutral and then the phases
7.
Vacuum entire upper chamber to ensure no metal
shavings are left
behind
Three phase power systems consist of three phase or hot
conductors that are shifted by 120 degrees. Three phase
loads such as motors may only work properly if the phases
are
connected in the correct order. Some motors may work
when
connected improperly, but will operate backwards.
Utility power
and electrical generators may be wired either
in a clockwise or counter-clockwise order. It is important that
any generator
connected to the ASCO Series 300 Quick
Connect Power Panel is connected in the same rotation
(clockwise or counter-clockwise) as the utility power.
Step 4: Determine Phase Rotation
This information will be needed when connecting a
generator
.
1.
Determine phase rotation of the utility power.
2.
Connect a phase rotation meter to a three phase power
source in
the building and record whether the building is
wired clockwise or
counter-clockwise
3.
Apply the provided label to the inside of the ASCO
Series 300 Quick Connect Power
Panel
on the inside of the
cam connection chamber door
. (Figure 4)
Figure 4
Place rotation label here

ASCO Series 300 Quick Connect Power Panel
6www.ascopower.com 381333-476
Step 5: Configuring the Phase Rotation
Monitor
A phase rotation monitor comes standard on all 2000A -4000A
pad mount Input panels. The Phase rotation monitor is
prewired from the factory for ABC rotation. (Figure 5)
1.
Should the phase rotation monitor configuration and
utility power (label found on the inside of
the door for the
Cam connection chamber) match, proceed to Step 6.
2.
Should the phase rotation monitor configuration and
utility power (label found on the inside of
the door for the
Cam connection chamber) differ, swap the A and B
phase rotation connection wires at the camlock
connection so it matches utility power and is consistent
with the label found inside the door.
Figure 5
Set-up
Step 6: Review Pre-Operation Checklist under
Appendix A prior to operation (pg. 8)
DO NOT ATTEMPT CONNECTION WHILE CIRCUITS
ARE LIVE
–
Do not use cables if they appear frayed
–
Do not use cable if connectors or plug do not seat properly
–
Do not use cables if any copper cabling is exposed
–
To limit risk of shock, disable generator automatic
start to
prevent unintended starting
Step 7: Determining phase rotation of generator
1.
Disconnect generator from all loads if needed
2.
Connect a phase rotation meter to the output phases
of the
generator
3.
Record generator phase rotation (clockwise or
counter-clockwise)
Step 8: Conduct a safety test to ensure proper
installation
1.
Do not attempt to use the ASCO Series 300 Quick Connect
Power Panel prior to
installation and completing the Pre-
Operation and Maintenance
Checklist under Appendix A
.
2.
Complete the Ground (green)connections, beginning
with the furthest from the from door to the left
Proper connection (Figure 6):
A.
Grasp connector jacket and firmly insert cam connector
into cam
plug
B.
Push on cam connector jacket until connector fully seats
in cam
plug
C.
Rotate cam connector jacket counterclockwise until it
stops
Step 9: Making Cam Connections
1.
Open main chamber door.
Figure 6
2.
Continue with connections, beginning with the rear of the
cabinet
and working forward
3.
Complete ALL Ground connections working from back to
front prior
to proceeding
4.
Complete the Neutral (white) connections, beginning with
the
furthest from the front door
Proper connection (Figure6):
A.
Grasp connector jacket and firmly Insert cam connector
into cam
plug
B.
Push on cam connector jacket until connector fully seats
in cam
plug
C.
Rotate cam connector jacket counterclockwise until it
stops

ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
7
Set-up – Continued
D.
Continue with connections, beginning with the rear of the
cabinet
and working forward.
E.
Complete the Phase (hot) connections
i.
Should the phase rotation of the generator (as
determined in
Step 5.B.3. above) and utility power
(label found on the inside of
the door for the Cam
connection chamber) match, connect the
Hots as
follows:
Generator Hot
ASCO Series 300 Quick Connect
Power Panel Hot
AA
B
B
C
C
ii.
Should the phase rotation of the generator (as
determined in
Step 7.3. above) and utility power
(label found on the inside of
the door for the Cam
connection chamber) NOT match, connect
the Hots as
follows:
Generator Hot
ASCO Series 300 Quick Connect
Power Panel Hot
A
B
B
A
C
C
Proper connection (Figure 6):
A.
Grasp connector jacket and firmly insert cam connector
into cam
plug
B.
Push on cam connector jacket until connector fully seats
in cam
plug
C.
Rotate cam connector jacket counterclockwise until it
stops
5.
Continue with connections, beginning with the rear of the
cabinet
and working forward
6.
Complete ALL Phase connections working from back to
front prior
to proceeding
7.
Make sure all connections are right and secure
Step 10: Connect 2 wire auto start circuit
1. Connect 2 wire auto start circuit from transfer
switch to terminal post located in the upper right
corner of the Quick Connect Panel.(Figure 7)
2. Connect the 2 wire auto start circuit from generator
to terminal post.
Figure 7
Step 11: Close and lock lower chamber door,
allowing cables to exit through smaller cable
door
(See Figure 8)
Figure 8

ASCO Series 300 Quick Connect Power Panel
8www.ascopower.com 381333-476
Step 12: Powering Up
Power MUST BE supplied from a single generator
1.
Start generator per manufacturer instructions
Toggle the transfer switch, diverting power from utility to
generator feed
Step 13: Disconnection
DO NOT ATTEMPT DISCONNECTING WHILE
CIRCUITS ARE LIVE
1.
To limit risk of shock, disable generator automatic start to
prevent
unintended starting
–
Open lower chamber door
–
Order of disconnect
2.
Disconnect the Phase (hot) connections, beginning with
the
closest to the front door to the right.
Proper disconnection (Figure 9):
A.
Grasp connector jacket firmly and rotate cam connector
clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside
3.
Continue with ALL Phase (hot) connections, beginning
with the front of the cabinet and working from front to
back
Figure 9
4.
Complete disconnect of ALL hot connections prior to
proceeding
5.
Disconnect the Neutral (white) connection, beginning with
the
closest to the front door.
Proper disconnection (See Figure 9):
A.
Grasp connector jacket firmly and rotate cam connector
clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside
6.
Continue with ALL Neutral (white) connections,
beginning with the
front of the cabinet and working from
front to back
7.
Complete disconnect of ALL Neutral connections prior to
proceeding
8.
Disconnect the Ground (green) connections, beginning
with the
closest to the front door
Proper disconnection (See Figure 9):
A.
Grasp connector jacket firmly and rotate cam connector
clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside
9.
Continue with ALL Ground (green) connections,
beginning with the
front of the cabinet and working
rearward
10.
Complete disconnect of ALL Neutral connections prior to
proceeding
Step 14: Secure front door to complete.

ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
9
Installation – Output Panels
Continued from page 4
Step 3: Wiring the Bus Bars
EnsurecircuitbreakersareOFFandthetransferswitchis
locked out from Source power prior to connection.
Failuretoinstalltransferswitchwillcreatethepotentialfor
thesource to energize
the ASCO Series 300 Quick
Connect Output Power Panel and
endanger installation
personnel.
The ASCO Series 300 Quick Connect Output
Power Panel is for the connection of a Load
Bank to the Output terminals of a transfer switch.
1.
Pull the cables for the transfer switch to the ASCO
Series 300 Quick Connect Power
Panel
2.
Beginning with the ground, strip and install the cables in
the appropriate compression terminals
The terminals can accommodate #2 to 600MCM, Copper
wire only
3.
Tighten terminal screws to 375 lb-in torque each
4.
If metallic conduit is used, connect ground wire from
ground
bushing on conduit to the ground connection
point in the upper
right quadrant of the panel
5.
Ground conductor must be a minimum of #2 AWG
6.
Conduit shall NOT be relied upon to provide grounding
protection to tap box
7.
Vacuum entire upper chamber to ensure no metal
shavings are left
behind
Step 4: Conduct a safety test to ensure proper
installation
Do not attempt to use the ASCO Series 300 Quick
Connect Power Panel prior to
installation and
completing the Pre-Operation and Maintenance
Checklist under Appendix A
.
Set-up
Step 5: Review Pre-Operation Checklist under
Appendix A prior to operation (pg. 8)
DO NOT ATTEMPT CONNECTION WHILE CIRCUITS
ARE LIVE
–
Do not use cables if they appear frayed
–
Do not use cable if connectors or plug do not seat properly
–
Do not use cables if any copper cabling is exposed
–
To limit risk of shock, disable generator automatic
start to
prevent unintended starting
Step 6: Making Cam Connections
1.
Open lower chamber door
2.
Complete the Ground (green)connections, beginning
with the furthest from the from door to the left
Proper connection (See Figure 10):
A.
Grasp connector jacket and firmly insert cam
connector
intocam plug
B.
Push on cam connector jacket until connector fully
seats
in cam plug
C.
Rotate cam connector jacket counterclockwise until
it
stops
Figure 10
3.
Continue with connections, beginning with the rear of
the cabinet and working forward
4.
Complete ALL Ground connections working from
back to frontprior to proceeding
5.
Continue with connections, beginning with the rear of
the cabinet and working forward

ASCO Series 300 Quick Connect Power Panel
10 www.ascopower.com 381333-476
Set-up – Continued
6.
Complete the Phase (hot) connections
Proper connection (See Figure 8):
A.
Grasp connector jacket and firmly insert cam
connector
intocam plug
B.
Push on cam connector jacket until connector fully
seats
in cam plug
C.
Rotate cam connector jacket counterclockwise until
it
stops
Step 7: Close and lock lower chamber door,
allowing cables to exit through smaller
cable door (See Figure 11)
Figure 11
Step 8: Powering Up
Power MUST BE supplied from a source wired to a Transfer
Switch
1.
Toggle the transfer switch, diverting power from building
loads to load bank.
Step 9: Disconnection
DO NOT ATTEMPTDISCONNECTING
WHILE CIRCUITS ARE LIVE
Open lower chamber door
Orderofdisconnect
1.
Disconnect the Phase (hot) connections, beginning with
the
closest to the front door to the right.
Proper disconnection (See Figure 12):
1.
Grasp connector jacket firmly and rotate cam connector
clockwise until it stops
2.
Firmly pull on connector until it separates from the plug
3.
Set aside
2.
Continue with ALL Phase (hot) connections, beginning
with the front of the cabinet and working from front to
back
Figure 12
3.
Complete disconnect of ALL hot connections prior
to
proceeding
4.
Disconnect the Neutral (white) connection,
beginning
withtheclosesttothefrontdoor.
Proper disconnection (See Figure 12):
A.
Grasp connector jacket firmly and rotate cam
connector clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside

ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
11
Set-up – Continued
4.
Disconnect the Ground (green) connections,
beginning
withtheclosesttothefrontdoor
Proper disconnection (See Figure 12):
A.
Grasp connector jacket firmly and rotate cam
connector clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside
5.
ContinuewithALLGround(green)
connections,
beginning with the front of the
cabinet and working
rearward
6.
Complete disconnect of ALL Neutral connections prior
to
proceeding
Step 10: Secure front door to complete.
Appendix A
Pre-Operation Checklist
1.
Visual inspection of enclosure
–
Ensure the ASCO Series 300 Quick Connect Power Panel
is firmly secured to its
base and/or building
–
Review conduit connection for signs of leakage
–
Ensure paint is intact with no signs of rust or corrosion
2.
Open main chamber door and remove rear and side
panels
–
Ensure unit is dry and free of debris
–
Ensure that gaskets are pliable and no cracking exists
–
Ensure that door hinges are secure and lubricated
–
Ensure that keylocks are intact and operational
–
Ensure that all load terminals are securely fastened and
that the
bolts are set at ninety-eight (98) foot pounds of
torque
–
Ensure paint is intact with no signs of rusting or corrosion
–
Ensure electrical connections are intact with no signs of
corrosion or cracking
3.
Review all safety labels and ensure that they are
present
and legible
–
Replace as needed
4.
Inspect all portable cables
–
Do not use cables if they appear frayed
–
Do not use cable if connectors or plug do not seat properly
–
Do not use cables if any copper wiring is exposed
5.
ASCO Power Services are available to assist in resolving
issues. If you have any questions or need technical advice
or
suggestions regarding this product, please contact
ASCO Power Technologies
at
1-800-800-2726(ASCO) or e-mail

ASCO Series 300 Quick Connect Power Panel
12 www.ascopower.com 381333-476
The ASCO and ASCO Power Technologies
marks are owned by Emerson Electric Co. or
its affiliates and utilized herein under license.
©2018 ASCO Power Technologies.
All Rights Reserved.
INDEX
A
annual inspection 1
B
bus bars 5, 9
C
cam connections 6, 9
chamber door 5, 6, 7, 8, 9, 10, 11
circuit breakers 5, 9
conduit, 5, 9 ,11
installing, 4
copper wiring, 11
D
disconnecting circuits 8, 12
G
gasket 4, 11
H
HELP
ASCO Power Services, Inc.
1-800-800-2726 (ASCO) 1, 6
powerwarranty@ascopower.com
hot conductors 5
I
inspection 1, 3, 11
L
limited warranty 1
M
maintenance 1, 5, 9
P
phase rotation 5, 6, 7
plug 6,7, 8, 9,10, 11
portable cables 11
powering up, 7, 10
pre-operation checklist 6, 9, 11
S
safety test 5, 9
safety labels, 11
site preparation, 3
shipment 3
T
technical support 1
terminals 5, 9, 11
torque 5, 9, 11
U
unpacking 3
V
visual inspection 3, 11
Other manuals for Series 300
6
Table of contents
Other Asco Switch manuals

Asco
Asco J 4000 Series User manual

Asco
Asco 7000 Series User manual

Asco
Asco 8215 Installation and operating instructions

Asco
Asco Series 300 User manual

Asco
Asco 940 User manual

Asco
Asco 7000 Series User manual

Asco
Asco 940 User manual

Asco
Asco 7000 Series User manual

Asco
Asco 911 series User manual

Asco
Asco 7000 Series User manual

Asco
Asco 386 Series User manual

Asco
Asco Series 300 User manual

Asco
Asco 8344 Installation and operating instructions

Asco
Asco 230 Series User manual

Asco
Asco 230 Series User manual

Asco
Asco 200 Series User manual

Asco
Asco Series 300 User manual

Asco
Asco 917 User manual

Asco
Asco Joucomatic 349 Series User manual

Asco
Asco 3ATS User manual