Asco 4000 series User manual

Operator’s
Manual
4000 Series ATS
Automatic Open-Transition Transfer Switches
D–design 30–230A, J–design 260–600A,
H-design 800–1200A, G-design 1600–4000A, F-design 4000A
Florham Park, NJ 07932-1591 USA
Call 1 800 800-2726 (ASCO) for sales or service www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
DANGER is used in this manual to warn of a
hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
Refer to the outline and wiring drawings provided with your
4000 Series ATS for all installation and connection details
and accessories.
Refer to Group 5 Controller User’s Guide 381333–126 for
ATS status display messages, time delays, pickup &
dropout settings, and adjustments.
An experienced licensed electrician must install the ATS
.
Rating Label
Each automatic transfer switch contains a rating label to
define the loads and fault circuit withstand / closing ratings.
Refer to the label on the transfer switch for specific values
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
381333-270 D
TABLE OF CONTENTS
page
Ratin
g
Label 1
Nameplate, Catalo
g
Number Identification 2
INSTALLATION
3-7
Removing the Shipping Skid, Supporting
Foundation, Mounting, Testing Power
Conductors,
3
Connecting Power Conductors, Auxiliary Cable
Boxes, Bus Connections, Controller Ground,
Harnesses, En
g
ine Startin
g
& Auxiliar
y
Circuits
4
En
g
ine Startin
g
Contacts 5
Functional Test 6-9
Functional Test
–
Manual Operation Test 6
Functional Test
–
Volta
g
e Checks
8
Functional Test - -Electrical Operation
9
TESTING & SERVICE
10-11
Transfer Test, Preventive Maintenance,
Replacement Parts, Disconnecting the Controller
10
Manual Load Transfer, Trouble-Shootin
g
11
INDEX
12

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 2 ASCO Power Technologies 381333-270D
Nameplate
The Transfer Switch nameplate includes data for each
specific 7000 Series ATS. Use the switch only within the
limits shown on this nameplate. A typical catalog number
is shown on the next page with its elements explained.
Catalog Number Identification
Typical 4000 Series catalog no. for D-design, 3 pole,
150 amp, 480 V, in Type 1 enclosure:
D4
A
TS B 3 150 N 5 C
Frame
&
Series
Neutral Phase Poles Amperes Voltage Controller Enclosure
A-solid
B-switched
blank- none
2-single
3-three
30
70
100
125
150
200
230**
260
400
600
800
1000
1200
1600
2000
2600
3000
4000
A 115
B 120
C 208
D 220
E 230
F 240
G 277
H 380
J 400
K 415
L 440
M 460
N 480
P 550
Q 575
R 600
5- standard
5X- if
accessories
ordered
C- Type 1
F- Type 3R
G- Type 4
H- Type 4X
L- Type 12
blank- open type
150 amp. size in typical enclosure with location of customer connections
power
connections
Transfer
Switch
engine
starting
contacts
connections
**230 amp limited to 480 volts
Transfer
Control &
lights
Group 5
Controller
power
connections

Operator’s Manual Series 4000 Automatic Transfer Switch
381333-270D ASCO Power Technologies Page 3
Installation
ASCO 4000 Series Automatic Open–Transition Transfer
Switches are factory wired and tested. Field installation
simply requires mounting and connection of service cables,
and auxiliary control circuits (if required).
Remove the Shipping Skid
For large switches, open the front door and remove the four
lag screws (2 in front, 2 in rear) securing enclosure to the
wood skid.
Supporting Foundation
The supporting foundation for the enclosure must level and
straight. Refer to the applicable enclosure outline drawing
included with the ATS for all mounting details including
door opening space.
If bottom cable entry is used, the foundation must be
prepared so that the conduit stubs are located correctly.
Refer to the enclosure outline drawing for specified area
and location. Provide cable bending space and clearance to
live metal parts. When a concrete floor is poured, use
interlocking conduit spacer caps or a wood or metal
template to maintain proper conduit alignment.
Mounting
Refer to the outline and mounting diagram provided with
the ATS; it shows all mounting details and instructions.
Protect the automatic transfer switch from construction
grit and metal chips to prevent malfunction or
shortened life of the transfer switch.
Mount the ATS vertically to a rigid supporting structure.
Level all mounting points by using flat washers behind the
holes to avoid distortion of the switch.
The controller is mounted on the cabinet door. An add-on
DIN rail is provided for some optional accessories and is
mounted below controller on the door.
De–energize the conductors before making any line or
auxiliary circuitry connections. Be sure that Normal
and Emergency line connections are in proper phase
rotation. Place engine generator starting control in the
OFF position. Make sure engine generator is not in
operation.
Testing Power Conductors
Do not connect the power conductors to the transfer switch
until they are tested. Installing power cables in conduit,
cable troughs and ceiling-suspended hangers often requires
considerable force. The pulling of cables can damage
insulation and stretch or break the conductor’s strands. For
this reason, after the cables are pulled into position, and
before they are connected, they should be tested to verify
that they are not defective or have been damaged during
installation.

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 4 ASCO Power Technologies 381333-270D
Connecting Power Conductors
A Wiring Diagram is furnished with the ASCO 4000
Series ATS (separate from this manual). Refer to this
drawing. All wiring must be made in accordance with the
National Electrical Code and local codes.
After the power cables have been tested, connect them to
the appropriate terminal lugs on the transfer switch as
shown on the wiring diagram provided with the switch.
Make sure the lugs provided are suitable for use with the
cables being installed. Standard terminal lugs are
solderless screw type and will accept the wire sizes listed
on the drawings provided with the switch. Be careful
when stripping insulation from the cables; avoid nicking
or ringing the conductor. Remove surface oxides from
cables by cleaning with a wire brush. When aluminum
cable is used, apply joint compound to conductors.
Tighten cable lugs to the torque specified on rating label.
Do not run cables in front of or behind the switch. Cables
can be bundled on the right side of the switch. Maintain
proper electrical clearance between the live metal parts
and grounded metal: ½ inch minimum for 150-400 amps,
1 inch minimum over 400 amps.
It is not necessary to remove the barriers from the transfer
switches to install the cables. If you do remove them,
however, be sure to reinstall the barriers carefully.
Three cable spacers are included with 150, 200, & 230
amp transfer switches. When installing power cables, run
the cables through the cable spacers as shown in Figure 1.
Position the cable spacers within 1½ inches from the lugs.
The cable spacers must be located as shown
for 150, 200, and 230 ampere transfer switches.
Figure 1. Cable spacer for 150, 200, and 230 amp.
transfer switches.
Auxiliary Cable Boxes
For 1000 & 1200 amp. sizes, an auxiliary cable box is
required for all (normal, emergency, & load) bottom or top
entry. Order ASCO part no. 609027 if required.
On 1000 & 1200 amp. be sure to install auxiliary
cable box if both service and load cables are
entering through the top or bottom of enclosure.
Bus Connections
For large switches use grade 5 hardware to connect bus to
appropriate terminal plates. Wipe off the bus surfaces
before they are joined. If the bus is very dirty, gently
clean the surfaces with a non-flammable solvent. Avoid
touching the cleaned surfaces.
Tighten bolted joints to the torque specified in Table A.
The reliability of the connection depends
on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints
(Grade 5 hardware)
Bolt Diameter
in inches
Tightening Torque
in foot pounds
1/4 7
5/16 12
3/8 20
1/2 50
5/8 95
3/4 155
Controller Ground
A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is
mounted on the enclosure door, a conductive strap must be
used between the enclosure and the door. This connection
provides proper grounding which does not rely upon the
door hinges.
Harnesses
The transfer switch is connected to the left side of the
control panel by a plug-in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on
the transfer switch. Note the control features that are
furnished on this switch. Make the necessary auxiliary
connections by referring to the Wiring Diagram.

Operator’s Manual Series 4000 Automatic Transfer Switch
381333-270D ASCO Power Technologies Page 5
Installation
Engine Starting Contacts
The engine control contact connections (if used) are
located on the transfer switch. Connect signal wires to
appropriate terminals as specified in Table B and shown in
Figures 2, 3 and 4.
Table B. Engine start connections
When normal
source fails
Terminals on
transfer switch
contact closes TB14 and TB15
contact opens TB14 and TB16
Figure 2. Engine starting contact label
and location for 30 through 230 amp.
D–design transfer switches.
Figure 3. Connections to engine starting contact terminal
block for 260 through 1200 amp. J– and H–design
transfer switches.
Figure 4. Connections to engine starting contact terminal
block located on 1600 through 4000 amp. G–design
transfer switches.
COMMON
FEATURE 7
closes to start
FEATURE 8
opens to start
COMMON
FEATURE 14B
closed on emergency
FEATURE 14A
closed on normal
COMMON
FEATURE
14BA
closed on emergency
FEATURE 14AA
closed on normal
Engine Starting
Signals
5 amps, 32 V DC
5 amps resistive 28 V DC
or 120 V AC max.
TS Auxiliary Contacts
Feature 14A & 14B
10 amps, 32 V DC
10 amps 250 V AC
general purpose
Optional
TS Auxiliary Contacts
Feature 14AA & 14BA
10 amps, 32 V DC
10 amps 250 V AC
general purpose
left side of transfer switch
TB Terminal Block
(field connections)
accepts wire range
22–12 AWG
Engine Starting
Signals
5 amps, 32 V DC
5 amps resistive 28 V DC
or 120 V AC max.
TS Auxiliary Contacts
Feature 14A & 14B
10 amps, 32 V DC
10 amps 250 V AC
general purpose
FEATURE 7
closes to start
FEATURE 8
opens to start

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 6 ASCO Power Technologies 381333-270D
Installation
Functional Test
The Functional Test consists of three checks:
□1 - Manual Operation Test, pages 6 and 7
□2 - Voltage Checks, page 8
□3 - Electrical Operation, page 9
Do these checks in the order presented
to avoid damaging the ATS.
Read all instructions on the Wiring Diagram and labels
affixed to the automatic transfer switch. Note the control
features that are provided and review their operation
before proceeding.
1 – Manual Operation Test
A manual operator handle (detachable on 260–4000 amp.
sizes) is provided on the transfer switch for maintenance
purposes only. Manual operation of the transfer switch
must be checked before it is operated electrically.
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
1. Select the appropriate switch design / amp. size and
follow directions for installing and using the handle:
30 through 230 amp. D–design See Figure 5.
The attached maintenance handle is located on the left
side of transfer switch. Grasp the maintenance handle
and turn it with thumb and fingers as shown to
manually operate it. The maintenance handle turns the
opposite direction of the weight.
260 through 1200 amp. J & H–design
See Figures 6 and 7. Attach the manual handle onto the
hub, left side of the operator.
1600 through 4000 amp. G–design See Figure 8.
Install the hub onto the center operator shaft and insert
the manual firmly into the hole in the side of the hub
(spring fully compressed).
4000 amp. F–design See Figure 9.
Insert the manual handle into the hole in the weigh
2. Move the handle as shown to manually operate the
Transfer Switch. The switch should operate smoothly
without binding. If it does not, check for shipping
damage or construction debris
3. Move the handle as shown to manually operate the
Transfer Switch. The switch should operate smoothly
without binding. If it does not, check for shipping
damage or construction debris
For switches rated 260 amps and higher, verify
that the maintenance handle has been removed
and stored properly before proceeding!
Figure 5. Permanently attached maintenance handle and
positions on 30 – 230 amp. D–design transfer switches.
Table C. Maintenance handle positions
A
TS Position Handle Indicators
Normal
E = O
upper contacts open
N = C
lower contacts closed
Emergency
E = C
upper contacts closed
N = O
lower contacts open
Now continue to 2 – Voltage Checks on page 8
up
down

Operator’s Manual Series 4000 Automatic Transfer Switch
381333-270D ASCO Power Technologies Page 7
maintenance
handle
Installation
Figure 6. Location of maintenance handle
on 260
–
1200 amp. J & H
–
desi
g
n transfer switches.
Figure–9. Removable maintenance handle on
4000 amp. F
–
desi
g
n transfer switch
Figure 7. Removable maintenance handle and positions on 260 – 1200 amp. J & H–design transfer switches.
Figure 8. Removable maintenance handle and positions on 1600 – 4000 amp. G–design transfer switches.
Left side of
transfer switch
storage clips
weight
hole
maintenance
handle
UP closes the
Normal source
contacts (lower)
Emergency
contacts
window
indicators
Normal
contacts
Emergency
contacts
contact position
indicators (left side)
Normal
contacts
window
indicators
CLOSED
or OPEN
Insert handle into hole (spring fully compressed)
Gras
p
handle firml
y
with both hands
Slide the hub
onto the shaft
Turn counterclockwise
DOWN to close top
(Emergency) contacts.
Turn clockwise DOWN
to close bottom
(Normal) contacts.
Ois open
C is closed
DOWN closes the
Emergency source
contacts (upper)
handle
hub
frame
contact position
indicators (right side)

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 8 ASCO Power Technologies 381333-270D
Installation
Figure 9. Standard controls and indicators.
2 – Voltage Checks
First check nameplate on transfer switch; the rated voltage
must be the same as normal and emergency line voltages.
Verify that the feeders have been
connected to the proper lugs.
Use extreme caution when using a meter
to measure voltages. Do not touch power
terminals; shock, burns, or death could result!
Perform steps 1 through 6 at the right.
Observe the status lights. See Figure 9.
Black circle means light is on.
White circle means light is off.
* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations. The
Automatic Transfer Switch will respond only to the rated
voltage specified on the Transfer Switch nameplate.
Note: Refer to Section 3 of Group 5 Controller User’s
Guide 381333–126 for how to display the Status of the
ATS and the Voltage and Frequency of each source.
Note: Press the Lamp Test button to verify that all
five lights work.
Now continue to 3 – Electrical Operation on next page.
1
Close the normal source (utility)
circuit breaker. Two left lights
should come on. The normal
source Accepted (upper left) and
the Transfer Switch Position
connected to normal (lower left)
li
g
hts should be on.
2
Carefully use an accurate
voltmeter to check the phase to
phase and phase to neutral
voltages present at the transfer
switch normal source terminals
3
Close the emergency source
(generator) circuit breaker.
(Start generator, if necessary.)
Another light should come on.
The emergency source Accepted
light (upper right) should be on.
4
Carefully use an accurate
voltmeter to check the phase to
phase and phase to neutral
voltages present at the transfer
switch emergency source
terminals. *
5
Carefully use a phase rotation
meter to check the phase
rotation of the emergency
source; it must be the same as
the phase rotation of the normal
source
(
refer to wirin
g
dia
g
ram
)
.
6
Shut down the generator, if
applicable. The emergency
source Accepted light (upper
right) should go off. Then set the
generator’s starting control
switch to automatic. Remove all
meters; close enclosure door.
observe
these lights

Operator’s Manual Series 4000 Automatic Transfer Switch
381333-270D ASCO Power Technologies Page 9
Installation
.
Figure 10. Standard controls and indicators
3 – Electrical Operation
This procedure will check the electrical operation of the
Automatic Transfer Switch. See Figure 10.
Be sure to close the enclosure door before
proceeding to prevent personal injury in case
of electrical system fault.
Transfer Test
Both normal and emergency sources must be available and
the emergency source generator (if used) must be capable
of being started in this procedure.
Perform steps 1 through 5 at the right. Observe the status
lights.
Black circle means light is on.
White circle means light is off.
If the User Controls Locked light is on, the Transfer Test
and Retransfer to Normal buttons will not work until you
unlock them.
How to temporarily unlock the user controls
(if the User Controls Locked light is on)
Press up or down arrow keys on Transfer Control Center
(Group 5 Controller), enter the password, and press Enter
key. The user controls are now unlocked for 5 minutes.
During that time the light will blink.
To permanently unlock or lock the user controls refer
to the Group 5 Controller User’s Guide 381333–126.
Password information and time delay settings are also
provided there.
This completes the Functional Test of the ATS.
1
The two left lights should be on;
the normal source Accepted
(upper left) and the Transfer
Switch Position connected to
normal (lower left) should be on.
2
Press and hold the Transfer Test
button until the generator starts
and runs (this should happen
within 15 sec.). The emergency
source Accepted light (upper
ri
g
ht
)
should come on.
3
Then the transfer switch should
operate to emergency.
The Transfer Switch Position
connected to emergency light
(lower right) should come on and
the connected to normal light
(lower left) should be off.
If Feature2B is used, the transfer
to emergency will occur after the
time dela
y
.
4
The transfer switch should
operate back to normal after
Feature 3A time delay.
For immediate retransfer press
the Retransfer to Normal button.
The Transfer Switch Position
connected to normal light (lower
left) should come on and the
connected to emergency (lower
ri
g
ht
)
li
g
ht should be off.
5
The generator will stop after
Feature 2E time delay (unloaded
running engine cooldown).
The emergency source Accepted
light (upper right) should go off.
observe
these lights

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 10 ASCO Power Technologies 381333-270D
Testing & Service
TRANSFER TEST
Operate the 4000 Series ATS at least once a month by
following the five–step Electrical Operation Transfer
Test procedure on page 9.
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure
high reliability and long life for the 4000 Series ATS. An
annual preventive maintenance program is recommended
ASCO Power Services, Inc. is ASCO Power Technologies
service organization for the United States and Canada.
Call 1-800-800-2726 (ASCO) to request a service call and
information on preventive maintenance agreements.
Annual Inspection Checklist
Hazardous voltage capable of causing
shock, burns, or death is used in this switch.
Deenergize both Normal & Emergency power
sources before performing inspections!
□Clean the ATS enclosure. Brush and vacuum away
any excessive dust accumulation. Remove moisture
with a clean cloth.
□Check the transfer switch contacts. Remove the
transfer switch barriers and check contact condition.
Replace the contacts if they become pitted or worn
excessively. Reinstall the barriers carefully
□Maintain transfer switch lubrication. If the transfer
switch is subjected to severe dust or abnormal
operating conditions, renew factory lubrication on
all movements and linkages. Relubricate the
solenoid operator if the TS coil is replaced. Do not
use oil; order lubrication 625550–001 (Castrol
Endurex R4000 lubricant) for 30–230 amp., or order
lubrication kit 75-100 for 260–4000 amp. sizes.
□Check all cable connections & retighten them.
REPLACEMENT PARTS
Replacement parts are available in kit form. When ordering
parts provide the Serial No., Bill of Material No. (BOM), and
Catalog No. from the transfer switch nameplate. Contact your
local ASCO Power Technologies Sales Office or ASCO Power
Services, Inc.
In the United States and Canada
call 1 – 800 – 800 – ASCO (2726)
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair
purposes only and should not have to be unplugged. If the
controller must be isolated, follow these steps.
Disconnecting the Plugs
Do not unplug the controller
until steps 1a or 1b is completed.
1.Observe the position of the transfer switch.
a. If the transfer switch is in the Normal position, first
place standby engine starting control in the off
position. Second, then open the emergency source
circuit breaker. Third, open the normal source circuit
breaker.
b.If the transfer switch is in the Emergency position, first
open the normal source circuit breaker. Second, place
the engine starting control in the test or run position.
Third, open the emergency source circuit breaker.
2. Separate the two quick disconnect plugs by squeezing
the latches. Do not pull on the harness wires.
Reconnecting the Plugs
Do not unplug the controller
until steps 1a or 1b is completed.
1. Observe the position of the transfer switch.
a. If the transfer switch is in the Normal position, first
be sure that both normal and emergency source
circuit breakers are open. Second, be sure that the
standby engine starting control is still in the off
position.
b. If the transfer switch is in the Emergency position,
first be sure that both normal and emergency source
circuit breakers are open.
2. The two harness plugs and sockets are keyed. Carefully
align the plugs with the sockets and press straight in
until both latches click. Close the door!
3. Restore the two sources in sequence as follows:
a. If the transfer switch is in the Normal position, first
close the normal source circuit breaker. Second, close
the emergency source circuit breaker. Third, place
the standby engine starting control in the automatic
position.
b. If the transfer switch is in the Emergency position,
first close the emergency source circuit breaker.
Second close the normal source circuit breaker.

Operator’s Manual Series 4000 Automatic Transfer Switch
381333-270D ASCO Power Technologies Page 11
Testing & Service
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the
controller is disconnected.
Do not manually operate the transfer switch
until both power sources are disconnected
(all conductors deenergized).
1. Deenergize both the normal and emergency source
conductors (remove fuses or open circuit breakers).
2. Use the maintenance handle to manually operate the
transfer switch to the opposite source. See Manual
Operation on pages 6-7.
3. Then remove the maintenance handle. See page 7.
Verify that the maintenance handle
has been removed before proceeding!
4. If the transfer switch is in the Emergency position
manually start the engine generator and then install
emergency source fuse or close the circuit breaker.
TROUBLE-SHOOTING
Note any optional accessories that may be furnished on
the automatic transfer switch (ATS) and review their
operation. Refer to any separate drawings and/or
instructions that may be packed with the ATS.
Hazardous voltage capable of causing shock,
burns, or death is used in this switch. Do not
touch the power or load terminals of the
transfer switch!
Table D. Trouble-Shooting Checks.
PROBLEM CHECK IN NUMERICAL SEQUENCE
1 OPERATION 2 GEN-SET 3 VOLTAGE
Engine–generator set does
not start when the
Transfer Test button is
pressed and held for 15
seconds or when normal
source fails.
Hold Transfer Test switch 15
seconds or the outage must
be long enough to allow for
Feature 1C time delay plus
engine cranking and starting
Starting control must be in
the automatic position.
Batteries must be charged
and connected. Check
wiring to engine starting
contacts.
-
Transfer switch does not
transfer the load to the
emergency source after
the engine–generator set
starts.
Wait for Feature 2B time
delay to time out (if used)
Generator output circuit
breaker must be closed.
Generator frequency must
be at least 95% of nominal
(57 Hz for a 60 Hz system.)
*
Voltmeter should read at
least 90% of nominal phase
to phase voltage between
transfer switch terminals EA
and EC (or EL1 and EL2 for
2 pole switches
)
. *
Transfer switch does not
transfer the load to normal
source when normal
returns or when the
Transfer Control switch is
released.
Wait for Feature 3A time
delay to time out (if used)
-
Voltmeter should read at
least 90% of nominal phase
to phase voltage between
transfer switch terminals NB
and NC, NC and NA, and
NA and NB (or NL1 and NL2
for 2 pole switches
)
.
Gen. does not stop after
load retransfer to normal
source
Wait for Feature 2E time
delay to time out (if used)
Starting control must be in
the automatic position. -
* These are factory settings. Refer to the Group 5 Controller User’s Guide.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies
sales office or ASCO Power Services, Inc.: in the United States or Canada, call 1–800–800–2726. Furnish the Serial No.,
Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate

Series 4000 Automatic Transfer Switch Operator’s Manual
Page 12 ASCO Power Technologies 381333-270D
©2009 ASCO Power Technologies.
All Rights Reserved.
INDEX
A
auxiliary circuits, 4
C
cable
lugs, 4
spacers, 4
illustration of, 4
catalog number, 2
cleaning, 10
connections
line, 3
controller, 3, 4
disconnecting, 10
see Controller User’s Guide
grounding, 4
E
electrical operation, 9
Emergency Source Accepted light,
8,9
F
frequency, generator, 11
functional test, 6, 7, 8, 9
H
harness, 4
disconnect plugs, 10
help
800–800–ASCO (2726)
I
inspection, 10
installation, 5-9
L
labels,
engine start contacts, 5, 11
rating, cover, 1
lights, 8, 9
lubrication, 10
M
maintenance, preventive, 10
manual load transfer, 11
warning, 11
manual operation, 6, 7
illustration of, 6, 7
warning, 6
N
nameplate, 2
Normal Source Accepted light, 8, 9
O
operation
electrical, 10
manual, 6,7
illustration of, 6,7
warning, 6
sequence of, 11
optional accessories
see Controller User’s Guide
P
parts, 10
phase rotation check, 8
problem, 11
R
rating label, 1
replacement parts, 10
S
settings
see Controller User’s Guide
T
test, functional, 6, 7, 8, 9
time delays, 11
see Controller User’s Guide
Transfer Control selector switch
Transfer Test, 10
Transfer Switch Connected to
Emergency light, 8, 9
Transfer Switch Connected to
Normal light, 8. 9
transfer to emergency, 8
transfer to normal, 8
trouble–shooting, 11
V
voltage checks, 8
voltage, pickup and dropout settings
see Controller User’s Guide
Printed in U.S.A
Other manuals for 4000 series
1
This manual suits for next models
1
Table of contents
Other Asco Switch manuals

Asco
Asco Series 300 User manual

Asco
Asco 7000 Series User manual

Asco
Asco 7000 Series User manual

Asco
Asco 917 User manual

Asco
Asco 7000 Series User manual

Asco
Asco 8215 Installation and operating instructions

Asco
Asco 230 Series User manual

Asco
Asco Series 300 Installation guide

Asco
Asco 7000 Series User manual

Asco
Asco J 4000 Series User manual