Bachmann BlueNet BN3000 Guide

BlueNet PDU
BN3000/3500/5000/7000/7500
Mounting and installation instructions
Read the instructions prior to performing any task!

Bachmann GmbH
Ernsthaldenstrasse 33
70565 Stuttgart
Germany
Telephone: +49 711 86602-0
Fax: +49 711 86602-34
Email: [email protected]
Internet: www.bachmann.com
Bach-30131-DE, 6, en_GB
© Bachmann GmbH 2017
01.03.2017BlueNet PDU BN3000/3500/5000/7000/75002

These instructions facilitate the safe and efficient mounting and
installation of the BlueNet power distribution unit (hereinafter called
“PDU”. These instructions constitute an integral part of the PDU
and must be retained. If the PDU is transferred to a third party,
these instructions must also be transferred with the PDU.
Persons who are entrusted to work on the PDU must have care-
fully read and understood these instructions prior to starting any
work. Compliance with all the safety information and instructions
set out in these instructions is an essential prerequisite for safe
operation.
The illustrations in these instructions are provided for the purpose
of a basic understanding and may deviate from the actual version.
The contents of these instructions are protected by copyright. Their
use is permitted in conjunction with the mounting and installation of
the PDU. Any use that exceeds this is not permitted, unless the
written approval of Bachmann GmbH has been obtained.
The software contains components that are protected by copyright
and are licensed under various license models. A copy of the terms
of the licences is included with the PDU and can be accessed
using the web interface for the PDU.
In addition to these instructions, the following additional documents
apply:
nOperating instructions
nData sheet
nSafety information
Telephone: +49 711 86602-888
E-mail: [email protected]
About the mounting and installa-
tion instructions
Copyright
Software licenses
Other applicable documents
Customer service
Supplemental directives
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 3

Table of contents
1 Overview.............................................................................. 5
1.1 Overview of the PDU.................................................... 5
1.2 Short description........................................................... 8
1.3 Displays and controls.................................................... 8
1.4 Communication........................................................... 11
1.5 Scope of delivery........................................................ 12
1.6 Optional accessories.................................................. 13
2 Explanation of symbols.................................................... 14
3 Personnel requirements and responsibilities................ 15
4 Unpacking the PDU........................................................... 16
5 Installing and connecting the PDU.................................. 17
5.1 Safety instructions for the installation......................... 17
5.2 Requirements of the installation location.................... 17
5.3 Installing the PDU....................................................... 17
5.3.1 Overview.................................................................. 17
5.3.2 Installing the PDU with the mounting brackets........ 19
5.3.3 Installation with plug-in brackets via the rear of the
PDU......................................................................... 20
5.3.4 Installation with plug-in brackets via the sides of the
PDU......................................................................... 21
5.3.5 Installation with the mounting solution in the rack... 22
5.4 Connecting the PDU to the power supply................... 24
5.5 Connecting the network cable.................................... 24
5.6 Connecting the sensors.............................................. 25
5.7 Cascading the PDUs.................................................. 25
6 Putting the PDU into operation........................................ 28
6.1 Adjusting the display orientation................................. 28
6.2 Querying the network address of the PDU................. 29
7 Operation........................................................................... 31
8 Troubleshooting................................................................ 32
9 Cleaning the PDU.............................................................. 33
10 Dismantling and disposing of the PDU........................... 34
10.1 Dismantling............................................................... 34
10.2 Disposal.................................................................... 34
11 Technical data................................................................... 35
12 Index................................................................................... 36
Table of contents
01.03.2017BlueNet PDU BN3000/3500/5000/7000/75004

1 Overview
1.1 Overview of the PDU
Functions Measurement per
phase
Measurement per
socket
Identification Switching
Product name
BN3000 x – – –
BN3500 x x x –
BN5000 – – x x
BN7000 x – x x
BN7500 x x x x
Fig. 1: Product overview (16 amp version)
AFitting slots for plug-in bracket
BCEE connector plug
CSockets
DConnector panel for GPIO, network, Modbus
and sensors
EControl panel
Overview of functions
Example of a 16-amp version
Overview
Overview of the PDU
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 5

Fig. 2: Product overview (32 amp version)
AFitting slots for plug-in bracket
BCEE connector plug
CSockets
DConnector panel for GPIO, network, Modbus
and sensors
EControl panel
FCircuit breakers
ASensor port S1 (to connect a sensor via a cat 5e cable or to
connect to a serial console)
BModbus port M1 (to connect a Slave PDU via a cat 5e cable)
CPort M2 (for connecting future applications)
DSensor port S2 (to connect a sensor via a CAT5e cable)
EGPIO port (supported on the PDU in software version V2.01
and higher)
FLAN port
GUSB port
ASensor port S1 (to connect a sensor via a cat 5e cable)
BModbus port M1 (to connect a Master PDU and upstream
Slave PDUs via a cat 5e cable)
CModbus port M2 (to connect a Slave PDU via a cat 5e cable)
DSensor port S2 (to connect a sensor via a CAT5e cable)
EGPIO port (supported on the PDU in software version V2.01
and higher)
Example of a 32-amp version
Connector panel for a Master PDU
Fig. 3: Connector panel (Master PDU)
Connector panel for a Slave PDU
Fig. 4: Connector panel (Slave PDU)
Overview
Overview of the PDU
01.03.2017BlueNet PDU BN3000/3500/5000/7000/75006

Fig. 5: Control panel
AStatus LED
BOperating button 1
CDisplay
DOperating button 2
EOperating button 3
FOperating button 4
GModbus LED
Fig. 6: Overview of the fitting options for the PDU
AFitting slots for plug-in bracket
BAttachment for the mounting bracket
CAttachment for the mounting solution in the
rack
DPlug-in bracket for mounting the PDU via the
back (2 each)
EPlug-in bracket for mounting the PDU via the
sides (2 each)
FMounting bracket (x 2)
Control panel
Attachment options at the back
Overview
Overview of the PDU
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 7

1.2 Short description
The power supply of a data centre can be monitored and controlled
remotely using the PDU. The PDU can be set up for single-phase
or three-phase systems. The individual phases can be distin-
guished by their colours. The PDU is supplied with electricity via a
CEE plug.
The current, power (effective, apparent and reactive power), power
consumption, voltage and frequency of all phases are monitored
using the PDU. This enables the efficient planning of resources
and the issuing of an alarm in the event of a fault. The PDU is
designed for a power range of 3.6 to 22 kW.
The PDU is integrated into the company network via the LAN port
(only available on the master PDU). Up to 11 Slave PDUs can be
cascaded with a Master PDU via the Modbus port.
The PDU can be operated locally via the display, via SNMP access
or with a web browser over a network, and the HTTP, HTTPS,
SSH, SNMP and Modbus-TCP protocols can be used.
The PDU is made of a sturdy aluminium profile and is installed
directly into the rack.
Depending on the type, the PDU has a range of equipment fea-
tures such as safety sockets or sockets for IEC320 C14 and C20
and external sensors (temperature/air humidity).
A connector inserted into the PDU can be secured with plug inter-
locks (C13/C19).
1.3 Displays and controls
The PDU can be operated locally using the display with the control
buttons:
nDisplay of system data (hardware and software version,
serial number, MAC address (only for Master PDUs) and item
no.)
nDisplay of the measured data
nSetting of the duration (only for Master PDUs) and orientation
of the display
nDisplay and adjustment of the network configuration as well as
enabling or disabling the DHCP protocol (only for Master
PDUs)
nSetting for Modbus (only for Slave PDUs)
Display with control buttons
Fig. 7: Display with control buttons
Overview
Displays and controls
01.03.2017BlueNet PDU BN3000/3500/5000/7000/75008

The status LED (Fig. 8/Ⓐ) indicates the status of the PDU. Pos-
sible statuses are:
Colour Light Status
Green Continuously green All measured data is OK and the status of
the individual connected loads and sensors
are OK
Orange Continuously orange The measurement monitor issues a warning
(based on all the measured data of the PDU
and sensors)
Red Continuously red The measurement monitor issues an alarm
(based on all the measured data of the PDU
and sensors) or the connection to a sensor
is interrupted
Orange Continuously orange PDU starting up
White Continuously white Performing factory reset (after releasing the
pressed buttons)
Purple 500 ms off, 500 ms purple An update of a PDU is in progress
Purple, red 500 ms off, 500 ms purple, 500 ms off,
500 ms red
Error during the update of a PDU
The status LED (Fig. 9/Ⓐ) indicates the status of the PDU. Pos-
sible statuses are:
Starting process
Colour Light Status
Blue, orange 900 ms blue, 100 ms orange Connection to Master PDU not yet estab-
lished or lost
Green Continuously green Connection to Master PDU present
Master PDU status LED
Fig. 8: Master PDU status LED
Slave PDU status LED
Fig. 9: Slave PDU status LED
Overview
Displays and controls
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 9

Colour Light Status
Blue, purple 500 ms blue, 500 ms purple An update of a PDU is in progress
Blue, purple, red 500 ms blue, 500 ms purple, 500 ms
blue, 500 ms red
Error during the update of a PDU
In operation
Colour Light Status
Orange 900 ms off, 100 ms orange Connection to Master PDU not yet estab-
lished or lost
Green, red 500 ms off, 100 ms green, 500 ms off,
100 ms red
Connection to Master PDU present, internal
communication problems have occurred
Green Continuously green Connection to Master PDU present, internal
communication functioning
Purple 500 ms off, 500 ms purple An update of the internal modules of a PDU
is being carried out
Purple, red 500 ms off, 500 ms purple, 500 ms off,
500 ms red
Error during update of the internal modules
of a PDU
Red Continuously red The measurement monitor is issuing an
alarm
Orange Continuously orange The measurement monitor is issuing a
warning
The Modbus LED (Fig. 10/Ⓐ) indicates the activity of the PDUs
connected to the Modbus.
The Modbus LED lights up continuously green. If there is commu-
nication between the Master and a Slave PDU, the Modbus LED
lights up yellow.
Slave PDU Modbus LED
Fig. 10: Slave PDU Modbus LED
Overview
Displays and controls
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750010

The status LEDs (only available on the BN3500/5000/7000/7500)
display the status of the loads connected to the sockets.
See the operating instructions for details on the status
LEDs on the sockets.
1.4 Communication
Temperature sensors, combination sensors (temperature, air
humidity and dew point) and GPIO modules can be connected to
the PDU via the ports for sensors. The values can be called up
under "Status è External Sensors" in the web interface.
Individual PDUs can be connected to each other with the Modbus
port. This way, up to 11 Slave PDUs can be cascaded with one
Master PDU and managed using the web interface. The first Slave
PDU is connected to Modbus port M1 of the Master PDU via
Modbus port M1. Further Slave PDUs are connected from their
Modbus port M1 with the Modbus port M2 of the Slave PDU con-
nected upstream.
The PDU can be integrated into the network via the LAN port. The
data transfer rate is controlled using the network.
There is a USB port on the PDU next to the display and control
panel. It is for updating the software.
The GPIO port is designed as an RJ-12 socket. It has a potential-
free digital input contact and a potential-free relay contact as a
changeover contact.
Electrical specifications for GPIO port
Port type RJ-12
Output Max. contact voltage 30 V DC/max.
500 mA
Input 5 – 30 V
Status LED on the sockets
(only on BN3500/5000/7000/7500)
Fig. 11: Status LEDs on the sockets
Connection for sensors S1/S2
Connection for Modbus M1/M2
LAN port (10/100 Mbit/s)
USB port for software updates
(only on the Master PDU)
GPIO port
Overview
Communication
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 11

Contact Function
Pin 1 Common terminal (COM)
Pin 2 Normally closed contact
Pin 3 Normally open contact
Pin 4 Potential-free digital input contact
Pin 5
Pin 6 Not assigned
Output: Pin 1, Pin 2 and Pin 3 serve as changeover contacts. Pin 1
is the common terminal (COM), Pin 2 is the normally closed con-
tact and Pin 3 is the normally open contact. Pin 1 is connected to
Pin 2 in the switched-off state. When the relay switches, Pin 1 is
connected to the normally open contact Pin 3.
The GPIO port (RJ-12) is supported on the PDU in
software version V2.01 and higher.
1.5 Scope of delivery
Fig. 12: Scope of delivery
The scope of delivery includes:
nPDU (Fig. 12/Ⓐ)
nTwo plug-in brackets for mounting the PDU via the back
(Fig. 12/Ⓑ)
nTwo plug-in brackets for mounting the PDU via the sides
(Fig. 12/Ⓒ)
nTwo mounting brackets (Fig. 12/Ⓓ)
nTwo sets of plug interlocks (C13/C19) (Fig. 12/Ⓔ)
nMounting and installation instructions
nSafety information
PDU
Overview
Scope of delivery
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750012

1.6 Optional accessories
The temperature, air humidity and dew point at the installation
location of the PDU can be measured via a temperature sensor or
a combination sensor for temperature and humidity. The values
can be displayed on the display and on the web interface. The
CAT5e cable required to connect the sensors is included.
The GPIO module can be used to connect the PDU to external
devices in order to read out input statuses and to switch outputs.
Temperature and combination
sensor
GPIO module
Overview
Optional accessories
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 13

2 Explanation of symbols
Safety information is indicated by symbols in these instructions.
The safety information is introduced by signal words that express
the nature of the danger.
DANGER!
This combination of symbol and signal word indicates
that there is an imminent danger that will result in
death or serious injury if it is not avoided.
WARNING!
This combination of symbol and signal word indicates
that there is a potential danger that can result in death
or serious injury if it is not avoided.
NOTICE!
This combination of symbol and signal word indicates
that there is a potential danger that can result in
damage to property if it is not avoided.
This symbol highlights useful tips and recommenda-
tions as well as information for efficient and trouble-
free operation.
The following markings are used to highlight specific instructions,
results, lists, references and other elements in these instructions:
Marking Explanation
Step-by-step instructions
ðResults of the steps of an instruction
References to sections in these instructions
and to other applicable documents
Items in a list without a specified sequence
Safety information
Tips and recommendations
Explanation of symbols
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750014

3 Personnel requirements and responsibilities
WARNING!
Risk of injury if the personnel is insufficiently
qualified!
If unqualified personnel carry out the installation work
on the PDU, serious injuries or substantial damage to
property can be caused.
– The installation and the connection of the PDU
must be carried out by an IT specialist.
– Defective components on the PDU must be
repaired by a qualified electrician.
Only permit persons to work on the PDU who can be expected to
carry out their work reliably. Persons whose capacity to react is
impaired, e.g. through drugs, alcohol, or medication, cannot be
permitted to perform such work.
In these instructions, the following personnel qualifications are
required for the various tasks listed below:
IT specialist
IT specialists have obtained specialist training or the appropriate
experience in dealing with IT systems and have a basic knowledge
of electrical engineering.
Due to their specialist training, IT specialists are in a position to
assess the consequences of their actions in dealing with the
system as well as its components and the potential dangers in
respect thereof and are able to avoid these.
The duties of an IT specialist include the following tasks:
nSetting up hardware and software systems
nInstalling updates
nMaintenance work on the PDU
nAdministration of the PDU via the web interface
nSystem diagnostics
Qualified electrician
Due to their professional training, knowledge and experience, as
well as their knowledge of the relevant standards and regulations,
qualified electricians are capable of working on electrical installa-
tions and independently identify and avoid potential dangers.
Qualified electricians are specifically trained for the working envi-
ronment in which they work and know the relevant standards and
regulations.
Personnel requirements and responsibilities
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 15

4 Unpacking the PDU
nUnpack the delivery and check its completeness and integrity.
If there is a defect, contact Bachmann GmbH immediately.
nIf possible, keep the packaging of the PDU so that the PDU
can be safely stored and transferred in the future. Dispose of
the packaging material that is no longer required in a manner
that is environmentally responsible.
Unpacking
Unpacking the PDU
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750016

5 Installing and connecting the PDU
5.1 Safety instructions for the installation
NOTICE!
Risk of damage due to improper fitting and instal-
lation!
Improper fitting and installation can cause substantial
damage to property.
– All the installation work must be carried out by an
IT specialist.
– Only install the PDU while it is de-energised.
– Before starting the work, ensure that you have suf-
ficient room for the installation.
– Ensure that installation area is clean and tidy.
– Install the components properly and lay the con-
nectors and cables in a manner that is safe.
– Secure the components so that they cannot fall
down or over.
5.2 Requirements of the installation location
nThere must be enough space in the rack to install the PDU.
nThe PDU may only be operated within the environmental con-
ditions set out in the technical specifications.
nThe the PDU may not be used in potentially explosive atmos-
pheres.
nThe PDU may not be subjected to vibrations.
nA location for the installation must be selected that does not
have excessive humidity, high temperatures, sources of elec-
tromagnetic interference, moisture, solvents, flammable gases,
dust or vapours.
nThere must be sufficient lighting.
nFire protection measures must be in place.
5.3 Installing the PDU
5.3.1 Overview
There are four options for installing the PDU in the rack:
nInstallation with mounting brackets (
Ä
Chapter 5.3.2 "Installing
the PDU with the mounting brackets" on page 19)
nInstallation with plug-in brackets via the rear of the PDU
(
Ä
Chapter 5.3.3 "Installation with plug-in brackets via the rear
of the PDU" on page 20)
Improper installation
Overview of the fitting options for
the PDU
Installing and connecting the PDU
Installing the PDU > Overview
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 17

nInstallation with plug-in brackets via the sides of the PDU
(
Ä
Chapter 5.3.4 "Installation with plug-in brackets via the
sides of the PDU" on page 21)
nInstallation with the mounting solution in the rack (
Ä
Chapter
5.3.5 "Installation with the mounting solution in the rack"
on page 22)
Fig. 13: Overview of the fitting options for the PDU
AFitting slots for plug-in bracket
BAttachment for the mounting bracket
CAttachment for the mounting solution in the
rack
DPlug-in brackets for mounting the PDU via the
back
EPlug-in brackets for mounting the PDU via the
sides
FMounting bracket
The following tools are required for the installation:
nPhillips screwdriver
nTorx screwdriver (IP8)
Tools required
Installing and connecting the PDU
Installing the PDU > Overview
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750018

5.3.2 Installing the PDU with the mounting brackets
Personnel: nIT specialist
1. Fit the mounting brackets (Fig. 14/Ⓑ) onto the attachments
at the top and bottom of the PDU (Fig. 14/Ⓑ).
2. Hold the PDU in the desired position against the rack and
mark the position of the mounting holes.
3. Remove the mounting brackets (Fig. 15/Ⓐ) from the PDU
and screw them onto the rack in the positions marked.
Fig. 14: Installation with mounting
brackets
APDU
BMounting bracket
Fig. 15: Rack with mounting brackets
Installing and connecting the PDU
Installing the PDU > Installing the PDU with the mounting brackets
01.03.2017 BlueNet PDU BN3000/3500/5000/7000/7500 19

4. Fit the PDU onto the mounting brackets (Fig. 16).
5.3.3 Installation with plug-in brackets via the rear of the PDU
Personnel: nIT specialist
1. Insert the plug-in brackets into the rear slots on both sides
(Fig. 17).
2. Position the PDU in the rack.
Fig. 16: Rack with PDU
Fig. 17: Fitting the plug-in brackets
Installing and connecting the PDU
Installing the PDU > Installation with plug-in brackets via the rear of the PDU
01.03.2017BlueNet PDU BN3000/3500/5000/7000/750020
Other manuals for BlueNet BN3000
1
This manual suits for next models
4
Table of contents
Other Bachmann Power Distribution Unit manuals
Popular Power Distribution Unit manuals by other brands

Minuteman
Minuteman RPM30241EV6 user manual

Synergy Global Technology
Synergy Global Technology RA5024-520-20A-L520 General information

BS
BS 89 H Series instruction manual

pizzato
pizzato FS 18 Seies quick start guide

Tripp Lite
Tripp Lite PDUMNV20/NET owner's manual

Tripp Lite
Tripp Lite PDUMH15AT owner's manual