Basler BE1-50/51B-225 User manual

INSTRUCTION MANUAL
FOR
OVERCURRENT RELAYS
BE1-50/51B-214 AND BE1-50/51B-225
Publication: 9252000994
Revision: G 03/2001
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - Introduction i
W A R N I N G !
To avoid personal injury or equipment damage, only qualified
personnel should perform the procedures presented in this manual.
INTRODUCTION
This manual provides information concerning the operation and installation of the BE1-50/51B-214 and BE1-
50/51B-225 Overcurrent Relays. To accomplish this, the following is provided.
Specifications
Functional description
Mounting information
Setting procedure/example
www . ElectricalPartManuals . com

ii BE1-50/51B-214/-225 - Introduction
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIALUSE,SUBJECTTORETURNONREQUEST,ANDWITHTHEMUTUAL
UNDERSTANDINGTHATITWILLNOTBEUSEDINANYMANNERDETRIMENTALTO
THE INTEREST OF BASLER ELECTRIC COMPANY.
First Printing: July 1995
Printed in USA
© 1995 - 2001 Basler Electric Co., Highland, IL 62249
March 2001
Itisnottheintentionofthismanualtocoveralldetailsand variationsinequipment,nordoesthis
manual provide data for every possible contingency regarding installation or operation. The
availability and design of all features and options are subject to modification without notice.
Should further information be required, contact Basler Electric Company, Highland, Illinois.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, [email protected]
PHONE 618-654-2341 FAX 618-654-2351
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - Introduction iii
$$#
SECTION 1 GENERAL INFORMATION ....................... 1-1
Description ........................................................ 1-1
Application ........................................................ 1-1
Features ........................................................ 1-2
Advantages ........................................................ 1-2
Specifications ........................................................ 1-2
Characteristic Curves ................................................. 1-10
SECTION 2 HUMAN MACHINE INTERFACE ................... 2-1
SECTION 3 FUNCTIONAL DESCRIPTION ..................... 3-1
General ........................................................ 3-1
Functional Description ................................................. 3-1
Sensing Input ..................................................... 3-1
Power Supply ..................................................... 3-1
Instantaneous Signal ............................................... 3-1
Time Signal ....................................................... 3-1
Microprocessor .................................................... 3-1
Power-Off Sensing ................................................. 3-1
Outputs ........................................................ 3-2
SECTION 4 INSTALLATION ................................ 4-1
General ........................................................ 4-1
Dielectric Test ........................................................ 4-1
Mounting ........................................................ 4-1
Factory Settings ...................................................... 4-1
Installation ........................................................ 4-1
Application Coordination ................................................ 4-2
Connections ........................................................ 4-3
AC Input Connections .............................................. 4-3
DC Control Connections ............................................ 4-4
SECTION 5 TESTING ...................................... 5-1
General ........................................................ 5-1
Dielectric Test ........................................................ 5-1
Operational Test Procedure ............................................. 5-1
Test Equipment Required ........................................... 5-1
Pickup and Timing Test Setup ........................................ 5-2
Target Operational Test Setup ........................................ 5-2
Test Procedure, Models BE1-50/51B-214 (Five Ampere Sensing Input) ....... 5-3
Test Procedure, Models BE1-50/51B-225 (One Ampere Sensing Input) ....... 5-5
Setting the Relay ...................................................... 5-8
Periodic Tests ........................................................ 5-8
General .......................................................... 5-8
Periodic Test ...................................................... 5-8
www . ElectricalPartManuals . com

iv BE1-50/51B-214/-225 - Introduction
CONTENTS- Continued
SECTION 6 MAINTENANCE .............................6-1
General .............................................................6-1
In-House Repair ......................................................6-1
Storage .............................................................6-1
Periodic Tests ........................................................6-1
General ..........................................................6-1
Periodic Test ......................................................6-1
SECTION 7 MANUAL CHANGE INFORMATION .............7-1
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-1
SECTION 1 • GENERAL INFORMATION
DESCRIPTION
BE1-50/51B-214andBE1-50/51B-225 OvercurrentRelaysaredirectreplacementsforGeneralElectric,IAC
relays. Specific IAC relays by model number are shown in Table 1-1. To replace an existing IAC relay,
perform the following steps.
• Select the desired relay settings on your new BE1-50/51B-214/-225 relay.
• Remove the existing IAC relay.
• Attach the cover adapter to the existing case.
• Insert the new BE1-50/51B-214/-225 relay.
• Reinstall the existing connection plug.
• Install the new Basler Electric cover.
BE1-50/51B-214/-225 Overcurrent Relays are self-powered,microprocessor based, non-directional phase
or ground relays that monitor the magnitude of a single phase ac current to provide accurate instantaneous
and timeovercurrentprotectionfor 50hertz or 60 hertz power systems. One modelcovers ten popular time
characteristics and a wide range of pickup settings.
Table 1-1. G.E. IAC Relays Suitable For Direct Replacement
IAC Model Number Curve Type
12IAC51A***A Inverse
12IAC51B***A Inverse with Instantaneous
12IAC53A***A Very Inverse
12IAC53B***A Very Inverse with Instantaneous
12IAC55A***A Short Time
12IAC55B***A Short Time with Instantaneous
12IAC66A**A Long Time
12IAC66B**A Long Time with Instantaneous
12IAC77A***A Extremely Inverse
12IAC77B***A Extremely Inverse with Instantaneous
NOTE: * = Any digit covering all pickup ranges and 50 hertz or 60 hertz models.
APPLICATION
BE1-50/51B-214/-225 Overcurrent Relays with a wide range of pickup settings and front panel selectable
timecharacteristicspermitapplicationsinvolving coordinationwithfuses,reclosers,coldloadpickup,motor
starting, and fixed time requirements. Also, a field selectable, integrating reset function that simulates the
disk reset of electromechanical relays or instantaneous reset to avoid ratcheting makes the BE1-50/51B-
214/-225 Overcurrent Relays ideal for almost every application.
www . ElectricalPartManuals . com

1-2 BE1-50/51B-214/-225 - General Information
Features
BE1-50/51B-214/-225 Overcurrent Relays have the following standard features.
• Independent time and instantaneous elements.
• A secure method to manually trip the breaker at the relay front panel.
• Direct reading front panel controls.
• Minimum pickup setting for safety during installation.
• Time characteristics extend to a pickup multiple of 40.
• Rugged draw-out construction with steel case.
• Magnetic latching targets retain indication without power.
• Built-in accuracy eliminates internal adjustments.
• Minimum transient overreach.
• Field selectable characteristic curve selection similar to either GE IAC or ABB type curves.
• Field selectable instantaneous or integrating reset.
• Field selectable 50 or 60 hertz operation.
• Field selectable 0.0 or 0.1 second, fixed, instantaneous delay.
• One ampere and five ampere sensing input models.
Internal switches provide for selecting system operating frequencies of 50 or 60 hertz, instantaneous
element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or ABB type
curves, and instantaneous or integrating reset characteristics. Switch location and description is
provided in Section 2. Table 1-2 provides model number to nominal current sensing input information.
Table 1-2. Model Number To Nominal Current Sensing Input
Model Number Nominal Current
Sensing Input
Sensing Input Range (Amperes)
TIME Increments INST Increments
BE1-50/51B-214 5 amperes 0.5 - 15.9 0.1 1.0 - 99.0 1.0
BE1-50/51B-225 1 ampere 0.1 - 3.18 0.02 0.2 - 19.8 0.2
Advantages
BE1-50/51B-214OvercurrentRelayshavemanyadvantagesoverotherovercurrentrelays. Thefiveprimary
advantages are:
• Time characteristics are defined by equations and graphs.
• Field selectable time characteristics.
• Very low burden extends the linear range of the CTs.
• Self powered from the sensed current.
• Continuous automatic calibration.
BE1-50/51B-214 Overcurrent Relays may be tested without removing the relay from the case. Shorting
contacts are provided for all current inputs when the connectionplugs or relay chassis is removed from the
relay case.
SPECIFICATIONS
BE1-50/51B-214/-225 Overcurrent Relays have the following features and capabilities.
Current Sensing Input
1 Ampere Unit
Continuous current: 2.8 amperes. One second current: 80 amperes.
5 Ampere Unit
Continuous current: 14 amperes. One second current: 400 amperes.
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-3
TIME PICKUP Range Setting theTIMEPICKUP to the minimum pickup (0.5 ampere), places the
relay in the most sensitive state and may be used as a safety setting.
1 Ampere Unit
0.1 to 3.18 amperes in 0.02 ampere steps.
5 Ampere Unit
0.5 to 15.9 amperes in 0.1 ampere steps.
TIME Dropout Dropout occurs at 95% of pickup value.
TIME PICKUP
Accuracy The timing accuracy is the sum of+1 cycle +2%. This is over the range of
1.3 to 40 times tap. This accuracy is for a given measured multiple oftap.
The measurement ofthe multipleof taphas an accuracy that is the sum of
+2% +25 milliampere for 5 ampere units and +2% +5 milliamperes for 1
ampere units.
Example: (5 ampere unit)
PU Setting: 5 amperes
Current Applied: 6.5 amperes
+ Multiple Tolerance: 6.655 amperes
- Multiple Tolerance: 6.345 amperes
Time Curve: E
Time Dial: 5.0
Minimum Time Using 6.655 amperes: 46.5470 seconds
Maximum Time Using 6.345 amperes: 61.3968 seconds
Curve Time Using 6.5 amperes: 53.1800 seconds
TIME PICKUP
Accuracy
1 Ampere Unit
±2% ±5 milliamperes at or above 0.1 ampere settings.
5 Ampere Unit
±2% ±25 milliamperes at or above 0.5 ampere settings.
Frequency Response A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
TIME DIAL Range
1 Ampere Unit
0.0 to 9.9, in 0.1 steps.
5 Ampere Unit
0.0 to 9.9, in 0.1 steps.
INST PICKUP Range Setting the INST PICKUP to the minimum pickup (1.0 ampere), places the
relay in the most sensitive state and may be used as a safety setting.
1 Ampere Unit
0.2 to 19.8 amperes in 0.2 ampere steps.
5 Ampere Unit
1 to 99 amperes in 1 ampere steps.
INST Dropout Dropout occurs at 95% of pickup value.
INST PICKUP
Accuracy
1 Ampere Unit
±2% ±5 milliamperes at or above 0.2 ampere settings.
5 Ampere Unit
±2% ±25 milliamperes at or above 1.0 ampere settings.
Frequency Response A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
www . ElectricalPartManuals . com

1-4 BE1-50/51B-214/-225 - General Information
Figure 1-1. Device Burden Characteristics
INSTTransientResponse Lessthan10%overreachwithsystemtimeconstantsupto 40 milliseconds
Burden Burden is non-linear. (Figure 1-1 illustrates the device burden.)
1 Ampere Unit
At 0.1 amperes, Z = 120 ohms. At 1.0 ampere, Z = 5 ohms.
5 Ampere Unit
At 0.5 amperes, Z = 4.8 ohms. At 5.0 amperes, Z = 0.2 ohms.
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-5
Figure 1-2. Harmonic Rejection
Harmonic Response Harmonic rejection is illustrated in Figure 1-2.
Figure 1-2 shows that a relay set for one ampere pickup would pickup at
0.96 ampere on a current containing 40% seventh harmonic. This
corresponds to a ten-to-one rejection ratio. Other conditions may be
evaluated in the same manner.
INST Characteristics Instantaneous characteristic curves are similar to standard
electromechanical instantaneous units. However, the time to trip for
applications where the initial current through the relay is less than 0.4
ampere (5 ampere relay) or 0.08 ampere (1 ampere relay) may be slightly
longer. This may occur on a very lightly loaded circuit or when the relay is
providing ground protection and is connected to measure neutral current.
Figure 1-3 shows the instantaneous characteristic curves for maximum
time to trip.
An additional fixed delay of 0.1 second may be added with internal switch
SW3-2. Thisdelayappliestobothphaseandgroundapplications. Closing
switch SW3-2 provides an additional delay of 0.1 second. Section 2
illustrates the location of SW3.
The instantaneous element in BE1-50/51B-214/-225 relays may be set
lowerthantheinstantaneouselementinIACrelaysandstillhavethesame
reach. This is because the BE1-50/51B-214/-225 instantaneous element
effectively eliminates the fault current transient overreach components.
When calculating BE1-50/51B-214/-225 relay instantaneous element
settings, calculate the symmetrical value without any adder for transient
overreach.
www . ElectricalPartManuals . com

1-6 BE1-50/51B-214/-225 - General Information
Figure 1-3. Instantaneous Characteristic Curves
TT
AD
MN
C
BD
K
Time Characteristics Nine inverse time functions and one fixed time function canbe selected by
afrontpanelswitch. Characteristiccurvesforthe inverse anddefinitetime
functions are defined by the following equation.
Where: TT= Time to trip in seconds
D = TIME DIAL setting
M = Multiple of PICKUP setting
A, B, C, N, K = Constants for the particular curve
Refer to Tables 1-3 or 1-4 for the time characteristic curve constants.
Constants have been selected to conform to the characteristics of
electromechanical relays over a range of pickup multiples from 1.3 to 40.
Values of the constants are provided for use in computer relay setting
programs. Timing accuracy is ±1 cycle ±2% of time to trip.
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-7
Time Characteristics - The fixed time characteristic provides delays of 0.0 to 9.9 seconds
Continued corresponding to the time dial setting. The time set is constant over a
range of pickup multiples from 1.0 to 40. Accuracy is ±1 cycle ±2% of time
to trip for time dial settings of 0.1 and greater.
Table 1-3. Time Characteristic Curve Constants With SW3-3 Open (OFF)
Curve Type Figure Constants
BE1 Similar To Number A B C N K R
S ABB CO-2 1-5 0.2663 0.03393 1.000 1.2969 0.028 0.500
L ABB CO-5 1-6 5.6143 2.18592 1.000 1.000 0.028 15.750
D ABB CO-6 1-7 0.4797 0.21359 1.000 1.5625 0.028 0.875
M ABB CO-7 1-8 0.3022 0.12840 1.000 0.5000 0.028 1.750
I ABB CO-8 1-9 8.9341 0.17966 1.000 2.0938 0.028 9.000
V ABB CO-9 1-10 5.4678 0.10814 1.000 2.0469 0.028 5.500
E ABB CO-11 1-11 7.7624 0.02758 1.000 2.0938 0.028 7.750
B BS142-B* 1-12 1.4636 0.00000 1.000 1.0469 0.028 3.250
C BS142-C* 1-13 8.2506 0.00000 1.000 2.0469 0.028 8.000
F None** None 0.0000 1.00000 0.000 0.0000 0.000 1.000
* Curves B and C are defined in British Standard BS142 and IEC 255-4 (International
Electrotechnical Commission)
** Fixed time from 0.1 to 9.9 seconds.
BE1 Curve Types:
S = Short Inverse V = Very Inverse
L = Long Inverse E = Extremely Inverse
D = Definite Time B = BS142 Very Inverse
M = Moderately Inverse C = BS142 Extremely Inverse
I = Inverse F = Fixed Time
Table 1-4. Time Characteristic Curve Constants With SW3-3 Closed (ON)
Curve Type Figure Constants
BE1 Similar To Number A B C N K R
S GE IAC 55 1-14 0.0286 0.0208 1.000 0.9844 0.028 0.0940
L GE IAC 66 1-15 2.3955 0.00002 1.000 0.3125 0.028 7.8001
D ABB CO-6 1-7 0.4797 0.21359 1.000 1.5625 0.028 0.8750
M ABB CO-7 1-8 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I GE IAC 51 1-16 0.2747 0.1042 1.000 0.4375 0.028 0.8868
V GE IAC 53 1-17 4.4309 0.0991 1.000 1.9531 0.028 5.8231
E GE IAC 77 1-18 4.9883 0.0129 1.000 2.0469 0.028 4.7742
B BS142-B* 1-12 1.4636 0.00000 1.000 1.0469 0.028 3.2500
C BS142-C* 1-13 8.2506 0.00000 1.000 2.0469 0.028 8.0000
F None** None 0.0000 1.00000 0.000 0.0000 0.000 1.0000
www . ElectricalPartManuals . com

1-8 BE1-50/51B-214/-225 - General Information
TR
RD
M
2
1
TT
AD
MN
C
BD
K
Time To Trip
TR
RD
M
2
1
Time To Rese
t
IntegratingTimeReset Resetbeginswhenthecurrentdropsbelow95%ofpickup. Integrating reset
Characteristic simulates the disk reset of electromechanical relays. BE1-50/51B-214/-
225 relays provide the integrating reset function even when input current
falls to zero.
Integrating reset characteristics are defined by thefollowing equation and
showninFigure1-4. EquationconstantsareprovidedinTables1-2or1-3.
Where: TR= Time to reset in seconds
R = Constant for the particular curve
D = TIME DIAL setting
M = Current in multiples of PICKUP setting during reset
Time characteristic curve equation.
Where: D = TIME DIAL setting
M = Multiple of PICKUP setting
Reset characteristic curve equation.
Instantaneous Time Reset Resets within 16 milliseconds when current drops below pickup.
Characteristic
Target Indicators Magnetically latched, manually reset targets indicate that current of 0.2
amperes or greater was present in the trip circuit. Target coil resistance is
less than 0.1 ohms and operate time is less than one millisecond. See
50/51 Output specifications for maximum current rating.
50/51 Output Output contacts are surge protected and rated as follows:
Resistive:
120/240 Vac Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive:
120/240 Vac, Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
125/250 Vdc minutes, 3 amperes continuously, and break 0.3 ampere. 0.3 amperes.
(L/R = 0.04).
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-9
1.0
10.0
100.0
0.0 0.2 0.4 0.6 0.8 1.0
Multiple of Pickup
xRD (Seconds)
Isolation Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric
(high potential) tests as follows:
All circuits to ground: 2828 Vdc
Input to Output Circuits: 2000 Vac or 2828 Vdc
Thischartverticalaxis xRD (Seconds) is
applicable for all curves and is derived
from multiplying the constant Rfor the
curve selected times D(the TIME DIAL
setting).
Figure 1-4. Integrating Reset Characteristic Curve
Surge Withstand Capability
Oscillatory
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems
.
Fast Transient
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems
.
Impulse Test Qualified to IEC 255-5.
Radio Frequency Field tested using a five watt, hand held transceiver operating at random
Interference (RFI) frequencies centered around 144 megahertz and 440 megahertz, with the
antenna located six inches from the relay in both horizontal and vertical
planes.
Patent Patented in U.S., 1998, U.S. Patent No. 5751532.
www . ElectricalPartManuals . com

1-10 BE1-50/51B-214/-225 - General Information
Temperature Operating Range
-40
C (-40
F) to 70
C (158
F)
Recommended Storage Range
-50
C (-58
F) to 50
C (122
F).
Shock 15 g in each of three mutually perpendicular planes.
Vibration 2 g in each of three mutually perpendicular planes swept over the range of
10 to 500 hertz for a total of six sweeps, 15 minutes each sweep.
Weight 6.1 pounds.
CHARACTERISTIC CURVES
Figures 1-5 through 1-18 illustrate the characteristic curves that are programmed into the nonvolatile
memory of this relay. To order full-size drawings of these characteristic curves, contact Customer Service
Department of the Power Systems Group, Basler Electric, and request publication 9 2520 00 999. This
publication contains fourteen full size characteristic curves on transparent paper (vellum).
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-11
MULTIPLES OF PICK-UP
Figure 1-5. Time Characteristic Curve 99-1369, S-Short Inverse (SW3-3 OFF, Similar to ABB CO-2)
www . ElectricalPartManuals . com

1-12 BE1-50/51B-214/-225 - General Information
MULTIPLES OF PICK-UP
Figure 1-6. Time Characteristic Curve, 99-1370, L-Long Inverse (SW3-3 OFF, Similar to ABB CO-5)
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-13
MULTIPLES OF PICK-UP
Figure 1-7. Time Characteristic Curve, 99-1371, D-Definite Time (Similar to ABB CO-6)
www . ElectricalPartManuals . com

1-14 BE1-50/51B-214/-225 - General Information
MULTIPLES OF PICK-UP
Figure 1-8. Time Characteristic Curve, 99-1372, M-Moderately Inverse (Similar to ABB CO-7)
www . ElectricalPartManuals . com

BE1-50/51B-214/-225 - General Information 1-15
MULTIPLES OF PICK-UP
Figure 1-9. Time Characteristic Curve, 99-1373, I-Inverse (SW3-3 OFF, Similar to ABB CO-8)
www . ElectricalPartManuals . com
This manual suits for next models
1
Table of contents
Other Basler Relay manuals

Basler
Basler BE1-50-219 User manual

Basler
Basler BE1-51 User manual

Basler
Basler BE1-50 User manual

Basler
Basler BE1-46N User manual

Basler
Basler BE1-79M User manual

Basler
Basler BE1-79A User manual

Basler
Basler BE-51/27C User manual

Basler
Basler BE1-51M User manual

Basler
Basler BE1-47N User manual

Basler
Basler BE1-50B User manual

Basler
Basler BE1-50/51B-233 User manual

Basler
Basler BE1-50BF User manual

Basler
Basler BE1-51/27R User manual

Basler
Basler BE1-50B-235 User manual

Basler
Basler BE1-81O/U User manual

Basler
Basler BE1-32R User manual

Basler
Basler BE1-24 User manual

Basler
Basler BE1-951 User manual

Basler
Basler BE1-50BF User manual

Basler
Basler BE1-47N User manual