Wiring diagrams:
2-wire-system (current)
2-wire-system (current) HART
3-wire-system (current/supply)
!A minimum static bending radius has to be complied
with. For static installation use the 10-fold cable diame-
ter, for dynamic applications use the 20-fold diameter.
!Prevent the damage or removal of the PTFE filter
which is fixed over the end of the air tube on devices
with cable outlet and integrated air tube.
Gauge / relative devices are equipped with cable with
integrated air tube for atmospheric pressure reference.
Install cable end in a control cabinet or suitable
terminal box in dry area which is free of aggressive
gasses to avoid damages.
For the electrical connection a shielded and twisted
multicore cable is recommended.
If a transition is desired from a probe cable with gauge
tube to a cable without gauge tube, we recommend our
terminal box KL 1 or KL 2.
Devices with TPE-cable
- Application in water with a temperature > 70°C de-
stroys the cable
- Applications at media temperatures > 70°C have to
be clarified with BD|SENSORS in advance
Usually, the required cable is included in the scope of
delivery. If it is although necessary to connect an exist-
ing or special cable, the total resistance will increase.
For applications, where this additional resistance of the
connecting cable could cause problems, this cable has
to be checked with the following calculation.
with RL: resistance of connecting cable in Ω
ρ: specific resistance in Ωmm²/m
l: cable length in m
A: cross section of conductor in mm²
( )
A0.02R...RRV loadL2L1tot ⋅+++=
with Vtot: total voltage drop
Rload: load resistance (to be taken out of the
current data sheet)
the following condition has to be fulfilled:
with VS:planned supply voltage
VS min:minimal supply voltage (to be taken out
of the current data sheet)
5. Characteristic
5.1 HARTcommunication (in H-devices)
The analogue output signal is overridden by an additional
signal according to the HART-specification. The device can
be configured via a HART-communication device. There-
fore we suggest our programming kit CIS 150 (available as
accessory). It consists of HART-modem, connecting cables
as well as configuration software and allows a simple and
time-saving configuration of all parameters. (The software is
compatible with all Windows-systems from Windows 98
and higher.)
To ensure a trouble-free operation the following require-
ments should be fulfilled:
maximal cable length between device and power supply:
V
VV
CC
R
L
36
max
10401065 ⋅
−
⋅
⋅
=
whereas Lmax: maximum length of cable in [m]
RV: resistance of the cable together with
the load resistance in [Ω]
CV: capacity of the cable in [pF/m]
resistance R:
whereas U: power supply in [VDC]
The resistance must be at least 240 Ω.
5.2 Separable probes
In order to facilitate stock keeping and maintenance, the
probe head is plugged to the cable assembly with a connec-
tor and can be easily changed. The following probes are
separable: LMK 358, LMK 358H, LMP 308, LMP 308i and
LMP 808
Disassembly
- Hold the probe on the sensor
section (2) with one hand and
turn the nut (4) carefully to the
left with the other hand. Prevent
torsion of the cable section (3)
against the housing!
- While screwing and pulling off
the sensor section (2) from the
cable section (3), hold it straight
to prevent damages on the
plugs.
Assembly
- Check the o-rings (5, 6) and exchange damaged o-
rings if necessary.
- Lubricate the radial o-rings (5) with Vaseline or o-ring
grease.
- Remove any grease residue from the axial-o-ring (6).
- Plug the cable section (3) straight into the plug of the
sensor section (2).
- Hold the probe onto the sensor section (2) with one
hand. Screw on and tighten the nut (4) carefully with
the other hand. Prevent torsion of the cable section (3)
against the housing!
Pin configuration
Binder series 723
(5-pin)
Binder series 723
(7-pin)
Supply −
4
1
TxD
-
5
5.3 Accuracy 0.1 % FSO
Devices with an accuracy of 0.1 % FSO have micro-
controlled electronics for processing and improving the
signal. As a matter of principle, the processing takes more
time than for analogue sensors, which have only an ampli-
fier. Due to this longer response time, the output signal
follows the measured value discontinuously. For relatively
stable measuring values, this characteristic is secondary.
Please compare the specification for the response time in
the data sheet.
5.4 Communication interface (i-devices)
Intelligent devices with an optional communication interface
can also be configured with these electronics. Offset, span
and damping are programmable within the limits given in the
data sheet. For configuration, the programming kit CIS 510
consisting of Adapt 1, power supply and Windowscom-
patible programming software is necessary. This can be
ordered as accessory from BD SENSORS.
6. Initial start-up
WARNING! Before start-up, the user has to check for
proper installation and for any visible defects.
WARNING! The device can be started and operated by
authorized personnel only, who have read and under-
stood the operating manual!
WARNING! The device has to be used within the
technical specifications, only (compare the data in the
data sheet)!
7. Placing out of service
WARNING! When dismantling the device, it must
always be done in the depressurized and currentless
condition! Check also if the medium has to be drained
off before dismantling!
WARNING! Depending on the medium, it may cause
danger for the user. Comply therefore with adequate
precautions for purification.
8. Maintenance
In principle, this device is maintenance-free. If desired, the
housing of the device can be cleaned when switched off
using a damp cloth and non-aggressive cleaning solutions.
Depending on the measuring medium, however, the dia-
phragm may be polluted or coated with deposit. If the
medium is known for such tendencies, the user has to set
appropriate cleaning intervals. After placing the device out
of service correctly, the diaphragm can usually be cleaned
carefully with a non-aggressive cleaning solution and a soft
brush or sponge. If the diaphragm is calcified, it is recom-
mended to send the device to BD SENSORS for decalcifica-
tion. Please read therefore the chapter “Service / Repair”
below.
!An incorrect cleaning can cause irreparable damages
on the diaphragm. Never use spiky objects or pres-
sured air for cleaning the diaphragm.
9. Service / Repair
9.1 Recalibration
During the life-time of a probe, the value of offset and span
may shift. As a consequence, a deviating signal value in
reference to the nominal pressure range starting point or
end point may be transmitted. If one of these two phenom-
ena occurs after prolonged use, a recalibration is recom-
mended to ensure furthermore high accuracy.
9.2 Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it has to be cleaned
carefully and packed shatter-proofed. You have to enclose a
notice of return with detailed defect description when
sending the device. If your device came in contact with
harmful substances, a declaration of decontamination is
additionally required. Appropriate forms can be downloaded
from our homepage www.bdsensors.com. Should you
dispatch a device without a declaration of decontamination
and if there are any doubts in our service department
regarding the used medium, repair will not be started until
an acceptable declaration is sent.
If the device came in contact with hazardous
substances, certain precautions have to be
complied with for purification!
10. Disposal
The device must be disposed according to the
European Directives 2002/96/EG and
2003/108/EG (on waste electrical and electronic
equipment) Waste of electrical and electronic
equipment may not be disposed by domestic
refuse!
WARNING! Depending on the measuring medium,
deposit on the device may cause danger for the user
and the environment. Comply with adequate precau-
tions for purification and dispose of it properly.
11. Warranty conditions
The warranty conditions are subject to the legal warranty
period of 24 months from the date of delivery. In case of
improper use, modifications of or damages to the device, we
do not accept warranty claims. Damaged diaphragms will
also not be accepted. Furthermore, defects due to normal
wear are not subject to warranty services.
12. Declaration of conformity / CE
The delivered device fulfils all legal requirements. The
applied directives, harmonised standards and documents
are listed in the EC declaration of conformity, which is
available online at: http://www.bdsensors.com.
Additionally, the operational safety is confirmed by the CE
sign on the manufacturing label.