1.2 Connections
The 2 core Enhanced cable should be
connected to the Line + and – terminals as
shown (the connector is a two part one so it
can be removed and terminated before being
plugged onto the board).
The Earth should be connected to the Earth
terminal in the back box.
The end of line is fitted internally so is not
required for correct operation and
monitoring.
The phone plate can be reassembled, and the
phone plugged into the grey connector (care
should be taken when plugging this in to
ensure it is the correct way round)
When the phone is correctly wired the
confidence LED lights dimly when the phone
is on hook.
2Operation
To call from the Type A phone simply remove the phone from the hook switch, this will cause all
masters programmed for this line to ring. The call can be ended by placing the phone back on the
hook switch (the confidence LED also lights again)
When the master calls the Type A outstation, the ringer sounds and the confidence LED flashes, to
answer the phone remove the handset from the cradle and speech can take place- To end simply
place the phone on the hook switch.
3Maintenance
It is a requirement of BS 5839-9:2021 that a maintenance agreement be in place for the EVCS. The
maintenance schedule should be as follows:
Weekly Each week test one type A outstation (a different one each week) and
ensure speech is clear and intelligible. Ring the outstation to verify the
operation of the ringer. Record this in the log book for the EVCS.
6 Monthly Every outstation on the system should be tested and the results logged
in the logbook.