10 IR427-MK7_D00118_00_M_ESEN / 09.2016
ISOMETER® IR427 + MK7
Interface for MK7
Cable length, twisted pairs, shielded ................................................................................. ≤200 m
Recommended cable ....................... min. J-Y(St)Y 2x2 x 0.6; shield on one side connected to PE
Power supply (terminals 1 and 2):
Uaus ...................................................................................................................................... DC 24 V
Imax (max. 4 MK7) ................................................................................................................. 80 mA
Communication (terminal 3 and 4):
Interface/protocol ............................................................ RS-485 / proprietary interface (no BMS)
Terminating resistor ............................................................ 120 Ω(0.25 W), internal, switchable
Interfaces for STW2 measuring current transformer and tem-
perature sensor
Cable lengths:
Single wire > 0.5 mm² .......................................................................................................... ≤1 m
Single wire, twisted > 0.5 mm² .......................................................................................... ≤10 m
twisted pair, shielded > 0.5 mm² ....................................................................................... ≤40 m
Recommended cable ............................. min. J-Y(St)Y 2x0.6, shield on one side connected to PE
Switching elements
Number of changeover contacts ................................................................... 1 changeover contact
Operating principle ............................................ N/C operation / N/O operation (N/C operation)*
Electrical service life, number of cycles ................................................................................. 10.000
Contact data acc. to IEC 60947-5-1
Utilization category .................................... AC -13..... AC -14 ...... DC-12...... DC-12 ...... DC-12
Rated operational voltage .............................230V ........230V ..........24V ........110V ........220 V
Rated operational current ................................. 5 A............3 A ............1 A.........0.2 A .........0.1 A
Minimum contact load .................................................................................. 1 mA at AC / DC 10 V
Environment / EMC
EMC ................................................................................................................................... IEC 61326
Operating temperature ........................................................................................ -25 °C…+55 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ......................... 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ................................. 2K3 (except condensation and formation of ice)
Storage (IEC 60721-3-1) .................................... 1K4 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................................................ 3M4
Transport (IEC 60721-3-2) ........................................................................................................ 2M2
Storage (IEC 60721-3-1) ........................................................................................................... 1M3
Connection
Connection type ......................................................................................... push-wire terminals
Connection properties:
Rigid ............................................................................................ 0.2…2.5 mm2 (AWG 24…14)
Flexible without ferrules.............................................................. 0.2…2.5 mm2 (AWG 24…14)
Flexible with ferrules................................................................... 0.2…1.5 mm2 (AWG 24…16)
Stripping length .................................................................................................................... 10 mm
Opening force ............................................................................................................................. 50 N
Test opening, diameter ........................................................................................................ 2.1 mm
General data
Operating mode ............................................................................................. continuous operation
Position of normal use ................................................................................................................ any
Degree of protection, internal components ................................................... (DIN EN 60529) IP30
Degree of protection, terminals ..................................................................... (DIN EN 60529) IP20
Enclosure material...................................................................................................... polycarbonate
Flammability class .............................................................................................................. UL94V-0
Screw mounting .................................................................................................................... 2 x M4
DIN rail mounting acc. to .................................................................................................. IEC 60715
Software version ............................................................................................................ D288 V1.0x
Weight ........................................................................................................................ approx. 150 g
( )* = Factory setting
Interfaz para MK7
Longitud de cable, retorcido por pares, apantallado ......................................................... ≤200 m
Cable recomendado ................................. mín. J-Y(St)Y 2x2 x 0,6; apantallado por un lado en PE
Suministro de corriente (terminal 1 y 2):
Uaus ....................................................................................................................................... 24 V CC
Imax (máx. 4 MK7) .................................................................................................................. 80 mA
Comunicación (terminal 3 y 4):
Interfaz/protocolo ............................................................................. RS-485 / propietario, no BMS
Resistencia de terminación ................................................ 120 Ω(0,25 W), interna, conmutable
Interfaces para toroidal de medida de corriente STW2 y sensor
de temperatura
Longitudes de cable:
Hilo único > 0,5 mm² ............................................................................................................. ≤1 m
Hilo único, retorcido > 0,5 mm² .......................................................................................... ≤10 m
Retorcido por pares, apantallado > 0,5 mm² ...................................................................... ≤40 m
Cable recomendado ...................................... mín. J-Y(St)Y 2x0,6; apantallado por un lado en PE
Elementos de conmutación
Cantidad ............................................................................................................. 1 contacto inversor
Modo de funcionamiento .......... corriente de reposo/corriente de trabajo (corriente de reposo)*
Vida útil eléctrica en condiciones de diseño ................................... 10.000 ciclos de conmutación
Datos de contacto conforme a IEC 60947-5-1
Categoría de consumo ................................. AC-13 ...... AC-14.......DC-12 ...... DC-12....... DC-12
Tensión de funcionamiento de diseño ......... 230V ....... 230 V ..........24 V ....... 110V....... 220 V
Corriente de funcionamiento de diseño ........... 5A ........... 3A ............1A ........ 0,2A........ 0,1 A
Capacidad de carga mínima de contacto .................................................. 1 mA para 10 V CA / CC
Medio ambiente/EMC
EMC ................................................................................................................................... IEC 61326
Temperatura de funcionamiento ........................................................................ -25 °C…+55 °C
Clases climáticas conforme a IEC 60721:
Uso estacionario (IEC 60721-3-3) ........................... 3K5 (sin condensación y formación de hielo)
Transporte (IEC 69721-3-2) .................................... 2K3 (sin condensación y formación de hielo)
Almacenamiento prolongado (IEC 60721-3-1) ..... 1K4 (sin condensación y formación de hielo)
Solicitación mecánica conforme a IEC 60721:
Uso estacionario (IEC 60721-3-3) ............................................................................................ 3M4
Transporte (IEC 60721-3-2) ..................................................................................................... 2M2
Almacenamiento prolongado (IEC 60721-3-1) ...................................................................... 1M3
Conexión
Tipo de conexión............................................................................................ terminales de presión
Capacidad de conexión:
rígida ........................................................................................... 0,2…2,5 mm2 (AWG 24…14)
flexible sin virola de cable ........................................................... 0,2…2,5 mm2 (AWG 24…14)
flexible con virola de cable ......................................................... 0,2…1,5 mm2 (AWG 24…16)
Longitud de desaislamiento.................................................................................................. 10 mm
Fuerza de apertura .................................................................................................................... 50 N
Abertura de prueba, diámetro ............................................................................................. 2,1 mm
Otros
Modo de funcionamiento ....................................................................... Funcionamiento continuo
Posición de uso ................................................................................................................ cualquiera
Clase de protección piezas montadas ............................................................ (DIN EN 60529) IP30
Clase de protección terminales ...................................................................... (DIN EN 60529) IP20
Material de la carcasa ................................................................................................ Policarbonato
Clase de inflamabilidad ..................................................................................................... UL94V-0
Fijación atornillada ................................................................................................................ 2 x M4
Fijación rápida sobre carril DIN.......................................................................................... IEC 60715
Versión de software ....................................................................................................... D288 V1.0x
Peso .......................................................................................................................................... 150 g
( )* = ajuste de fábrica