Bevent Rasch BSK6 User manual

13/09/2017
www.bevent-rasch.com
BSK6
Rectangular Fire damper
FIRE SAFETY

2BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper BSK6 EI60
Installation
BSK6 is installed in duct work separating walls or joist sys-
tems, according to the adjoining installation instructions.
Should not be installed outdoors or in damp areas.
Actuator
BSK6 is always supplied with an electric safety actua-
tor with spring return complete with thermal sensor with
pushbutton for local manual operating test. The sensor
disconnects the power to the actuator if the temperature
exceeds 72°C inside or outside the damper. 24V actuators
are always used in connection with the MRB monitoring
system. Dampers can also be supplied with electric actu-
ator 230V.
Note that the BSK6 damper is always supplied with an
actuator.
Activation
According to Boverket’s Building Regulations smoke de-
tectors must be verified according to SS-EN 54-7 to acti-
vate dampers. The mandatory thermal sensor closes the
damper at 72°C according to ISO 10294-4.
Control and monitoring
When the damper is used to prevent the spread of fire and
combustion gases it must be closed via impulses from the
smoke detector. This must be fitted in the ventilation duct
in the proximity of the damper or in another suitable loca-
tion. Smoke detectors are monitored by means of Bevent
Rasch’s MRB system or the like. The MRB monitoring
system also performs automatic operating checks on the
damper every 48 hours and is designed so that faults are
indicated immediately and the damper closes.
See www.bevent-rasch.com for further details.
Quick facts
• Fire resistance class EI60 / EI60S
• Sizes from 200 x 200 mm to 800 x 800 mm
• Prefitted safety actuator 24V or 230V
• Low weight
• Easy installation
• CE-marked building product according to 15650:2010
• Available in MagiCAD
Use
Damper in combination with walls or joist systems for fire
separation of heating, ventilation and air conditioning in-
stallations in buildings. In accordance with the harmonised
European standard EN 15650:2010. In designs according
to associated documents, installation instructions and
when the damper is used in combination with smoke
detectors and monitoring system (MRB), or the like, the
spread of fire/combustion gases is prevented. No further
action against the spread of fire/combustion gases is re-
quired.
Performance
EC certificate according
to EN 15650:2010
0402-CPR-SC1299-13
Classification of fire resistance
according to EN 13501-3
EI60 (ve ho i <–> o) S
For complete classification,
see the Declaration of Performance.

3BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
EI60 Fire damper BSK6
Size
From 200 x 200 mm to 800 x 800 mm, in steps of 50 mm.
Design
BSK6 is supplied complete with factory mounted,
maintenance-free, 24V or 230V electric safety actuator
with thermal sensor featuring built-in signal contacts to
indicate the damper position. Flanged connections.
Material and surface finish
Casing and components of galvanized steel sheet
according to environmental class C3. Fabric seals.
Blade and casing of solid fire protection materials.
Accessories
BRAS Connection spigot for spiral duct
RBFS Extension spigot for wall/joist systems
thicker than 280 mm, and in combination
with BRAS or wire mesh grilles
RBMP Assembly plate, excl. refinishing material
(RBBM), for installation in plaster
structures EI 60 / EI 120
RCKB Connection box
RCDU MRB system, max 2 dampers
RCBK4 MRB system, max 4 dampers
RCMU8 MRB system, max 8 dampers
RCKD/-RD Smoke detectors
BRTR Wire mesh grille, rectangular
RCTU/RCTC MRB3 system, max 236 dampers
Specification
Example:
Fire damper BSK6 - 400 - 400 - 1 - 1
Size
Width x Height (W x H), mm
Material
Galvanized sheet steel = 1
Stainless AISI 3041 – EN 1.4301 = 2
Stainless AISI 316L – EN 1.4404 = 3
Actuator
Electric 24V with thermal sensor = 1
Electric 230V with thermal sensor = 3
Electric 24V incl. RCTU = 5
Note. Factory fitted actuator always included.

4
Brand-/Brandgasspjäll BSKC6 EI60
BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper BSK6 EI60
Dimensions and weight
Electrical data (values in brackets refer to 230V)
Actuator type BF...
Sizing, max ...................... 10 VA (12.5 VA)
Running time:
– motor opening, max ..... approx. 120 s
- spring return, max ......... approx. 20 s
Protection class ............... IP 54
Power supply .................. 24V~ ±20%, 50/60Hz
24V= ±10%
(220-240V~ , 50/60Hz)
Ambient temperature ....... -30° to +50°C
Safety temperature .......... -30° to +75°C
(24 hrs. guaranteed safety)
Tripping temperature
thermal sensor .................
72°C
End position contacts
- load ≤ 300 mW ..... min 1 mA/5V=, max 100 mA/250V~
After exceeding the above values it applies:
- load > 300 mW ..... min 100 mA, max 3 A/250~
Sound level when opening approx 45 dB(A)
Sound level when closing approx 62 dB(A)
Chart indicates in
the de-energized
state
Wiring
diagram
Tf1 Tf2
BAE72-S
Actuator
C
O
N
L1
M
1
2
1
2
3
4
5
6
5°
80°
Thermal
sensor
Actuator
43
48 D125 227
400
A
max*)
128 W
H
Flanged connection19
*) applies to standard design
HAD
200 0 0
250 25 0
300 50 0
350 75 0
400 100 0
450 125 0
500 150 0
550 175 0
600 200 20
650 225 45
700 250 70
750 275 95
800 300 120
Dimensions, mm Weight incl. 24V actuator, kg
H
W
200
250
300
350
400
450
500
550
600
650
700
750
800
200 12 13 15 16 17 18 20 21 22 24 25 27 28
250 13 15 16 17 18 20 21 22 24 25 27 28 30
300 15 16 17 18 20 21 22 24 25 27 28 30 32
350 16 17 18 20 21 22 24 25 27 28 30 32 33
400 17 18 20 21 22 24 25 27 28 30 32 33 35
450 18 20 21 22 24 25 26 28 30 32 33 35 36
500 20 21 22 24 25 26 28 30 32 33 35 36 38
550 21 22 24 25 26 28 29 32 33 35 36 38 39
600 22 24 25 26 27 29 30 33 35 36 38 39 41
650 24 25 26 27 29 30 31 35 36 38 39 41 42
700 25 26 27 29 30 31 33 36 38 39 41 42 44
750 26 27 29 30 31 33 34 38 39 41 42 44 45
800 27 29 30 31 33 34 35 39 41 42 44 45 47

5
EI60 Brand-/Brandgasspjäll BSKC6
BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
EI60 Fire damper BSK6
Assembly plate (incl. in delivery)
Supplied unassembled
Ød Ød
A 400 A
A 400 A
BRAS RBFS BRAS
BRAS RBFS BRAS
RBFS
L2
L1
L1
Ød
L
1
/L
2
A
Connection spigot
BRAS
Extension spigot
RBFS
Ød = 250 - 500 mm
1 x RBFS required Ød = 630 - 800 mm
2 x RBFS required
Installation
*) Length as per the table above
*)
*)
*)
Note. For circular dampers first use the BSKC6 damper.
BRAS
Ød
Min. damper
size A
RBFS
L1L2
100 200 x 200 50 – –
125 200 x 200 50 – –
160 200 x 200 50 – –
200 200 x 200 50 – –
250 250 x 250 50 155 –
315 350 x 350 65 155 –
400 400 x 400 80 155 –
500 500 x 500 80 330 –
630 650 x 650 80 330 155
800 800 x 800 80 330 155
Duct size W/H + 65 mm
60
60

6
Brand-/Brandgasspjäll BSKC6 EI60
BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper BSK6 EI60
13-0272_ENG / Sept. 2017 teamfront.se
Sound data
The speed is calculated on the damper’s gross area, i.e. a
BSK6 - 400 x 400 has a gross area of 0.16 m2.
The specified pressure drop applies to the damper without accessories.
Technical data
75
Total pressure drop, Pa
Air speed, m/s
Sound power level
1 Damper Height < 400 mm
2 Damper Height ≥ 400 mm
Correction of sound power level, Lok, in octave band
LWok = LW+ Kok
Correction of sound power level, LW, for different sizes
use curves 1 - 2 according to: LW= LWt + K1
Damper
height
mm Damper area, m2
<200 as per 1 - 0,08 0,16 0,28 -
≥400 as per 2 0,08 0,16 0,32 0,64 1,28
K1-3 0 3 6 9
Correction, Kok
Opening
angle
Centre frequency Hz
63 125 250 500 1000 2000 4000 8000
90° -1 -11 -18 -23 -26 -28 -32 -38
Tol. ± dB 1 2 3 4 6 6 6 6

7
EI60 Brand-/Brandgasspjäll BSKC6
BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
EI60 Fire damper BSK6
13-0272_ENG / Sept. 2017 teamfront.se
Options 1 and 2
1. Aperture equivalent to damper dimensions + 50 mm,
is produced in the building element.
When mounted in a drywall, horizontal metal joists
45x45 mm shall be applied as a frame in the wall
structure.
2. The damper is secured flat and tight using fire stopping
sealant (Intumex AN) against the wall/joist structure with
the fastening lugs, which are opened out.
When mounted in drywall, Spax screws shall be
screwed in to the joists.
3. Make sure the gap between damper and wall is 25 mm
all around. Sealing is carried out by caulking with miner-
al wool, min 40 kg/m3.
4. Fit the assembly plates RBMP on to the building ele-
ment, using appropriate fastening material.
When mounted in drywall, Spax screws shall be
screwed in to the joists. Attach the assembly plates on
to the damper, using stainless steel pop rivets through
the prepunched holes in the assembly plates.
Mount the pop rivets from the inside and out. Make
sure nothing is obstructing the movement of the
damper blade.
Building element (wall or joist structure)
in fire resistance class EI60.
Damper’s fire resistance class: EI60
(ve ho i <-> o) S.
EC certificate 0402-CPR-SC1299-13
Option 1 Option 2
5. If fire damper is not connected to the duct system, fit
non-combustible grilles designed for the damper on the
unconnected sides. Connection piece RBFS may be
needed from sizes 600 mm or larger.
The minimum distance between the damper blade in
the open position and the grille is 50 mm.
6. Install the thermal sensor with the sensor body in the air
stream without obstructing the movement of the
damper blade.
7. Install the duct system according to applicable require-
ments.
8. Install the duct system according to applicable require-
ments. Make sure that the connected duct system
does not impact on the damper in the event of a fire
load.
• Minimum distance between dampers must be 200 mm.
• Minimum distance to joist structure/wall must be 75 mm.
• Horizontal installation of the damper spindle.
W + 50 mm
H + 50 mm
Refinish
see section
3
(Protective grille,
see section 5)
Concrete screw
8x5x65 or equivalent
approved fastening
material
Fastening
lugs
Assembly
plate RBMP
Pop rivet
mounted
fr
om inside
and out
Min. thickness
125 mm
Joist of concrete
or equivalent
fire resistance
class ≥EI60
Installation instruction
W + 50 mm
H + 50 mm
Refinish
see section 3
(Protective grille,
see section 5)
Screw (Spax 5x45
or equivalent approved
fastening material)
Fastening lugs
Assembly plate RBMP
Pop rivet mounted
from inside and out
Horizontal joist,
see section 1
Min. thickness 95 mm
Drywall insulated
with mineral wool
≥ 40kg/m3.
Or equivalent with
wall fire resistance
class ≥ EI60.
Table of contents
Other Bevent Rasch Fire And Smoke Damper manuals