BIRD 4043E User manual

Directional Power Sensor
Model 4043E
Operation Manual
©Copyright 2021
by Bird Technologies, Inc.
Instruction Book Part Number 920-4043E Rev. A

i
Safety Precautions
The following are general safety precautions that are not necessarily related to
any specific part or procedure, and do not necessarily appear elsewhere in this
publication. These precautions must be thoroughly understood and apply to all
phases of operation and maintenance.
WARNING
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety precautions. Do
not replace components or make adjustments to the inside of the test
equipment with the high voltage supply turned on. To avoid casualties, always
remove power.
WARNING
Shock Hazard
Do not attempt to remove the RF transmission line while RF power is present.
WARNING
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure for the
purpose of service or adjustment of equipment except in the presence of
someone who is capable of rendering aid.
WARNING
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the main
power source to test instruments. Grounding one conductor of a two
conductor power cable is not sufficient protection. Serious injury or death can
occur if this grounding is not properly supplied.
WARNING
Resuscitation
Personnel working with or near high voltages should be familiar with modern
methods of resuscitation.
WARNING
Remove Power
Observe general safety precautions. Do not open the instrument with the
power applied.

Safety Precautions
ii
Safety Symbols
Note: Calls attention to supplemental information.
Warning Statements
The following safety warnings appear in the text where there is danger to
operating and maintenance personnel, and are repeated here for emphasis.
See page 6.
WARNING
Warning notes call attention to a procedure, which if not correctly performed,
could result in personal injury.
CAUTION
Caution notes call attention to a procedure, which if not correctly performed,
could result in damage to the instrument.
WARNING
Leaking RF energy is a potential health hazard. Never attempt to connect or
disconnect equipment from the transmission line while RF power is being
applied. Severe burns, electrical shock, or death can occur.

Directional Power Sensor 4043E
iii
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY
THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY
PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA
POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE
SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM
HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT
BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS
EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT
ENDOMMAGER LE DISPOSITIF DE PROTECTION DE
L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO
DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA
PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.

Safety Precautions
iv
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE - TRAINED
PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO
NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO
DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL
PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN
SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR
FÜR GESCHULTES FACHPERSONAL. ZUR VERMEIDUNG
GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND
WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM
SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ
AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR
PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS
EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR
CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE
ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE
ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE
NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE
QUALIFICATI A FARLA.

Directional Power Sensor 4043E
v
About This Manual
This manual covers the operating and maintenance instructions for the
following models:
Changes to this Manual
We have made every effort to ensure this manual is accurate. If you discover any
errors, or if you have suggestions for improving this manual, please send your
comments to our Solon, Ohio factory. This manual may be periodically updated.
When inquiring about updates to this manual refer to the part number and
revision on the title page.
Chapter Layout
Introduction — Describes the features of the 4043E Directional Power
Sensor.
Installation — Describes how to set up and prepare the 4043E Power Sensor
for use.
Maintenance — This section provides the specifications for the 4043E Power
Sensor as well as a model identification table.
4043E - Directional Power Sensors

vi
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Warning Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Changes to this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Chapter Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Purpose and Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Ethernet Measurement Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ethernet IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PTT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Power Sensor Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Direct PC Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LAN Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
RF Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PTT Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 3 Sensor Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
RF Measurement Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
PTT Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Zero Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Implement SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Set IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Update sensor firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Factory Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 5 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Model Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

1
Chapter 1 Introduction
Purpose and Function
The Bird 4043E Directional Power Sensors are digital power sensors. The 4043E
power sensors are typically used to measure forward and reflected average
power on a 50 ohm RF transmission line with a maximum 500 watt forward and
maximum 50 watt reflected power levels in a frequency band with an overall
range of 118 to 940 MHz. See
"Model Identification" on page 19
for specific
frequency ranges and model features. The 4043E sensor also provides a VSWR
reading.
Figure 1 4043E Power Sensor
The 4043E Power Sensor uses Ethernet communications for sensor control and
measurement data.
See
"Sensor Operation" on page 8
.
The 4043E Sensor is designed to transfer data over an Ethernet connection. The
power sensor requires an external power supply.
Each sensor is equipped with RF input and output connectors, one RJ-45
connector for Ethernet communications, a PTT connector, and a status indicator.
See
Figure 2
.

Introduction
2
Figure 2 Bird 4043E, Ethernet Communication Power Sensor
Features
RF Input N-Type (male) connector (shown), other connector types
available, see
"Model Identification" on page 19
RF Output N-Type (female) connector (shown), other connector types
available, see
"Model Identification" on page 19
DC Power Connector DC input connector for the included 15 VDC power supply.
Ethernet Port RJ-45 connector used to interface with the Sensor’s Web UI
and provide the measurement interface.
PTT Connector
Push-To-Talk terminal is used to prevent spurious alarms
during periods when the transmitter is not transmitting, see
"PTT" on page 3
.
Reset Button
This reset button is a hole under the Ethernet jack.
When short pressed (less than 5 seconds), the
button will cause the IP address to be reset to the
default of 192.168.3.200.
When long pressed (more than 5 seconds), all of
the 4043E settings are reset to the factory defaults.
Status LED
Solid green: Power applied during boot-up.
Blue flashing: Normal operation.
Red: Reset button pressed and released.

Directional Power Sensor 4043E
3
Ethernet Measurement Interface
The 4043E sensor displays measurement information on a Web UI. Using a web
browser, enter the IP address for the 4043E to display the web page.
Table view displays the current Forward, Reflected, and VSWR measurements.
See
Figure 7
.
Figure 3 Web UI, Table View Measurement Display
Ethernet IP Address
Each 4043E leaves the factory with the same default IP Address.
Default IP Address: 192.168.3.200
To change the IP address see
"Set IP Address" on page 14
.
PTT
PTT is used to prevent false alarms during periods when the transmitter is not
transmitting. PTT disables alarm detection when the transmitter is off. Alarm
functions will only be possible when the transmit button is engaged.
PTT may be set to normally open or normally closed logic. The PTT terminals
must be in the correct logic state for PTT to operate correctly.
Note: PTT input is a passive connection and requires a 5V TTL
signal to operate.

4
Chapter 2 Power Sensor Installation
The Bird 4043E Directional Power Sensors are designed to be used for
continuous RF power monitoring. The 4043E can provide real-time RF forward
and reflected power and VSWR measurements.
Ethernet Connection
The Ethernet connector is used to connect the 4043E to a PC or a network
router/switch. Measurement data is transported over the Ethernet connection
so the data can be viewed in a web browser. The configuration depicted in
Figure 4
is an example of one possible installation.
Since the 4043E is shipped with a static IP address, before more than one unit
can be added to a LAN, the IP address must be changed to a unique static IP
address or set to DHCP.
Direct PC Connection — A direct PC connection is a connection between a
PC and a single 4043E. This connection can be used to view the sensor’s
measurement data, however, if the sensor will be used with a LAN connection,
this type of connection must be used to change the IP address of the 4043E. See
"Direct PC Ethernet Connection" on page 5
.
LAN Connection — The 4043E may be connected to a router or switch so it
can provide measurement information through a LAN. A LAN connection can
provide the ability to monitor several 4043E sensors from a single PC.
Additionally, SNMP management software can be used to aggregate multiple
sensors and monitor their outputs. See
"LAN Connection" on page 5
.
Figure 4 4043E Connection Diagram

Directional Power Sensor 4043E
5
Direct PC Ethernet Connection
This connection can be used to view measurement information, manage the
sensor’s behavior, and change the default IP address.
1. Connect a power cable to 4043E power sensor.
2. Connect your laptop’s network port to the LAN connector on the 4043E
using a standard Ethernet cable.
3. Insure that your laptop’s IP address is compatible with the default address
of the 4043E. This may require changes be made to the Ethernet adapter
address on your laptop.
Set laptop’s IP address to “192.168.3.1” and a subnet mask of
“255.255.255.0”.
4. Launch your web browser on the laptop.
5. In your web browsers address box type-in the 4043E’s IP address:
192.168.3.200. and press the ENTER key.
6. The web page interface to the unit should appear in your laptop’s browser
window.
7. Connect sensor to RF delivery system. See
"RF Connections" on page 6
.
8. If PTT will be used, see
"PTT Connections" on page 7
.
9. See
"Sensor Operation" on page 8
for descriptions of the sensor’s User
Interface.
LAN Connection
A LAN connection is used to allow multiple sensors to be deployed then
monitored via a single PC or SNMP management software.
The 4043E sensor’s IP address should be set to a unique static IP address or set
to DHCP so the IP address can be assigned when the sensor is connected to the
network.
1. Connect a power cable to 4043E power sensor.
2. Change sensor’s IP Address.
a. Connect your laptop’s network port to the LAN connector on the
4043E using a standard Ethernet cable.
b. Insure that your laptop’s IP address is compatible with the default
address of the 4043E. This may require changes be made to the
Ethernet adapter address on your laptop.
Set laptop’s IP address to “192.168.3.1” and a subnet mask of
“255.255.255.0”.
c. Launch your web browser on the laptop.
d. In your web browsers address box type-in the 4043E’s IP address:
192.168.3.200. and press the ENTER key.
The web page interface to the unit should appear in your laptop’s
browser window.

Power Sensor Installation
6
e. Click MENU in the top right of the display. See
Figure 5 on page 6
.
f. Select Static or DHCP.
If Static is selected, enter a unique IP address, Netmask,
Gateway.
If DHCP is selected, go to next step.
g. Click Submit.
h. Disconnect Ethernet cable from the 4043E.
Figure 5 IP Address Configuration
3. Connect a standard Ethernet cable to the LAN connector on the 4043E and
an open connector on a network switch or router.
4. Launch your web browser on a PC connected to the same network as the
4043E.
5. Enter the sensor’s newly assigned IP address in the web browsers address
box.
6. Connect sensor to RF delivery system. See
"RF Connections" on page 6
.
7. If PTT will be used, see
"PTT Connections" on page 7
.
8. See
"Sensor Operation" on page 8
for descriptions of the sensor’s User
Interface.
RF Connections
1. Disable RF power for transmission lines to be disconnected.
2. Connect combiner's RF output cable to the 4043E RF input.
3. Connect 4043E's RF output connector to the antenna cable.
4. Repeat step
1
through
3
for any additional 4043E power sensors.
WARNING
Leaking RF energy is a potential health hazard. Never attempt to connect or
disconnect equipment from the transmission line while RF power is being
applied. Severe burns, electrical shock, or death can occur.

Directional Power Sensor 4043E
7
PTT Connections
PTT may be set to normally open or normally closed logic. The PTT terminals
must be in the correct logic state for PTT to operate correctly.
Note: PTT input is a passive connection and requires a 5V TTL
signal to operate.
Figure 6 PTT Connections
The PTT settings in the User Interface must be enable and set to correct logic to
match the PTT connection. See
"PTT Settings" on page 10
.

8
Chapter 3 Sensor Operation
User Interface
The User Interface provides a way to view the RF measurements made by the
4043E. Table view displays the current Forward, Reflected, and VSWR
measurements. See
Figure 7
.
Figure 7 Web UI, Table View Measurement Display
The User Interface also provides the following capabilities:
RF Measurement Alarms
PTT Settings
Zero Sensor
Implement SNMP
Set IP Address
Update sensor firmware

Directional Power Sensor 4043E
9
RF Measurement Alarms
The 4043E power sensor can be set to display an alarm, and send SNMP
messages, for exceeding forward power and VSWR limits set by the user.
Alarms are controlled on the settings page, a threshold can be set for minimum
and maximum forward RF power in watts and minimum and maximum VSWR.
See
Figure 8
.
Figure 8 Alarm Settings
The alarm function may be enabled or disabled.
when enabled, a measurement exceeding a threshold will display an alarm
message in the Table View, see
Figure 9
.
When disabled, alarms are not displayed and no SNMP traps will be generated.
The alarms can be set to latched or unlatched.
When set to latched, alarm messages remain on the display until the Reset
Alarm button is clicked on the settings page.
When set to unlatched, alarm messages are only displayed while the threshold is
exceeded.
Figure 9 Alarm Display

Sensor Operation
10
PTT Settings
PTT is used to prevent spurious alarms during periods when the transmitter is
not transmitting because alarm functions for that channel will only be possible
when the transmit button is engaged.
PTT is controlled on the settings page, PTT may be set to normally open or
normally closed logic, or disabled, see
Figure 10
.
The PTT terminals on the 4043E must be connected to the transmitter in the
correct logic state for PTT to operate correctly.
Figure 10 PTT Options
Zero Sensor
Zero Sensor is used if the 4043E sensor’s readings are not zero when the RF
transmitter connected to the sensor is off.
The Zero Sensor option merely applies a negative offset to the power reading
based on the value the sensor displays when RF is off.
Figure 11 Zero Sensor Option
=HUR6HQVRU
5)SRZHU
WRWKH(
PXVWEH2))

Directional Power Sensor 4043E
11
Implement SNMP
The Simple Network Management Protocol (SNMP) feature is designed to
provide reliable Internet notification of an alarm occurrence. SNMP is an
Internet standard protocol for managing devices on IP networks.
SNMP network management software is required to implement SNMP. It is the
customers responsibility to ensure the destination computer is running suitable
SNMP management software.
Bird provides MIB files for use with the customers SNMP management software.
These MIB files allow the trap messages to be properly decoded. The MIB files
can be downloaded from the product page on the Bird website at;
“www.birdrf.com”.
The 4043E supports SNMP GET and SET commands, and can be configured to
send SNMP Trap messages. All of the 4043E’s SNMP commands can be found in
the MIB file.
GET and SET Commands
The SNMP manager can issue a GET request to read settings and power
measurements, and the SNMP manager can issue a SET request to change
settings.
GET
The SNMP GET operation is used by the SNMP manager applications to retrieve
one or more values from the 4043E.
The SNMP GET operation is used to query the scalar variables in a MIB. Each
variable is identified by its OID. The 4043E will respond with a return value or
with an error.
Sets
The SNMP SET operation is used by the SNMP manager to modify settings in the
4043E.
Perform an SNMP SET operation by providing the host name of the 4043E, one
or more OIDs along with its instance, and the new value. The 4043E processes
the request and assigns the new value to the MIB variable. If an error occurs, the
new value is not assigned.

Sensor Operation
12
SNMP Traps
Traps are messages sent to the SNMP manager by the 4043E when events occur.
To enable SNMP Trap functionality, connect to the 4043E User Interface, enable
Traps, and enter the SNMP Manager’s IP address. See
Figure 12
.
A trap message will be sent to designated host computers whenever the sensor
detects an alarm condition. See
Table 1 on page 13
.
Figure 12 SNMP Configuration
'HOD\
%HIRUH
0HVVDJH
0D\%H6HQW
,I6WLOO$FWLYH
,3 $GGUHVV
RI6103
0DQDJHU

Directional Power Sensor 4043E
13
Table 1 Table 1 SNMP Trap Message Definitions
Name Message Alarm/Clear Description
MinVSWRAlarmTrap
Site Name,
Sensor Name,
MinVSWR SetPoint,
Forward Power, VSWR
"Alarm" when sensor
state changes to an alarm
state. "Clear" when
sensor state changes
from alarming to clear.
Clear trap not sent if
manually cleared.
Alarm that occurs
when the VSWR is
below the minimum
VSWR setting.
MaxVSWRAlarmTrap
Site Name,
Sensor Name,
MaxVSWR SetPoint,
Forward Power, VSWR
"Alarm" when sensor
state changes to an alarm
state. "Clear" when
sensor state changes
from alarming to clear.
Clear trap not sent if
manually cleared.
Alarm that occurs
when the VSWR is
above the maximum
VSWR setting.
MinFwdPowerAlarm
Trap
Site Name,
Sensor Name,
MinFwdPower
SetPoint,
Forward Power, VSWR
"Alarm" when sensor
state changes to an alarm
state. "Clear" when
sensor state changes
from alarming to clear.
Clear trap not sent if
manually cleared.
Alarm that occurs
when the Forward
Power is below the
minimum power
setting.
MaxFwdPowerAlarm
Trap
Site Name,
Sensor Name,
MaxFwdPower
SetPoint,
Forward Power, VSWR
"Alarm" when sensor
state changes to an alarm
state. "Clear" when
sensor state changes
from alarming to clear.
Clear trap not sent if
manually cleared.
Alarm that occurs
when the Forward
Power is above the
maximum power
setting.
PttTrap
Site Name,
Sensor Name, Forward
Power, VSWR
N/A Trap sent when PTT
changes to active.
Table of contents
Other BIRD Accessories manuals
Popular Accessories manuals by other brands

Aqua-Scope
Aqua-Scope RANLWE01 quick start guide

Safety Technology International
Safety Technology International STI-34601 manual

Invacare
Invacare T1358 Assembly, installation and operating instructions

senva
senva TotalSense Series installation instructions

D-Link
D-Link DCH-Z122 manual

ECOWITT
ECOWITT WN51E Getting started