Note, that around 0=10%, below which will
appear insignificant and become hard to read, you
are close to the commonly accepted lower limit =
2, below which improved antenna match becomes
less and less worthwhile in many systems. Experi-
mentally, using the THRULINE, it is readily shown
that minimizing 0below 10% produces little gain in
\J^ .TV transmitter antenna lines, and VHP Omni-
range transmitters, are among systems requiring
much lower levels of reflected power for reasons
other than simple power transmission. Note also in
Fig. 4-la, the very small level of reflected power,
0=.06 percent ,corresponding to -1.05. With a
single Element, detection of reflected power is pos-
sible down to about 0=1 percent, >^= 1.2; if
approaches full scale, measurement is possible down
to about 0=5percent, /O =1.5.
LOW-REFLECTION MEASUREMENTS may be ex-
tended below this with two Elements. Say 80 watts
are available, and you have 100 watt and 10 watt
Elements.
Measure with the 100 watt Element. Re-
move 100 WElement and Insert 10 watt Element.
CAUTION:10 watt Element must be ONLY in
the REFLECTED direction. ARROW toward
TRANSMITTER. Insert and remove ONLY this
way.
Now read on the 10 watt Element.
SPECIAL NOTE
DON’T ROTATE 10 watt Element while TRANS-
MITTER is on. Always use great care with
LOW SCALE Elements on HIGH power RF lines.
Inadvertent exposure of these Elements to too
much FORWARD or even too high reflected
power may permanently damage the measuring
Element or the microammeter.
In this case, measurement down to at least .5 watt
reflected is possible which means to
0=percent, or to about =1.16
and detection of reflections is possible down to about
.1 watt,
0=~=.00125, say .1 percent, or to about ~1.06
80
Caution is necessary in the above method, and
preferably it should not be used with Element ranges
differing more than 100 to 10, although 250 to 10 can
be used with extreme caution. With certain Ele-
ments now available down to 1watt full scale this
method is usable with medium and low power
transmitters.
4. MEASUREMENT &MONITORING OF
TRANSMITTER POWER
Little more need be said about this, in view of
LOAD POWER paragraph above. The THRULINE is
useful for continuous monitoring of transmitter out-
put, and may be found useful in continuous monitoring i
of reflected power, for Instance in checking inter-
mittent antenna or line faults.
Like diode devices generally, the THRULINE in-
dicates the carrier component on amplitude modu- ^
latlon, with very little response to sideband compo-
nents added by modulation.
The THRULINE is highly useful for this purpose,
and may be employed in several ways.
(a) VSWR (Insertion) or 0(Insertion) may be mea-
sured with the line terminated in agood load resis-
tor (TERMALINE). The lower limits of sensitivity
in this are given above under LOW REFLECTION
MEASUREMENTS.
(b) ATTENUATION (Power lost by heat in the
line) as well as VSWR (Insertion) and 0(Insertion)
may be measured by inserting the unknown line be-
tween two THRULINES, or between two RF bodies
used with one meter and one set of Elements. (End
of line to be terminated in aload resistor). This
method applies also to insertion between the THRU-
LINE and aTERMALINE absorption wattmeter.
Very small values of attenuation require allow-
ance for normal Instrument errors. The correction
may be determined by direct rigid connection of the
THRUUNES, or of the THRUUNE -TERMALINE
combination, in cascade. Slight juggling of zero
settings is permissible for convenience in elimi-
nating computation, provided readings are being
taken fairly well up on scale.
(c) ATTENUATION BY OPEN OR SHORT CIR-
CUIT METHOD. Neater by far than method (b) is
one depending on the high directivity (null balance)
to which the THRULINE Elements are held. They
should, and do, exhibit good equality between for-
ward and reflected readings when the load connector
is open or short circuited. In this condition 0=100
percent, the forward and reflected waves being equal
in magnitude, and Say that this is checked
on open circuit, and then alength of line of unknown
attenuation, also open circuited, is connected to the
load connector. The ratio 0then shown is the atten-
uation in two passes along the line (down and back).
Expressed in dB, (using the equation NdB =^^g ^),
the dB figure may be compared with published data
for line type and length by remembering to halve
NdB* because twice the line length is actually being
measured.
This measurement should be supplemented by one
of 0(Insertion) as in (a) above, or at least by dc con-
*Or to tiouble the tine tendth.
5. TESTING OF LINES, CONNECTORS,
FILTERS, ETC.
4-4