www.blaubergventilatoren.de
Centro EC
7
Temperature sensor failure
Alarm code Alarm description
Two short pulses Short circuit of the temperature sensor
One pulse Breakdown of the temperature sensor
The motor shuts down
Electronics operation algorithm
The Centro EC ... G1(GT1/GI1/GTI1/GS1/GSI1) fan is equipped with an electronic module TSC (speed controller with an electronic
thermostat) for automatic speed control (air flow) depending on the air temperature.
The terminal compartment incorporates 2 control knobs:
• presetting speed
• setting electric thermostat threshold value
The fan is equipped with two indicators:
• temperature sensor indicator (hereinafter referred to as TSI) - yellow colour
• motor control indicator (hereinafter referred to as MCI) - green/yellow colour
When the fan turns on, the TSI indicates the unit operation algorithm:
• one pulse - G1(GI1);
• two pulses - GT1(GTI1);
• three pulses - GS1(GSI1).
The MCI lights up in green when the motor rotates and in red when it stops (or rotates
very slowly).To set the thermostat threshold, rotate the thermostat control knob
clockwise to increase or counter-clockwise to decrease the temperature set point. To set the fan speed (air flow), rotate the speed
control knob in the same way.
Centro EC ... G1(GI1): In this case, fan speed switching operations are rare.
The TSI lights up and the fan switches to the maximum speed as the room air temperature exceeds the set point.
As the air temperature drops 2 °C below the set point or if the initial temperature is below the set point, the TSI goes out and the fan
operates with the set speed.
Centro EC ... GT1(GTI1): The speed switching operations are more frequent as compared to the temperature-based functioning logic
G1(GI1), but one speed interval continues at least 5 minutes.
The TSI lights up and the fan switches to the maximum speed as the room air temperature exceeds the set point.
As the air temperature drops down below the set point, the TSI starts blinking, the timer starts a 5-minute countdown and then the fan
switches to the set lower speed and the TSI goes out.
Centro EC ... GS1(GSI1): The fan starts only at a certain air temperature.
The TSI lights up and the fan switches to the set speed as the room air temperature exceeds the set point.
As the air temperature drops 2 °C below the set point or if the initial temperature is
below the set point, the TSI goes out and the fan turns off.
The Centro EC ... FR1 fan is equipped with a built-in smooth speed controller that
enables switching the fan on/off, smoothly adjusting the rotation speed (air flow) in
the range from minimum to maximum speed.
min max
~
~
~
Air flow regulator
min max
21
22
23
24
25 26
27
28
29
30°C20°C
Temperature regulator
Air flow regulator