SHIPPING SPECS
Individual Carton Dimensions 5.3" L x 3.0" W x 5.3" H
Weight: 0.9 lbs.
Cube: 0.1 ft 3
UPC: 0 29054 01814 4
Master Carton Dimensions 19.2" L x 5.8" W x 6.0" H
Master Pack: 6
Weight: 5.6 lbs.
Cube: 0.4 ft 3
I2of5: 600 29054 01814 6
Pallet Information
Cases per Layer: 17
Number of Layers: 8
Cases per Pallet: 136
Units per Pallet: 816
Cube: 59.3 ft 3
Weight: 806 lbs.
ARCHITECTURAL AND ENGINEERING SPEC
The integrated strobe light & combination smoke & carbon monoxide shall be a BRK Model
7030BSLA (Cat. 1038871) and shall provide at a minimum the following features and functions:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
THE PARTS OF THIS ALARM
1. Mounting Bracket
2. Mounting Slots
3. Hot (Black) AC Wire
4. Neutral (White) AC Wire
5. Interconnect (Orange) Wire
6. Quick-Connect Power Connector
7. Turn this way to remove from
bracket (Counterclockwise)
8. Turn this way to attach to bracket (Clockwise)
1.
Alarm
2.
Ceiling or Wall
3.
Power Connector
4.
Wire Nut
5.
Junction Box
6.
Neutral Wire (Wht)
7.
Interconnect Wire (Orange)
8.
Hot Wire (Blk)
A. 120VAC 60 Hz source
B. To additional units; Maximum = 18
total (Maximum 12 Smoke Alarms)
43
5
7
8
6
5
A
B
8
7
3
1
1
3
4 4
5
INSTALLATION OF ALARM
TECHNICAL SPECS
Alarm Dimensions: 5.2" Dia. x 2.3" H
Weight: 10.6oz
Operating Voltage: 120V AC 60Hz with3V SealedLithium
Battery Backup for alarm.
Operating Current: Alarm 0.8 A
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulatessmoke condition, causing
the unit to alarm.Press and hold test/silence button.
Alarm Reset: Automaticwhen smoke clears
Interconnections: Up to 18 unitsof First Alert or BRK Smoke,COand
Heat Alarms. Maximum number of 12 smoke alarms.
Smoke Sensor: Photoelectric
CO Sensor: Electrochemical
Strobe Light: 177 candela LED strobe
Indicator Lights/Sounds:
AC Power: Constant GreenLED
DC Power: Green LEDflash, once per minute
Alarm Condition:Red LEDflashes with audible alarm (horn)pattern and
strobe (flash) pattern
Horn Pattern:Smoke - Approx. 1 beep per second for 3beeps, then 1
second off.CO- 4rapid beeps, then 5 secondsoff.
Strobe Pattern:
Smoke - Constant, approx. 1 flash per second. CO - Approx.
1 flash per second for 4 flashes,then 3 secondsoff.
Silence: Approx.9 minutesSmoke initiatingalarm, approx.
4.5 minutesCOinitiating alarm, 8 hoursEnd of Life
Alarm Latch: Smoke - Horn off and Red LED flashing 2 secondson, 2
secondsoff.CO- Same as smoke but with 4 short red LED
pulses after 2 secondson.
LatchingEnd of Life /
Low Battery Indicator: Green LEDflashing 2 seconds on, 2 seconds off
End of Life Signal /
Low Battery Signal: 5 short chirpswith 5 Green LED flashes once per minute
Listing: Certified to CAN/CSA STD 6.19-01 & ULC STD S531
& ULC STD S526
A photoelectric smoke sensing chamber and electrochemical carbon monoxide sensor.
A 177 candela LED strobe light. The Smart Strobe shall have separate flash patterns to distinguish between
smoke/heat and carbon monoxide dangers. When multiple units installed, strobe flash patterns will synchronize.
Fully screened sensing chamber to resist entry of small insects thereby reducing the probability of unwanted alarms.
Powered by 120V AC, 60Hz and have a sealed 10 year lithium battery backup for alarm and a solid state piezo horn
rated at 85dB at 10 ft and be capable of self-restoring.
A visual green LED power-on indicator to confirm unit is receiving power or is in alarm.
A full function test button. The test button should check all alarm functions by stimulating the chamber to simulate a
smoke condition, causing the unit to alarm.
Two Latching features: Alarm Latch to easily identify initiating alarm after alarm condition has subsided. Low battery
latch: to visually identify which unit is in low battery or end of life condition. Two Silence Features: Alarm Silence to
temporarily silence nuisance alarms. End of Life: Silence alarm for 8 hours.
The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and relative humidity between 10% and 95%.
The unit shall have a plug in connector and be capable of interconnection of up to 18 units with smoke, heat, CO
alarms and relays, of which 12 can be smoke alarms.
The unit shall at a minimum meet the requirements of CAN/CSA STD 6.19-01 & ULC STD S531 & ULC STD S526.
The unit shall have an “End of Life” signal.
© 2021 BRK Brands, Inc. All rights reserved. Distributed by BRK
Brands, Inc., Aurora, Illinois 60504. BRK Brands, Inc. is a subsidiary
of Newell Brands Inc. (NASDAQ: NWL). REV 11/20
brkcanada.ca
TOP VIEW SIDE VIEW
5.3"
2.4"
MOUNTING
BRACKET
Model7030BSLA
CAT. 1038871
10
YEAR
Installation of this smoke alarm must conform to all local electrical codes and Article 760 of the National Electrical Code
(NFPA 70) and NFPA 72. Interconnected units must meet the following requirements: Total length of wire interconnecting
units should be less than 1000 feet, be #18 gauge or larger and be rated at least 300V. It is recommended that all units
be on the same fuse or circuit breaker. If local codes do not permit, be sure the neutral wire is common to both phases.