ARCHITECTURAL AND ENGINEERING SPEC
INSTALLATION OFALARM
The smoke alarm shall be a BRK model 9120BA with battery backup and shall provide
at a minimum the following featuresand functions:
1. A Ionization smoke sensing chamber.
2. The unit shall be capable of self restoring.
3. Fully screened sensing chamber to resist entry of small insects
thereby reducing the probability of unwanted alarms.
5. A visual green LED power-on indicator to confirm unit is receiving power or
is inalarm.
6. A full function test button should check all alarm functions by simulating a smoke
condition, causing the unit to alarm.
7. Silence feature - Temporarily silence unwanted nuisance alarms.
8. Two Locking features - tamper resistant locking pins that lock battery drawer
and/or alarm to mounting bracket.
9. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between10% and 90%.
10. The unit shall have a gasketlessbase for easy installation and be capable of
keeping alarm secure over a wide rotationrange to allow for true alarm
alignment.
11. The unit shall have a plug in connector and be capable of interconnection of up to
18 alarms, 12of which can be smoke alarms.
12. The unit shall at a minimum meet the requirements of CAN/ULC S531.
SHIPPING SPECS:
TECHNICAL SPECS
Individual Carton Dimensions 5.69"L x 2.25"W x 5.59"H
.sbl69.0thgieW
3
tf340.0ebuC
0 29054 01757 4CPU
Master Carton Dimensions 14.43"L x 6.19"W x 12.63"H
Master Pack 12
67 lbs..8thgieW
456.0:ebuC
100 29054 01757 1:5fo2I
Pallet Information
Cases per Layer 19
Number of Layers: 3
Cases per Pallet: 57
Units per Pallet: 684
17.24:ebuC
539.19 lbs.:thgieW
Alarm Dimensions: 5.6” dia x 2.0”H
Weight: 6.5 oz
Operating Voltage: 120V AC 60Hz w/ lithium battery backup
Operating Current: .04 amps (standby/alarm)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 90% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke condition,
causing the unit to alarm
Press and hold test/silence button
Alarm Reset: Automatic when smoke clears
Interconnections: Up to 18 units of First Alert or BRK Smoke, CO and
Heat Alarms. Maximum of 12 smoke alarms. See
user’s manual for details.
Smoke Sensor: Dual chamber ionization
Indicator Lights/Sounds:
ACPower: Constant GreenLED
Local Alarm: Red LED flashes rapidly
Remote Alarm: Red LED out.
Latching Alarm: Green LED flashes 2 sec. on/2 sec. off after local alarm
Listing: Listed to CAN/ULC S531
5.6"
TOP VIEW SIDE VIEW
2.0"
CAT.
9120LBLA
THE PARTS OF THIS SMOKE ALARM
MOUNTING
BRACKET
A.Unswitched 120VAC 60 Hz source
B.To additional units;Maximum= 18 total
(Maximum 12 Smoke Alarms)
1. Smoke Alarm 5. Junction Box
2. Ceiling or Wall 6. Neutral Wire(White)
3. PowerConnector 7. Interconnect Wire (Orange)
4. Wire Nut 8. HotWire(Black)
678
4 3 1
5 2
A
B
}}
4 3 15
DCPower: Intermittent Red LED
4. Powered by 120V AC, 60Hz and have a 10 year sealed lithium battery backupmodel
anda solid state piezo hornrated at 85dB at 10 ft.
1. Mounting bracket
2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Nuetral (White) AC Wire
6. Interconnect (Orange) Wire
7. Quick-Connect Plug
1
2
3
5
6
4
2
3
7
7
8
Installation of this smoke alarm must conform to all
Canadian electrical code Interconnected units must meet
the following requirements: wire gauge to be per
local codes. It is recommended that all units be on
the same fuse or circuit breaker. If local codes do not
permit, be sure the neutral wire is commonto both phases.