BSB FSD-C Series User manual

SD-C Series
Circular Single Blade
Combination ire and
Smoke Damper
•ES classified fire dampers with reduced smoke leakage characteristics to
BS EN 1366-2 (test standard) and BS EN 13501-3 (extended field of application)
•Aerodynamically Air Control tested to BS EN 1751
•Tested and assessed installation methods in differing support constructions
BS EN 1366-2
•Rotatable cleats®
•Can be installed from one side of the fire separation without the need to fit a
secondary installation plate or provide fire-rated infill material
•Replaceable thermal fuse element from outside of the duct.
•Commissioning friendly
•Blade Position Indicator
•IP54 degree of protection
•Test switch for periodic damper testing
•LED green indication when lit indicates that a supply voltage is present and that the
temperature fuses are operational
•Damper casings conform to BS EN 1506
•CE marked complying with the requirements of EN 15650
M
A
D
E
I
N
B
R
I
T
A
I
N
M A N U A C T U R E R S O A I R , I R E A N D S M O K E C O N T R O L P R O D U C T S
V12103

Introduction
What is a fire damper and why might they be needed?
The SD-C Series Single Blade Circular ire Damper is designed to
stop the spread of fire through ducts passing through walls and
floors.
The product range has many features and options to meet the
requirements of specifiers, contractors, local and national authorities.
Dampers are available to suit both low/medium and high velocity
applications.
What are the ‘E’ and ‘ES’ classifications?
To achieve the classifications to EN13501-3, fire dampers and fire
and smoke dampers shall be tested to EN1366-2 and a 300Pa
pressure difference is applied across the damper. During the fire
test period, the integrity of the seal between the damper and the
structure shall not have any gaps larger than 150mm x 6mm. There
shall not be any sustained flaming. The largest size of damper to be
manufactured for sale as a single section shall be fire tested.
E = Integrity
The maximum leakage permissible at 300Pa corrected to 20°C is
360m3/hr/m2(100 l/s/m2) throughout the fire test period.
ES = Integrity with Smoke Leakage Performance
The maximum leakage permissible at 300Pa corrected to 20°C is
200m3/hr/m2(55.5 l/s/m2) at ambient prior to the fire test and
throughout the fire test period. In addition, for the ES classification to
be attained, the smallest damper must also meet the 200m3/hr/m2
maximum leakage with a 300Pa pressure across the damper. (This is
equivalent to just 0.55 l/s on a 100x100 damper)
ire dampers should be installed as tested.
Some applications (fan off) allow the use of tests undertaken to BS
476-20/22 and this is also allowed worldwide in areas outside of the
EU. Test reports showing testing to EN 1366-2 should be acceptable
to meet the requirements of BS 476-20/22, but the reverse is
definitely not the case and no classifications are available.
However, as a word of caution, in whichever case, the correct model
must be selected, to match fire resistance time with installation
method and with the supporting construction (wall or floor).
To ensure that all testing and assessments are traceable back to
initial fire test reports, the BSB SD-C series is product certificated by
the Loss Prevention Certification Board (LPCB). This means that in
addition to normal BS EN ISO 9001 compliance, the product is also
checked to ensure that same product is being manufactured that has
been tested or assessed.
BSB have a policy of continued testing and product certification to try
and provide as broad a number of installation methods as possible.
BSB also follow regulation and standards development very carefully
to provide input on changes and to be able to pass on relevant
information to designers, specifiers, building control authorities
(BCA's) and installers.
Introduction
The SD-C Motorised ailsafe Single Blade combination ire
and Smoke Damper has been designed specifically for
installations where space is at a premium and installation within
the fire separation is not feasible.
The SD-C Single Blade ire/Smoke Damper provides greater
free area than comparable sized conventional multi blade
fire/smoke dampers.
The installation plate, with its engineered installation
perforations, acts as a template to allow the marking of the fixing
positions on the surface structure to which the plate will be
affixed, allowing for a quick and efficient install.
Testing and Conformities
Tested to EN1366-2. See installation details for full details.
Damper casings conform to BS EN 1506
Tested/assessed and achieved equivalent classification to:
ES Classification (BS EN 1366-2/BS EN 13501-3)
•BSB SD-C fitted with Installation Plate
E180 - Blockwork/Masonry wall
ES120 - Blockwork/Masonry wall
ES90 - Concrete floor
ES120 - Horizontal application
(please refer to BSB sales office)
ES90 - Horizontal application
(please refer to BSB sales office)
E120 - Dry Partition wall
ES120 - Dry Partition wall
Integrity only (BS 476-20/22 - ADB)
Meets the requirements of BS 476-20/22 -
Refer to BS 476-10.6.6.3
SD-C Blade leakage (BS EN 1751)
•Class 2
Corrosion Testing
BBA test report 50447 issue 2 refers
•Tested to BS EN 60068-2-11:1999
SD-C Series
Single Blade Combination ire and Smoke Dampers – Introduction
www.bsb-dampers.co.uk
2
SD-C eatures and Benefits
•Tested and certified installation variants of the SD-C are
available for both blockwork and stud partitions.
•All BSB tested installation methods give at least a E90
classification.
•Unique blade construction.
•Halogen free LS cable
•Exceeds the requirements of EN1366-2
•Reduced commissioning time
•Thermal fuse replaceable external to the duct.
•Test switch integral to the thermal fuse allowing the damper
to be tested locally and individually.
•LED indication that power is available to the actuator and the
thermal fuse is intact.
•Installation plate with template location holes to allow easy
installation.

SD-C100 - 100mm dia.
SD-C125 - 125mm dia.
SD-C150 - 150mm dia.
SD-C160 - 160mm dia.
Typical Tender/Specification Text
The BSB SD-C combination ire and Smoke Damper
shall pass the test requirements stated in EN 1366-2.
or maintenance of the integrity of compartmentation the
fire damper shall have an E classification to EN 13501-3.
The damper shall have an ES classification complying with
EN1366-2 and EN 13501-3 and have a minimum E120 and
ES120 rating.
or the protection of escape routes and areas with sleeping
risk, the SD-C fire/smoke damper should be used. Please
refer Approved Document B (ADB).
The single blade layered design shall be held open against
the constant force of the fitted actuator that is released to
spring closed via the activation of the fitted thermal fuse
rated at 72°C.
The damper actuator assembly shall be safely tested and
released closed externally to the damper without the need
for specialist tools.
The fire damper body shall be fully welded to meet the air
tightness test requirements of HVCA specification DW144
to class A B & C to a maximum of 1000Pa and comply with
EN1751.
The closed blade shall meet the air tightness test
requirement of BS EN 1751 Class 2.
The BSB SD-C combination ire and Smoke Damper
shall have a tested or assessed installation method that
matches the requirement of the supporting construction.
DW145 Method 4 Blockwork Walls and Partition Walls
refers.
Leakage Classification
Blade leakage classification is given numerically and case
leakage classification is given using capital letters.
•Class 4, 3, 2 or 1 refers to blade leakage –
EN1751 section C.2 refers
•Class 4 achieving the lowest leakage.
•Class A, B or C refers to casing leakage -
EN1751 section C.3 refers
•DW144 part 8 table 17 and figure 178 refers.
•Class C achieving the lowest leakage at elevated
pressures.
The above references are illustrated in the graphs on
Pages 10, 11 and 13 of this brochure.
SD-C Series
Single Blade Combination ire and Smoke Dampers – Introduction
3
www.bsb-dampers.co.uk
Thermal use
The BSB PML24-T and PML230-T
actuators incorporate a thermal
fuse (T ), which operates at 72°C.
The thermal fuse will be factory fitted to
the SD-TD series damper a quick visual
check as standard, unless requested
otherwise.
The thermal fuse has a green LED indicator
which provides a quick visual check that the
fitted actuator is receiving power and that the
thermal fuse is intact.
A momentary push test switch is included within the thermal
fuse head for periodic testing of the damper.
or reasons of safety the thermal fuse is designed to operate
only once upon reaching the activation temperature. Cutting
the cable to the thermal fuse with the power on will trip an
electrical fuse within the actuator, rendering it inoperable.
The SD-C Series Range
The BSB SD-C series is available in the following case
diameters:
SD-C200 - 200mm dia.
SD-C250 - 250mm dia.
SD-C300 - 300mm dia.
SD-C315 - 315mm dia.
Damper Control Panels
BSB offer two alternative damper control panels when
monitoring and controlling dampers. The Electro Mechanical
System and the ully Addressable System. Please contact our
sales office or consult relevant product brochures for further
information.
Nom. Dia.
(mm) 320mm 320mm 420mm Total
no inst.plate with inst. plate no inst.plate Weight
0.7 2.7 2.5 2.8
1.0 3.0 2.7 3.2
1.2 3.3 3.1 3.5
1.2 3.3 3.2 3.5
1.8 4.0 3.7 4.3
2.6 4.9 4.6 5.3
3.7 6.2 5.7 6.6
4.0 6.6 6.1 7.0
100
125
150
160
200
250
300
315
Damper Weight Chart Including Actuator (kg approx.)

Installation Plate
The installation plate allows the damper
to be fixed into place from one side only
with no infill material being required on the
other open side
Use either of the two appropriate 5mm dia.
corner fixing holes and all of the 5mm dia.
mid span fixing holes to secure the plate into
position.
Thermal use
Thermal use rated at 72°C
is factory fitted and is replaceable
external to the damper case.
The thermal fuse is fitted with a
green LED indication light which
provides a quick visual check that
the actuator is receiving power
and that the thermal fuse is
operational. A manual momentary
push test switch for periodic testing
of the damper is also included
Blade Seal (patented)
Layered glass woven sheets
and central intumescent disc to
a patented design that allows
the blade assembly to be of
minimal thickness, thus
minimising pressure loss,
providing an effective seal to
comply with
EN 1366-2 achieving ES
classification.
Blade
Galvanised 1.2mm one piece
circular steel discs either side of
the patented seal design
providing a 5mm thick assembly
affixed by blade brackets to the
drive spindle. Grade 430
stainless steel blade option
available.
PML-T Actuator
The PML-T actuator is a
spring return actuator. The
PML-T actuator is available
as 24 volt or 230 volt.
Case
Galvanised mild steel to
BS EN 10346 DX 51D Z275 0.8 0.1mm
Damper casing conforms to BS EN 1506.
SD-C Series
Single Blade ire and Smoke Dampers – Product Specification
4www.bsb-dampers.co.uk
+
––

Velocity (m/s)
Performance Data
Pressure Drop (Pa)
110 11 12
67.5° from open
45° from open
22.5° from open
ully open
Pressure Drop Graph - Model SD-C100
100mm diameter.
ree area = 64%
Velocity range 0 to 10 m/s
Velocity (m/s)
1000
100
10
1
Pressure Drop (Pa)
110 11 12
67.5° from open
45° from open
22.5° from open
ully open
Pressure Drop Graph - Model SD-C200
200mm diameter.
ree area = 85%
Velocity range 0 to 10 m/s
Velocity (m/s)
1000
100
10
1
1 10 11 12
67.5° from open
45° from open
22.5° from open
ully open
Pressure Drop Graph - Model SD-C300
300mm diameter.
ree area = 91%
Velocity range 0 to 10 m/s
Pressure Drop (Pa)
Time / Temperature Curve - EN13501-4:2007
Standard Curve
BRE Test 279799
Time (minutes)
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
0 30 60 90 120 150
Temperature (°C)
1000
100
10
1
SD-C Series
Single Blade ire and Smoke Dampers – Performance
5
www.bsb-dampers.co.uk

SD-C Series
Single Blade Combination ire and Smoke Dampers – Product Dimensions
6www.bsb-dampers.co.uk
Note: All dimensions are nominal and may change due to varying coil widths
The SD-C Series - ire/Smoke Damper
Diameter
Plate Size (See Below)
*
60
60
46 mm
25mm
46mm
5mm
25mm
3.3mm
5mm
Installation Plates
SD-C100
SD-C125
SD-C150
SD-C160
SD-C200
SD-C250
SD-C300
SD-C315
100
125
150
160
200
250
300
315
Model
Diameter
60
17mm
radius
corners 60
Installation Plate ixing Hole Detail
Damper ree Area
SD-C100
SD-C125
SD-C150
SD-C160
74%
80%
84%
85%
Model ree Area
SD-C200
SD-C250
SD-C300
SD-C315
88%
90%
92%
92%
Model ree Area
220
245
270
280
320
370
420
435
60
60
60
60
60
60
60
60
Plate Size
(mm2)
lange
Size
(mm)
40
40
40
40
40
60
60
60
Spigot
Length
(mm)
Dia.
(mm)
151.540 73.5 40
Diameter
420
115
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

SD-C Series
Single Blade ire and Smoke Dampers – Product Testing
7
www.bsb-dampers.co.uk
SD-C in Blockwork Wall
BLOCKWORK
WALL
INSTALLATION
PLATE
A
CKWORK
CKWORK
L
LAT
ION
O5 X 50 LODEN
ANCHORS
used to secure damper
installation plate to
blockwork
1500
150
1500
750
750
A
VIEW FROM INSIDE FURNACE
No infill
required thus
allowing ease
of installation
as tested
,
,
::
::
. . .
(. )
...
/
/
/
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Test Conclusions:
The SD-C combination ire and Smoke Damper satisfied
the requirements of BS EN 1366-2 and BS EN 13501-3
achieving the lowest closed blade leakage of any damper
within its class.
Dampers were tested affixed to the inside of the furnace
wall and also to the external wall of the furnace with the
damper closed blade being fully exposed to the furnace
rapid rising temperature.
The achieved ES classification ensures that in a fire
condition the non fire side is fully protected (from radiated
heat) for the achieved period, providing vital time for the
emergency services to respond, ensuring safe passage of
escape and protection of contents.
See Page 5 for Pressure Drop Graphs
Blade Leakage Graph
1000
100
10 1 10 100
Leakage (l/s/m2)
Pressure Drop (Pa)
300mm dia.
200mm dia.
100mm dia.
Case Leakage Graph - Model SD-C100
2000
1000
100
10
0.01 0.1 1
Leakage (l/s/m2)
Duct Pressure (Pa)
Leakage
EN1751 Class C
EN1751 Class B
EN1751 Class A
EN1751 - Class 4
EN1751 - Class 3
EN1751 - Class 2
•Tested to BS EN 1366-2 and BS EN 13501-3
•E180 integrity classification.
•ES120 integrity classification.
•ES90 horizontal concrete floor.
•Complies with classes A, B & C of DW144.
•Surpasses minimum requirements on case leakage
•Surpasses minimum requirements on blade leakage
Tested to BS EN 1366-2
The SD-C series damper has been tested both
ways, with access side inside the furnace and non-
furnace side.
The addition of the PML actuator allows this tested product to become fully automatic in its operation via the fire detection
system or one of the BSB control panels. To comply with the forthcoming revision of the fire damper test standard.

SD-C in Dry Wall - Actuator inside and outside of furnace
VIEW FROM NON-FURNACE SIDE
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•Tested to BS EN 1366-2 and BS EN 13501-3
•E120 integrity classification.
•ES120 integrity classification.
•Complies with classes A, B & C of DW144.
•Surpasses minimum requirements on case leakage
•Surpasses minimum requirements on blade leakage
•Damper casing conforms to BS EN 1506
Test Conclusions:
The SD-C combination ire and Smoke damper satisfied
the requirements of BS EN 1366-2 and BS EN 13501-3
achieving the lowest closed blade leakage of any damper
within its class.
Dampers were tested affixed to the inside of the furnace
wall and also to the external wall of the furnace with the
damper closed blade being fully exposed to the furnace
rapid rising temperature.
The achieved ES classification ensures that in a fire
condition the non fire side is fully protected (from radiated
heat) for the achieved period, providing vital time for the
emergency services to respond, ensuring safe passage of
escape and protection of contents.
Tested to BS EN 1366-2
Test Report No. 279799 refers
The SD-C single blade combination fire and smoke
damper with its unique feature of requiring only a single
installation plate when being installed within tested
applications, and without the need for any infill between the
damper body and the structure that it sits within. Is the first
damper of its type to achieve and exceed the requirements
of classification EN1366-2.
SD-C Series
Single Blade ire and Smoke Dampers – Product Testing
8www.bsb-dampers.co.uk

SD-C in Dry Wall
Test Report No. 279799 refers
Actuator outside of furnace
FURNACE
SIDE
DRY WALL SCREWS
38 LONG x 300
CENTRES
GTEC FIREBOARD
360 x 122 x 12.5
TYPE 5
PLASTERBOARD
GTEC FIREBOARD
ROCKWOOL
FLEXI SLAB
(35KG/M3)
DRY WALL
SCREWS
38 LONG
DRY WALL SCREWS
25 LONG
O7.5 X 60 LONG STEEL FIXINGS
AT 600 CENTRES
INSTALLATION
PLATE
UT 72/R
TRACK
315MM DIA. DAMPER TESTED
NON
FURNACE
SIDE
SD-C in Dry Wall
Test Report No. 279799 refers
Actuator inside of furnace
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FURNACE
SIDE
NON
FURNACE
SIDE
315MM DIA. DAMPER TESTED
DRY WALL SCREWS
38 LONG x 300
CENTRES
GTEC FIREBOARD
360 x 122 x 12.5
TYPE 5
PLASTERBOARD
GTEC FIREBOARD
ROCKWOOL
FLEXI SLAB
(35KG/M3)
DRY WALL SCREWS
38 LONG
DRY WALL SCREWS
25 LONG
O7.5 X 60 LONG STEEL
FIXINGS AT 600 CENTRES
INSTALLATION
PLATE
UT 72/R
TRACK
See Page 5 for Pressure Drop Graphs
Blade Leakage Graph
1000
100
10
1 10 100
Leakage (l/s/m2)
Pressure Drop (Pa)
300mm dia.
200mm dia.
100mm dia.
Case Leakage Graph - Model SD-C100
2000
1000
100
10
0.01 0.1 1
Leakage (l/s/m2)
Duct Pressure (Pa)
Leakage
EN1751 Class C
EN1751 Class B
EN1751 Class A
EN1751 - Class 4
EN1751 - Class 3
EN1751 - Class 2
SD-C Series
Single Blade ire and Smoke Dampers – Product Testing
9
www.bsb-dampers.co.uk

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
122
Diameter
Dry Wall Screws 38mm
long to affix installation
plate ensuring fixing
into dry lining metal frame
No infill
required,
thus allowing
ease of installation
as tested
43
43
Installation Method
DW145 Method 4 - Blockwork walls
DW145 Method 4 - Partition walls
SD-C Series
Single Blade ire and Smoke Dampers – Installation and Maintenance
10 www.bsb-dampers.co.uk
Maintenance Notes
SD-C Series combination ire and Smoke Dampers are
designed for normal dry filtered air systems. A programme of
planned inspections should be carried out to include full
operational checks, correct interface with, and function of, any
control systems, cleaning and light lubrication.
As a guide, this should take place annually. Please refer to
BSB Operating and Maintenance instructions.
Reference should be made to BS 9999 for more information.
Records of damper installation and position shall be kept.
Records of the condition of the dampers and their
functionality/repair etc should be kept as these products come
under the requirements of the Regulatory Reform ( ire safety)
Order (RR SO).
These inspection and maintenance programmes may need to
be repeated more regularly if the dampers are exposed to
inclement/dusty conditions or fresh air intakes and the
frequency of such checks should be developed based on site
experience.

SD-C Series
Single Blade Combination ire and Smoke Dampers – Actuators
11
www.bsb-dampers.co.uk
BSB SD-C-T Electric Actuator Specifications
~
1 Black
2 Red
S1 Violet
S2 Red
S3 White
S4 Orange
S5 Pink
S6 Grey
LEDT1Tf
<5° <80°
Common
NC
NO
Common
NC
NO
Damper
Closed
Damper
Open
BSB PML230-T
DAMPER ENERGISED OPEN / SPRING CLOSED
Supply 230V AC 50/60 Hz
• Wiring diagram shows switch positions based on no power to actuator
•Power On - Damper blades drive open
•Power Off - Damper to spring closed
•Electric thermal release rated at 72°C
•External position indicator
• Adjustable blade position stop
Release Time: 15 secs ; Reset Time: 40 secs
7VA Typically 5W motoring, 4W holding
or wiring size – Imax 5.8A @ 5ms
Operating temperature range -30° to +50° continuous.
Connecting cables need to be protected from sharp edges
Unused cores should be isolated
or damper closed indication use terminals 1 & 2
or damper open indication use terminals 4 & 6
Terminals 1 & 4 can be linked where required as an option
1 Blue
2 Brown
S1 Violet
S2 Red
S3 White
S4 Orange
S5 Pink
S6 Grey
LEDT1Tf
<5° <80°
Common
NC
NO
Common
NC
NO
Damper
Closed
Damper
Open
NL
or disconnection from
the supply, a separate
device must be
incorporated in the fixed
wiring (at least 3mm
contact gap in all poles)
Where the manual adjustment is required and fitted, open indication to be provided by contacts 1 and 3.
BSB PML24-T
DAMPER ENERGISED OPEN / SPRING CLOSED
Supply 24V AC/DC 50/60 Hz
•Wiring diagram shows switch positions based on no power to actuator
•Power On - Damper blades drive open
•Power Off - Damper to spring closed
• Electric thermal release rated at 72°C
• External position indicator
• Adjustable blade position stop
Release Time: 15 secs ; Reset Time: 40 secs
7VA Typically 5W motoring, 2.5W holding
or wiring size – Imax 5.8A @ 5ms
Operating temperature range -30° to +50° continuous.
Connecting cables need to be protected from sharp edges
Unused cores should be isolated
or damper closed indication use terminals 1 & 2
or damper open indication use terminals 4 & 6
Terminals 1 & 4 can be linked where required as an option
The SD-C S ire/Smoke Damper is supplied fitted with either a PML24-T or PML230-T spring return actuator where
the damper fail safe operation is via a thermal fuse or purpose supplied damper control panel
PML24-T (as illustrated) PML230-T
Voltage 24volt AC/DC 230volt AC
Power Consumption Operating: 4W (watts); At rest: 1.4W (watts) Operating: 5W (watts); At rest: 2.1W (watts)
Cable itted Power: 1m, 2 x 0.75mm21m, 2 x 0.75mm2
Cable itted Aux. Switch: 1m, 6 x 0.75mm21m, 6 x 0.75mm2
(Cables are halogen free)
Control Spring return closed Spring return closed
Torque Motor: 9Nm 9Nm
Spring Return: 7Nm 7Nm
Running Time: Motor: 40 seconds 40 seconds
Spring Return: 15 seconds 15 seconds
Sound Power Level 55dB (A) 55dB (A)
Spring Return: 67dB (A) 67dB (A)
Operating Temp. Range -30°C to +55°C -30°C to +55°C
Degree of Protection IP54 IP54
Mounting Actuator coupling is located onto a 12mm square on the 8mm dia shaft and secured by two bolts through the
actuator into rivet nuts affixed to the three position mounting bracket. A centre bolt and pointer are also used.
Connect via
safety
isolation
transformer
Motor Weights: PML24-T / PML230-T : 1.5kg PML24-NT / PML230-NT : 1.8kg

Rotatable Easy Bend Cleats
The optional Rotatable Cleat Easy ix System will be supplied
factory fitted to the SD-C Series dampers.
The installation plate should be fitted to the fire separation barrier
to ensure test conformity is maintained. The Easy Bend Cleat is
available factory fitted four per plate. The cleats should only be
used where the fire separation element is not yet in place,
offering a temporary installation support. The cleats must not be
the sole independent method of supporting the fire damper.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The cleats can easily be bent out using a flat head screwdriver.
Supporting drop rods are used in the normal way.
The cleats can be rotated through 90 degrees to suit handle
position where the damper requires to be installed with the
handle either left, right, top or bottom giving full flexibility during
installation.
SD-C Series
Single Blade ire and Smoke Dampers – Cleats
12 www.bsb-dampers.co.uk

SD-C Series
Single Blade Combination ire and Smoke Dampers – Cleats
13
www.bsb-dampers.co.uk
Rotation point
around single rivet
Corner
fixing holes
Cleats
Rotatable cleats are available as an optional accessory where requested and will be
provided factory fitted as shown right.
The D-C series damper must be installed as per BSB installation, operating and
maintenance document to comply with CE marking.
The use of cleats as the sole installation/support method will not comply with CE
marking rules.
Where cleats are requested to be fitted and local authority approval has been given,
the drop rod system will be the responsibility of others.
ixing Kit
ixing cleat (4) kits are available for retro fixing, please refer to the sales office.
Diameter
28
28
52
55
O10.5
M6
M8
6
8
1.00
1.25
Pitch
4.772
6.465
Core D
Drop Rod Studding Minimum Recommended Diameter
Minimum loads are taken from the AS P Blue Book and refers to unprotected steel
studding, generally up to 1.5m long. igures shown must be read in conjunction with
the AS P Blue Book.
60 mins - 15n/mm 2 Min. load
>
OD Max. load per pair of
studs (kg)
54.7
100.4
17.9
32.8
CSA
(mm 2)
>
M6
M8
6
8
1.00
1.25
Pitch
4.772
6.465
Core D
120 mins - 10n/mm 2 Min. load
>
OD Max. load per pair of
studs (kg)
36.5
66.9
17.9
32.8
CSA
(mm 2)
>
11

BSB Engineering Services Limited
Unit 56, Trinity Trade Centre, Mill Way, Sittingbourne, Kent ME10 2PD, UK • Tel: +44 (0)1795 422609
or purchase orders and order related enquiries, please email: orders@bsb-dampers.co.uk
or pricing, technical and general enquiries, please email: enquiries@bsb-dampers.co.uk
Website: www.bsb-dampers.co.uk • A member of the Maico group
BSB Engineering Services Ltd. reserves the right to modify or withdraw any specification without prior notice that may result from
continuous product development. The information contained within this brochure is correct at the time of going to press. ( SDC-03-2020)
Model:
SD-C
Externally Resettable Circular
Single Blade Combination
ire and Smoke Damper
Blade Material:
GGalvanised Mild Steel
S430 Grade Stainless Steel
Installation Plate:
IP Installation Plate
Accessories:
CL Cleats
SD-C G IP CL 200 PML24-T
SD-C Series
Single Blade Circular ire Dampers – Ordering Codes
Application / Motor Type:
PML24-T 24 volt Spring Return Actuator with Thermal use
PML230-T 230 volt Spring Return Actuator with Thermal use
PML24-NT 24 volt Spring Return Actuator no Thermal use
PML230-NT 230 volt Spring Return Actuator no Thermal use
M
A
D
E
I
N
B
R
I
T
A
I
N
MADE IN BRITAIN
SOLD TO THE WORLD
bre Testing facilityMember of HEVAC AssociationMember of ADCAS Association
Diameter:
100 100mm Diameter
125 125mm Diameter
150 150mm Diameter
160 160mm Diameter
200 200mm Diameter
250 250mm Diameter
300 300mm Diameter
315 315mm Diameter
or full details of the complete BSB Product Range, please refer to our individual product brochures, sales office or website.
Other Air, ire and Smoke Control Products in the BSB Range:
A60 Series
Marine ire Dampers
D Series
ire Dampers
Control Systems
D-C Series
Circular ire Dampers
BD Series
Backdraught Dampers
HD Series
Heavy Duty Dampers
SS Series
SlimSeal Dampers
SD-TD Series
ire/Smoke Dampers
ETD Series
Elevated Temperature Dampers
VC Series
Volume Control Dampers
Standard
Electrical Mechanical
Premier
Electrical Mechanical
Addressable
Other manuals for FSD-C Series
1
This manual suits for next models
8
Table of contents
Other BSB Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Lindab
Lindab CFDM technical information

Mandik
Mandik FDMB installation instructions

Swegon
Swegon REACT Pa Instructions for use

SMAY
SMAY KWP-L Technical documentation

Greenheck
Greenheck FD Series Installation, operation and maintenance instructions

Honeywell
Honeywell TrueZONE EARD Series installation instructions