Mandik SEDS-L User manual


1
These technical specifications state a row of manufactured sizes and models of smoke extraction dampers - single
(further only dampers) SEDS-L. It is valid for production, designing, ordering, delivery, maintenance and operation.
1. Description.........................................................................................................................
2
2. Design................................................................................................................................
3
3. Dimensions, weights...........................................................................................................
8
4. Placement and Assembly....................................................................................................
10
5. Pressure drops...................................................................................................................
12
6. Noise data………………………………...............................................................................
12
7. Material............................................................................................................................. 14
8. Inspection, testing............................................................................................................. 14
9. Logistic terms....................................................................................................................
14
10. Assembly..........................................................................................................................
14
11. Entry into service and revisions.........................................................................................
15
12. Spare parts.......................................................................................................................
15
13. Product label....................................................................................................................
16
14. Ordering key.................................................................................................................….
16

2
Smoke extraction dampers - single are shutters in smoke exhaust piping systems. Dampers are
designed to remove heat and combustion products (e.g. smoke) from single fire compartment.
In the event of fire the Smoke and Fire ventilation system opens the damper in the affected
section which removes combustion products and heat from this section.
The damper blade is operated by an actuating mechanism.
The dampers can be installed in various duct sizes with respect to the field of direct applications
according with EN 1366-9.
The field of direct applications based on tests results is acceptable according to EN 1363-1,
part A.1 and A.2, EN 1366-2, part 13 and EN 1366-10, part 9.
Smoke extraction dampers - single are classified as
The duct can be ended by KMM (TPM 002/96) grilles.
Damper characteristics
• CE certified acc. to EN 12101-8
• Tested in accordance with EN 1366-10
• Classified acc. to EN 13501- 4+A1
• External Casing leakage min. class B, Internal leakage min. class 3 acc. to EN 1751
• Cycling test in class C 10000 acc. to EN 12101-8
• ES Certificate No. 1391-CPR-2018/0106
• Declaration of Perfomance No. PM/SEDS-L/01/20/1
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c

3
Working conditions
Dampers are designed for smoke exhaust piping systems with underpressure max. 1500 Pa or
overpressure max. 500 Pa.
Dampers are designed for maximum air velocity 12 m.s.
Dampers are installed with the horizontal or vertical axis of the blades.
Dampers are intended for installation on air ducts and in/onto the walls where in the case of wall
installation, this wall with damper does not have fire resistance and therefore does not separate
two fire compartments.
Dampers are suitable for systems without abrasive, chemical and adhesive particles.
Dampers are designed for macroclimatic areas with mild climate according to EN 60 72133.
Temperature in the place of installation is permitted to range from - 20°C to + 50°C.
Design with actuating mechanism
SEDS-L is equipped by actuating mechanism Belimo BLE24 (BE24-12) for 24V supply or
BLE230 (BE230-12) for 230V supply. After being connected to power supply the actuating
mechanism displaces the damper blade into operation position "OPEN" or „CLOSED“ (according
to method of connection, see connection diagram). Running time is max. 60s. If is power supply
cut off, actuating mechanism is stopped in actual position. The crank handle supplied with the
actuator allows it to be operated manually. Signaling of the damper blade positions "OPEN" and
"CLOSED" is provided by means of two integrated, invariably set terminal switches.

4
2
1
N
S3S2
S1 S6S5S4
<3° <87°
Parrallel connection of other driver is possible.
Pay attention to the power input data.
3
L1
Nominal voltage AC 24V 50/60Hz
DC 24 V
AC 230 V 50/60Hz
Power consumption - motoring
- holding
7,5 W
< 0,5 W
5W
< 1 W
Dimensioning 9 VA (Imax 2,7 A @ 5 ms) 12 VA (Imax 6 A @ 5 ms)
Protection class III II
Degree of protection IP 54
Running time for 95° < 30 s
Ambient temperature range
Non-operating temperature
- 30 °C … + 50 °C
- 40 °C … + 80 °C
Connecting - motor
- auxiliary switch
cable 1 m, 3 x 0,75 mm
cable 1 m, 6 x 0,75 mm
(BLE 24-ST) with plug-in connectors
~
+-
S2S1 S3 S5S4 S6
BLE24-ST: Design with connector plugs for communication
Connection through
an insulation transformer.
to network and communication device BKNE230-24
Parrallel connection of other driver is possible.
Pay attention to the power input data.
2
13
<3° <87°

5
Nominal voltage AC 24V 50/60Hz
DC 24 V
AC 230 V 50/60Hz
Power consumption - motoring
- holding
12 W
0,5 W
8W
0,5 W
Dimensioning
18 VA (Imax 8.2 A @ 5 ms)
15 VA (Imax 7.9 A @ 5 ms)
Protection class III II
Degree of protection IP 54
Running time for 95° < 60 s
Ambient temperature range
Non-operating temperature
- 30 °C … + 50 °C
- 40 °C … + 80 °C
Connecting - motor
- auxiliary switch
cable 1 m, 3 x 0,75 mm
cable 1 m, 6 x 0,75 mm
(BE 24-ST) with plug-in connectors

6
Design with the communication and power supply unit
Design with the communication and power supply unit BKNE230-24 and the actuating mechanism
BLE24(BE24-12)-ST.
BKNE230-24 functions as a decentralized network device for supplying the actuating mechanism
BLE24(BE24-12)-ST on one hand and on the other hand it transmits signals from communication
and control device BKSE24-6.
It simplifies electrical wiring and interconnection of dampers. It facilitates on site check and
enables central control and checks of fire damper by means of a simple 2-conductor wiring.
BKNE230-24 signals the damper position „OPEN“/„CLOSED“ (from switches on the actuator)
and any fault alarms to the BKSE24-6 unit. It also receives positioning commands from the
control unit and triggers the actuator to the required position. The last control command is
retained troughout temporary power failures.
The BKNE230-24 unit monitors the positions of the switches on the actuator, its running time and
the exchange of data with the control and monitoring unit BKSE24-6. It also monitors the actuator
current and the power supply. In order to make installation as simple as possible the smoke
extraction damper actuators ...-ST are fitted with plug connectors that can be inserted directly into
the BKNE230-24 unit.
The 2-wire conductor must be connected to screw terminals 6 and 7. It is recommended that a
fire alarm signal cable suitable for the application be used for the 2-wire conductor. It is essential
to ensure the correct polarity.
More information in catalogue Belimo.

7
Communication and control devices
Nominal voltage AC 230V 50/60Hz
Power consumption 10 W (including actuating mechanism)
Dimensioning 19 VA (including actuating mechanism)
Degree of protection II
Ambient temperature range
Non-operating temperature
- 30 °C … + 50 °C
- 40 °C … + 80 °C
Connecting - net
- actuator
- terminal board
cable 1 m without plug
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm
BKSE24-6 indicates operating status and fault signals for the smoke extraction dampers. The
auxiliary contacts that are incorporated also allow functions to be signaled or passed on to
higherlevel control systems. The signals from the BKNE230-24 unit are received by the
BKSE24-6 unit and evaluated individually. All BKNE230-24 units are triggered simultaneously.
To BKSE24-6 can be connected max. 6 BKNE230-24.
Communication is via the 2-wire conductor. Correct operation of the dampers is indicated by
means of two LEDs. The operating status of the SBSE-Control system and any faults are also
indicated by this LED and the corresponding fault LED.
The BKSE24-6 unit can be clipped directly to a 35 mm DIN mounting rail and connected by
means of two 9-pole plug-in terminals. The BKSE24-6 unit isn´t in the scope of delivery MANDIK
company.
17
an insulation transformer.
~
AC 24 V
18
SMOKE EXTRACTION
Connection through
15
16
13
14
2
1
4
3
6
5
7
9
8
11
12
10
+
-
U
a1...a6
a1...a6
BKNE230-24
Input 2
(isolated)
AUTO
CEASE SMOKE EXTRACTION
COM
Delay 0 s (Fan)
Delay 60 s (Fan)
OPEN
CLOSED
*Fault (Error)
*Inverted output: fault = contact open
Input 1

8
1 Damper body
2 Damper blade
3 Actuating mechanism cover
Dimensions
Nominal voltage AC 24 V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 5,5 VA 18 VA (Imax 6.4 A @ 2.5 ms)
Protection class III
Degree of protection IP 20
Ambient temperature range 0 … + 50 °C
Connecting screw terminals for cable 2x1,5 mm2
[mm] [mm]
BLE 176,5 300
BE 186,5 380
BLE + BKNE 236,5 300
BE + BKNE 251,5 380
* standard height of the flange

9
Weights and effective area cross section
1 14.3 0.0227 BLE 1 17.6 0.0511 BLE
2 16.4 0.0270 BLE 2 20.3 0.0608 BLE
2 17.3 0.0350 BLE 2 21.5 0.0788 BLE
2 18.3 0.0430 BLE 2 22.6 0.0968 BLE
2 19.2 0.0510 BLE 2 23.8 0.1148 BLE
3 21.2 0.0554 BLE 3 26.4 0.1246 BLE
3 22.2 0.0634 BLE 3 27.6 0.1426 BLE
3 24.1 0.0794 BLE 3 30.0 0.1786 BLE
4 27.0 0.0917 BLE 4 33.7 0.2063 BLE
4 28.9 0.1077 BLE 4 36.1 0.2423 BLE
5 34.5 0.1200 BE 5 42.5 0.2700 BE
5 36.4 0.1360 BE 5 44.8 0.3060 BE
6 39.3 0.1483 BE 6 48.6 0.3337 BE
6 41.2 0.1643 BE 6 51.0 0.3697 BE
1 15.1 0.0298 BLE 1 18.4 0.0582 BLE
2 17.4 0.0355 BLE 2 21.3 0.0693 BLE
2 18.4 0.0460 BLE 2 22.5 0.0898 BLE
2 19.4 0.0565 BLE 2 23.7 0.1103 BLE
2 20.4 0.0670 BLE 2 25.0 0.1308 BLE
3 22.5 0.0727 BLE 3 27.7 0.1419 BLE
3 23.5 0.0832 BLE 3 28.9 0.1624 BLE
3 25.5 0.1042 BLE 3 31.4 0.2034 BLE
4 28.7 0.1203 BLE 4 38.0 0.2349 BE
4 30.7 0.1413 BLE 4 40.5 0.2759 BE
5 36.5 0.1575 BE 5 44.5 0.3075 BE
5 38.5 0.1785 BE 5 47.0 0.3485 BE
6 41.6 0.1947 BE 6 50.9 0.3801 BE
6 43.6 0.2157 BE 6 53.4 0.4211 BE
1 15.9 0.0369 BLE 1 19.2 0.0653 BLE
2 18.3 0.0439 BLE 2 22.2 0.0777 BLE
2 19.4 0.0569 BLE 2 23.5 0.1007 BLE
2 20.5 0.0699 BLE 2 24.8 0.1237 BLE
2 21.5 0.0829 BLE 2 26.1 0.1467 BLE
3 23.8 0.0900 BLE 3 29.0 0.1592 BLE
3 24.9 0.1030 BLE 3 30.3 0.1822 BLE
3 27.0 0.1290 BLE 3 32.9 0.2282 BLE
4 30.3 0.1490 BLE 4 39.7 0.2636 BE
4 32.5 0.1750 BLE 4 42.3 0.3096 BE
5 38.5 0.1950 BE 5 46.5 0.3450 BE
5 40.6 0.2210 BE 5 49.1 0.3910 BE
6 43.9 0.2410 BE 6 53.2 0.4264 BE
6 46.1 0.2670 BE 6 55.8 0.4724 BE
1 16.8 0.0440 BLE 1 20.9 0.0795 BLE
2 19.3 0.0524 BLE 2 24.2 0.0946 BLE
2 20.4 0.0679 BLE 2 25.6 0.1226 BLE
2 21.6 0.0834 BLE 2 27.0 0.1506 BLE
2 22.7 0.0989 BLE 2 28.4 0.1786 BLE
3 25.1 0.1073 BLE 3 31.6 0.1938 BLE
3 26.2 0.1228 BLE 3 33.0 0.2218 BLE
3 28.5 0.1538 BLE 3 35.8 0.2778 BLE
4 32.0 0.1776 BLE 4 43.1 0.3209 BE
4 34.3 0.2086 BLE 4 45.9 0.3769 BE
5 40.5 0.2325 BE 5 50.5 0.4200 BE
5 42.7 0.2635 BE 5 53.3 0.4760 BE
6 46.3 0.2874 BE 6 57.9 0.5191 BE
6 48.5 0.3184 BE 6 60.7 0.5751 BE

10
1 22.5 0.0937 BLE 1 27.5 0.1363 BLE
2 26.1 0.1115 BLE 2 32.0 0.1622 BLE
2 27.7 0.1445 BLE 2 33.9 0.2102 BLE
2 29.2 0.1775 BLE 2 35.7 0.2582 BLE
2 30.7 0.2105 BLE 2 37.6 0.3062 BLE
3 34.2 0.2284 BLE 3 42.0 0.3322 BLE
3 35.7 0.2614 BLE 3 43.9 0.3802 BLE
3 38.8 0.3274 BLE 3 50.3 0.4762 BE
4 46.4 0.3782 BE 4 56.5 0.5501 BE
4 49.5 0.4442 BE 4 60.3 0.6461 BE
5 54.5 0.4950 BE 5 66.5 0.7200 BE
5 57.5 0.5610 BE 5 70.2 0.8160 BE
6 62.5 0.6118 BE 6 76.5 0.8899 BE
6 65.6 0.6778 BE 6 80.2 0.9859 BE
1 24.2 0.1079 BLE 1 29.1 0.1505 BLE
2 28.1 0.1284 BLE 2 34.0 0.1791 BLE
2 29.7 0.1664 BLE 2 35.9 0.2321 BLE
2 31.4 0.2044 BLE 2 37.9 0.2851 BLE
2 33.0 0.2424 BLE 2 39.9 0.3381 BLE
3 36.8 0.2630 BLE 3 47.2 0.3668 BE
3 38.4 0.3010 BLE 3 49.2 0.4198 BE
3 41.7 0.3770 BLE 3 53.2 0.5258 BE
4 49.8 0.4355 BE 4 59.9 0.6074 BE
4 53.1 0.5115 BE 4 63.8 0.7134 BE
5 58.5 0.5700 BE 5 70.5 0.7950 BE
5 61.8 0.6460 BE 5 74.5 0.9010 BE
6 67.2 0.7045 BE 6 81.1 0.9826 BE
6 70.5 0.7805 BE 6 85.1 1.0886 BE
1 25.8 0.1221 BLE 1 30.8 0.1647 BLE
2 30.0 0.1453 BLE 2 35.9 0.1960 BLE
2 31.8 0.1883 BLE 2 38.0 0.2540 BLE
2 33.5 0.2313 BLE 2 40.1 0.3120 BLE
2 35.3 0.2743 BLE 2 42.2 0.3700 BLE
3 39.4 0.2976 BLE 3 49.8 0.4014 BE
3 41.1 0.3406 BLE 3 51.9 0.4594 BE
3 47.3 0.4266 BE 3 56.1 0.5754 BE
4 53.1 0.4928 BE 4 63.2 0.6647 BE
4 56.7 0.5788 BE 4 67.4 0.7807 BE
5 62.5 0.6450 BE 5 74.5 0.8700 BE
5 66.0 0.7310 BE 5 78.7 0.9860 BE
6 71.8 0.7972 BE 6 85.8 1.0753 BE
6 75.4 0.8832 BE 6 90.0 1.1913 BE
Smoke extraction dampers single are designed to remove heat and combustion products (e.g.
smoke) from single fire compartment according EN1366-9.
Smoke extraction dampers single are designed for installation with horizontal or vertical axis of the blades.
Backtoback smoke exhaust duct has to be hung or supported so as all load transfer from the backtoback
smoke exhaust duct to the damper is absolutely excluded. To provide needed
access space to the control device, all other objects must be situated at least 350 mm from the
control parts of the damper.
During installation the damper blade must be in position CLOSED. The damper body should
not be deformed in the course of installation. Once the damper built in, its blade should not grind
on the damper body during opening or closing.
Example, how to calculate effective area and size of SEDS-L damper [AxB], when knowing air volume in [m³/s] or [m³/h] on damper.
Maximum allowed air velocity on SEDS-L is 12 [m/s].
Formula:
Q … air volume [m³/s]
Sef … effective free area of damper [m²]
v … air velocity on damper [m/s]
Example:
Air volume needed is 26000 m³/h
26000 / 3600 = 7,222 m³/s
7,222 / 12 = 0,602 m² is min. effective free area [Sef]
Find the value Sef in the table 3.2.1. The effective are has to be the same or bigger. There will be more options of damper, sizes AxB.

11
Installation examples
Pozice:
1
Damper hinge
2
Nut
3
Washer
4
Profile C
5Washer C
6
Wall construction without fire resistance

12
16 24 29 29 28 26 23 9
25 33 38 38 37 35 32 18
32 40 45 45 44 42 39 25
38 46 51 51 50 48 45 31
42 50 55 55 54 52 49 35
46 54 59 59 58 56 53 39
49 57 62 62 61 59 56 42
50 58 63 63 62 60 57 43
53 61 66 66 65 63 60 46
55 63 68 68 67 65 62 48
57 65 70 70 69 67 64 50
w - air velocity in the free cross section (AxB) - i.e. before blades
f - frequency of octave band
Sound power level corrected with filter A
Δps - static pressure drop
w - air velocity in the free cross section (AxB)
B - height of the damper
0
10
20
30
40
50
60
70
80
90
100
110
120
2 3 4 5 6 7 8 9 10 11 12
B=200/400/600/800/1000/1200mm B=250mm B=300/450mm B=350/500/700/900/1100mm
w (m/s)
Δps(Pa)

13
15 23 28 28 27 25 22 8
24 32 37 37 36 34 31 17
31 39 44 44 43 41 38 24
36 44 49 49 48 46 43 29
41 49 54 54 53 51 48 34
45 53 58 58 57 55 52 38
48 56 61 61 60 58 55 41
49 57 62 62 61 59 56 42
51 59 64 64 63 61 58 44
53 61 66 66 65 63 60 46
55 63 68 68 67 65 62 48
w - air velocity in the free cross section (AxB) - i.e. before blades
f - frequency of octave band
13 21 26 26 25 23 20 6
21 29 34 34 33 31 28 14
28 36 41 41 40 38 35 21
34 42 47 47 46 44 41 27
38 46 51 51 50 48 45 31
42 50 55 55 54 52 49 35
45 53 58 58 57 55 52 38
47 55 60 60 59 57 54 40
48 56 61 61 60 58 55 41
50 58 63 63 62 60 57 43
52 60 65 65 64 62 59 45
w - air velocity in the free cross section (AxB) - i.e. before blades
f - frequency of octave band

14
Damper casing and damper blade are made of galvanized plate without any other surface finish.
Fasteners are galvanized.
The appliance is constructed and preset by the manufacturer, its operation is dependent on
proper installation and adjustment.
Dampers are transported by box freight vehicles without direct weather impact, there must not
occur any shocks and ambient temperature must not exceed + 40 °C. Dampers must be protected
against mechanic damages when transported and manipulated. During transportation, the
damper blade must be in the "CLOSED" position.
Dampers are stored indoor in environment without any aggressive vapours, gases or dust. Indoor
temperature must be in the range from -5 °C to +40 °C and maximum relative humidity 80 %.
Dampers must be protected against mechanic damages when transported and manipulated.
All effective safety standards and directives must be observed during damper assembly.
To ensure reliable smoke exhaust damper function it is necessary to avoid blocking the closing
mechanism and contact surfaces with collected dust, fibre and sticky materials and solvents.
Without power supply, the damper can be operated manually and fixed in any required position.
The actuator cover is made of fire-resistant material (fire protection board)
Assembly, maintenance and damper function check can be done only by qualified and trained
person, i.e. “AUTHORIZED PERSON” according to the manufacturer documentation. All works
done on the fire dampers must be done according international and local norms and laws.

15
Check of damper blade displacement can be realize after actuating mechanism supply connec-
tion or signal connection from higher level control systems. Blade displacement from position
“OPEN” to position “CLOSED” and return displacement is checked.
Before entering the dampers into operation after assembly and after sequential revisions, checks
and functionality tests of all designs including operation of the electrical components must be
successfully provided and finished. After entering into operation, these revisions must be done
according to requirement set by national regulations.
In case that dampers are found unable to serve for their function for any cause, it must be clearly
marked. The operator is obliged to ensure that the damper is put into condition in which it is ready
for function and meanwhile he is obliged to provide the fire protection by another appropriate way.
Results of regular checks, imperfections found and all-important facts connected with the damper
function must be recorded in the "FIRE BOOK" and immediately reported to the operator.
Before entering the dampers into operation after their assembly and by sequential checks, the
following checks must be carried out for all designs.
Visual inspection of proper damper integration, inside damper area, damper blade, contact
surfaces and silicon sealing.
Spare parts are supplied only on basis of an order.

16
Product label is placed on the damper casing
technical specifications
special design tab. 14.1.2
design according tab. 14.1.1
size
type
with actuating mechanism BLE230 (BE230-12) .44
with actuating mechanism BLE24 (BE24-12) .54
with the communication and supply device BKNE 230-24 and actuating mechanism BLE24 (BE24-12)-ST .66
insulation inside of the blades I
flanges with height 20 mm F
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
EN 12101-8:2011
TPM 121/16
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2018/0106, DoP: PM/SEDS-L/01/20/1

The producer reserves the right for innovations of the product. For actual product information see
www.mandik.com
MANDÍK, a.s.
Dobříšská 550
26724 Hostomice
Czech Republic
Tel.: +420 311 706 706
E-Mail: [email protected]
www.mandik.com
Other manuals for SEDS-L
2
Table of contents
Other Mandik Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Trox Technik
Trox Technik AKK Assembly and operating instructions

Schako
Schako BSK-RPR-EU Series Technical documentation

Greenheck
Greenheck HBS Series Installation, operation and maintenance instructions

Lindab
Lindab WH45 Series Installation booklet

klimaoprema
klimaoprema FDC25 Series manual

aldes
aldes Isone manual

SOLID AIR
SOLID AIR FDC25 Technical manual

Trox Technik
Trox Technik EK-JZ Installation and operating manual

mercor
mercor mcr WIP Series Operation and maintenance manual

Lindab
Lindab CFDM technical information

KOOLAIR
KOOLAIR SAFEAIR BDK60 Technical documentation

Tecnosystemi
Tecnosystemi GALAXY SIRIO 0.10V user manual