mercor mcr FID WING Guide

Ul. Grzegorza z Sanoka 2
80-408 Gdańsk
tel. (0-58) 341 42 45
tel./fax (0-58) 341 39 85
OPERATION
AND MAINTENANCE MANUAL
Fire protection cut-off damper
mcr FID WING
Version 21.08.02.1
FIRE VENTILATION SYSTEMS DEPARTMENT

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 2/15
CONTENTS:
1. INTRODUCTION ...................................................................................................................................................... 3
2. THE SUBJECT OF THE MANUAL .......................................................................................................................... 3
3. DEVICE INTENDED USE ......................................................................................................................................... 3
4. DEVICE DESIGN AND PRINCIPLE OF OPERATION............................................................................................. 4
5. DEVICE LABELLING ................................................................................................................................................ 5
6. DEVICE INSTALLATION .......................................................................................................................................... 6
6.1. INSPECTION BEFORE THE INSTALLATION ............................................................................................... 6
6.2. FIXING HOLE .................................................................................................................................................. 7
6.3. EMBEDDING ................................................................................................................................................... 7
6.4. ELECTRICAL CONNECTIONS .................................................................................................................... 10
7. TRANSPORT AND STORAGE CONDITIONS ....................................................................................................... 11
8. MAINTENANCE AND SERVICE ............................................................................................................................ 11
9. WARRANTY CONDITIONS .................................................................................................................................... 11
Labelling used in the operation and maintenance manual
Option available
Option unavailable
NOTE
With the date of publication of the operation and maintenance manual, the previous versions are
no longer valid.
The operation and maintenance manual does not concern the dampers manufactured before the
date of its publication.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 3/15
CAUTION
The product should be stored and used in rooms where:
• there is no access to dust, gases, caustic vapors and other aggressive chemical
vapors that can destroy the insulating elements and structural elements;
• the dampers are not affected by direct sunlight and UV radiation;
• the maximum relative humidity does not exceed 80% at the temperature of +20 ºC;
• the ambient temperature is between - 20 ºC and + 40 ºC;
• there are no vibrations.
The device is equipped with a thermal release containing one-time temperature fuses. During normal
operation, the above mentioned element should be protected against the impact of the permissible
temperature Tmax (see the table below). When it is exceeded, the temperature fuses may operate, which
is a normal operation and is not covered by the guarantee or warranty.
A thermal release for a damper equipped with RST mechanism:
Thermal fuse for temperature 72 ºC 95 ºC
Temperature fuse inside the duct Tmax 40 ºC Tmax 60 ºC

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 4/15
1. INTRODUCTION
The purpose of this operation and maintenance manual is to get the user acquainted with the intended use, design,
the principle of operation, correct installation and operation of the product.
The manual also includes additional information about the operating conditions, maintenance and warranty conditions
of the product.
2. THE SUBJECT OF THE MANUAL
This operation and maintenance manual concerns the entire group of fire protection cut-off dampers of type
mcr FID WING. Observing recommendations included in the manual ensures correct function of the device in terms
of fire protection of rooms as well as safety of the system users.
3. DEVICE INTENDED USE
Application
A mcr FID WING type damper may be used as a fire protection cut-off damper with a duct connection as well as a
transfer damper (installation without ventilation ducts).
The damper may not work in systems exposed to dust, except for when they are included in a special, individually
developed programme of service and technical inspections.
Fire resistance
The mcr FID WING type fire protection cut-off damper has the following fire resistance:
EI60S /S /V /V-M /T /G EI120S /S /V /V-M /T /G
EI60 /S /V /V-M /T /G EI120 /S /V /V-M /T /G
E60S /S /V /V-M /T /G E120S /S /V /V-M /T /G
E60 /S /V /V-M /T /G E120 /S /V /V-M /T /G
Performance versions
The mcr FIND WING type fire dampers may be manufactured as:
rectangular fire dampers
round fire dampers
Dimension range
The mcr FID WING type dampers are manufactured in the following dimensions - diameters:
Ø100
Ø125
Ø160
Ø200
4. DEVICE DESIGN AND PRINCIPLE OF OPERATION
Design
The mcr FID WING fire damper consists of a casing with a round cross-section, a movable cut-off partition and a
release and control mechanism that is automatically activated after the thermal fuse is actuated. The damper housing
is made of steel sheet. In the housing of the device, on its perimeter, there is a ventilation and intumescent gasket.
The cut-off partition of the damper is made of a non-flammable plate. Additionally, the damper can be equipped with
microswitches indicating the position of the device partition. The damper can also be equipped with an air valve (air
diffuser), enabling the adjustment of the parameters of the ventilation system. The device is delivered complete with
two insulating bands. The manufacturer requires the installation of the bands according to the drawings included in
the Operation and Maintenance Manual in order to obtain the declared fire resistance.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 5/15
Diameter ØD [mm] Diameter ØD2 [mm] Length A [mm] Mass [kg]
100 149 21 0,2
125 169 34 0,3
160 195 51 0,4
200 240 72 0,6
Operation
The operating principle and behaviour of the mcr FID PRO single-plane fire dampers depends on the version and
use:
automatically – by actuation of the thermoelectric release
manually – by pressing the control button on the thermoelectric release
remotely – by actuation of the axial electric actuator with a return spring as the supply voltage
disappears
automatically – by actuation of the thermal release and the power spring
The structure of the system equipped with an air diffuser enables the regulation of efficiency during normal operation
of the device (setting the gap between the body of the mechanism and the valve plug). The adjustment is made by
rotating the plug around the damper axis.
Release and control mechanisms
A release and control mechanism for the mcr FIND WING damper can be:
An RST type mechanism composed of a drive spring and a fuse release
Optionally, there is a possibility to equip the damper with WK1 limit switches that signal the damper operation status
(open/closed).

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 6/15
5. DEVICE LABELLING
mcr FID WING
/
DIA 200
/
WK1
/
EIS 120
Parametry dodatkowe:
WK1 – limit switch - signaling that the partition is closed
AN – air diffuser
PM – mounting plate
NOTE
As a default, the damper release temperature equals 72°C. In case of another temperature value, it has to be
specified in the order after prior confirmation of the temperature value with the Sales Department.
6. DEVICE INSTALLATION
NOTE
During the installation of damper and the finishing works, take into account the possibility of
access to the device later and the disassembly of release and control mechanism in order to carry
out the possible service works and technical inspections.
The mcr FID WING fire dampers may be installed in the following space dividing elements (walls or structural floors):
masonry/concrete walls with the minimum thickness of 100 mm
brickwork walls or blockwork walls with the minimum thickness of 100 mm
walls made of boards with the minimum thickness of 100 mm
structural floors with the minimum thickness of 150 mm for EIS120 and 100mm for EIS60
Additionally, fire dampers may be installed:
outside walls
in dampers sets (multiple damper sets)
The mcr FID WING cut-off damper may also be installed in partitions with lower fire resistance class In case of such
an installation, damper have fire protection equal to the fire protection of the partition, maintaining the smoke tightness
criteria.
INSPECTION BEFORE THE INSTALLATION
Each damper is inspected before packaging and transporting by the manufacturer. After unpacking at the recipient,
inspect visually in terms of possible deformation of the casing or damper damage during transportation.
The damper is delivered in the closed position. Before installation, it should be armed.
Fire resistance
Additional equipment
Diameter
Damper type

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 7/15
6.2. FIXING HOLE
Minimum diameter of the hole that allows correct installation of the mcr FID WING damper equals:
- min. D + 50, max. D + 70 – in the case of a wall made of plasterboards and wet installation
- min. D + 50, max. D + 70 – in the case of concrete and masonry partitions and in the ceiling and wet installation
- min. D + 100, max. D + 600 – in the case of a wall made of plasterboards and dry installation
- min. D + 100, max. D + 600 – in the case of concrete and masonry partitions and in the ceiling and dry installation
Wall Ceiling
Wet
installation
Dry installation
6.3. EMBEDDING / SETTING THE DAMPER
INSTALLATION IN A PLASTERBOARD, CONCRETE OR MASONRY WALL
Insert the connection duct in the assembly opening so that the axis of the channel coincides with the axis of the
opening. The gap between the duct and the edge of the opening should be tightly filled with mortar or other material
ensuring the required fire resistance. Place an armed damper in the duct.
CAUTION
Pay special attention to the roundness of the connection duct when filling the opening hole with mortar. Any
irregularities will make it impossible to install the damper.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 8/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar*
5. Drywall
6. The 12,5mm drywall board
band
7. Mortar or mineral wool *
X Wall thickness
installation of the mcr FID WING damper in plasterboard walls for EIS60
* Recommended installation of the damper in a dry system is based on wool of min. 40 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar or mineral wool *
5. Drywall
6. The 12,5mm drywall board
band
X Wall thickness
installation of the mcr FID WING damper in plasterboard walls for EIS120
* Recommended installation of the damper in a dry system is based on wool of min. 100 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 9/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar*
5. Rigid walls
6. The 12,5mm drywall board
band
7. Mortar or mineral wool *
X Wall thickness
installation of the mcr FID WING damper in rigid walls for EIS60
* Recommended installation of the damper in a dry system is based on wool of min. 100 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar*
5. Rigid walls
6. The 12,5mm drywall board
band
7. Mortar or mineral wool *
X Wall thickness
installation of the mcr FID WING damper in rigid walls for EIS120
* Recommended installation of the damper in a dry system is based on wool of min. 100 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 10/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar *
5. Ceiling
6. Mortar / fire-resistant
paint *
7. Mineral wool *
X Thickness of the ceiling
Y 75mm for EIS120
45mm for EIS60
installation of the mcr FID WING damper in ceilings
* Recommended installation of the damper in a dry system is based on wool of min. 140 kg / m3 with non-flammability
class A1, thickness min. 50mm and securing the joint between the wool and the wall with PROMASTOP E PASTE
or HILTI CFS-CT paint and wool with the fire-retardant PROMASTOP E PASTE or HILTI CFS-S ACR paint, as shown
in the above drawing. The recommended installation of the damper in a wet system is based on plaster or cement
mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mineral wool *
5. Mortar / fire-resistant paint *
6. Drywall
7. Rigid wall
X Thickness of the wall
installation of the mcr FID WING damper in dry systems
* Recommended installation of the damper in a dry system is based on wool of min. 140 kg / m3 with non-flammability
class A1, thickness min. 50mm and securing the joint between the wool and the wall with PROMASTOP E PASTE
or HILTI CFS-CT paint and wool with the fire-retardant PROMASTOP E PASTE or HILTI CFS-S ACR paint, as shown
in the above drawing. The recommended installation of the damper in a wet system is based on plaster or cement
mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 11/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar or mineral wool *
5. Drywall
6. The 12.5mm GK board band
7. Mortar *
8. Air diffuser
X Wall thickness
installation of the mcr FID WING damper in plasterboard walls for EIS60
* Recommended installation of the damper in a dry system is based on wool of min. 40 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar or mineral wool *
5. Drywall
6. The 12.5mm GK board band
7. Mortar *
8. Air diffuser
X Wall thickness
installation of the mcr FID WING damper in plasterboard walls for EIS120
* Recommended installation of the damper in a dry system is based on wool of min. 40 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 12/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar or mineral wool *
5. Drywall
6. The 12.5mm GK board band
7. Mortar *
8. Air diffuser
X Wall thickness
installation of the mcr FID WING damper in rigid walls for EIS60 and EIS120
* Recommended installation of the damper in a dry system is based on wool of min. 40 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mineral wool *
5. Mortar / fire-resistant paint *
6. Drywall
7. Rigid wall
8. Air diffuser
X Thickness of the wall
installation of the mcr FID WING damper in dry systems
* Recommended installation of the damper in a dry system is based on wool of min. 140 kg / m3 with non-flammability
class A1, thickness min. 50mm and securing the joint between the wool and the wall with PROMASTOP E PASTE
or HILTI CFS-CT paint and wool with the fire-retardant PROMASTOP E PASTE or HILTI CFS-S ACR paint, as shown
in the above drawing. The recommended installation of the damper in a wet system is based on plaster or cement
mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class
of fire resistance for the applied method of assembly.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 13/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar *
5. Ceiling
6. Mortar / fire-resistant
paint *
7. Mineral wool *
8. Air diffuser
X Thickness of the ceiling
Y 75mm for EIS120
45mm for EIS60
installation of the mcr FID WING damper in ceilings
* Recommended installation of the damper in a dry system is based on wool of min. 140 kg / m3 with non-flammability
class A1, thickness min. 50mm and securing the joint between the wool and the wall with PROMASTOP E PASTE
or HILTI CFS-CT paint and wool with the fire-retardant PROMASTOP E PASTE or HILTI CFS-S ACR paint, as shown
in the above drawing. The recommended installation of the damper in a wet system is based on plaster or cement
mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class
of fire resistance for the applied method of assembly.
6.4. ELECTRICAL CONNECTIONS
Before the damper is finally mounted in the connection duct, if it has elements that require connection to the electrical
installation, connect the wires of this installation properly. The connection method and basic data of electrical
components are presented below.
Electrical connection diagram of the mcr FID WING + WK1 fire
damper
1 - black
2 - gray
4 - blue
1mA 4V AC min
6A 250V AC max
7. TRANSPORT AND STORAGE CONDITIONS
Fire dampers are packaged in cardboard boxes or placed on pallets. Dampers are protected against damage by film
or another covering material. Damper shipping may take place using any means of transport, under the condition
they are protected against weather factors. Dampers placed on means of transport should be secured against shifting
of position during transport. Before installing dampers, control each of them visually. Do not move the damper by
holding by the connection cable or put a device on a release and control mechanism. Do not hit or drop the damper.
When moving and installing, support the damper on the sides or edges of the body.
Dampers should be stored in closed rooms that provide protection against external weather conditions. In the case
dampers are stored on the ground, place them on protection pads in order to protect them against damage. Storage
should take place in rooms where:
• there is no access to dust, gases, caustic vapors and other aggressive chemical vapors that can destroy
insulating elements and structural elements;

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 14/15
• the dampers are not affected by direct sunlight and UV radiation;
• maximum relative humidity does not exceed 80% at the temperature of + 20 ºC;
• the ambient temperature is between - 20 ºC and + 40 ºC;
• there are no vibrations.
8. MAINTENANCE AND SERVICE (REPAIRS)
Products manufactured by „MERCOR” SA should undergo periodic technical inspections and maintenance at least
every 12 months throughout their service life, i.e. in the warranty period and later. Inspections and maintenance
should be carried out by the manufacturer or by companies authorised to service „MERCOR” SA’s products.
The obligation to conduct regular inspections of fire equipment is stipulated in § 3 section 3 of the Regulation of
Minister of Internal Affairs and Administration dated 7 June 2010 on the fire protection of buildings, other structures
and areas (Dz. U. [Journal of Laws] 2010 No. 109, item 719).
The recommended operations to be carried out between the inspections are as follows:
check the condition of electrical connections, paying particular attention to mechanical damage;
Inspections of the condition of the supply voltage for the devices, which allowed the following tolerances:
24V±10% for electric actuators
24V±2% for electromagnetic release mechanism
230V ±10% for electric actuators
230V±2% for electromagnetic release mechanism
check the condition of the fire damper’s body, paying particular attention to mechanical damage;
check for causes that could possibly affect the correct operation of the fire damper.
To enable full service inspections as well as servicing, including servicing under the warranty, such as visual
inspections and repairs, the user has to ensure physical access to the product, e.g. by removing thermal
insulation/suspended ceilings and disassembling other systems if they prevent free access to the product, etc.
In the case of fire dampers installed in ducts, it is recommended to make a service duct such as the mcr KRW type,
for instance.
If devices are installed on the roof, ensure the possibility to enter the roof (ladder or lift).
For matters relating to technical inspections, maintenance and service of our products, please contact the Service
Department of „Mercor” SA at serwis@mercor.com.pl, phone 058/ 341 42 45 (extension number 170), fax 058/341
39 85, 8 am–4 pm (Mon–Fri).
9. WARRANTY TERMS AND CONDITIONS
1. “MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase,
unless the sales contract states otherwise.
2. Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty
eligible defect
3. Submit warranty claims by calling at: tel. +48 58 341 42 45, by fax: +48 58 341 39 85, by e-mail:
[email protected]m.pl or by traditional mail: “MERCOR” SA, ul. Grzegorza z Sanoka 2, 80-408
Gdańsk, Poland.
4. If physical defects of equipment are found during the warranty period, “MERCOR” SA warrants and
represents to remove them in shortest possible time from serving the written warranty claim with the
proof of purchase or sales contract, subject to Item 10.
5. “MERCOR” SA has the right to extend the time of repair if the defect removal is complicated or
requires purchase of custom components or spare parts.
6. The warranty liability only covers all defects arising from causes present in the equipment at the date
of sale.
7. Defects caused by improper operation or otherwise as listed in Item 10 herein, the buyer / warranty
beneficiary will be charged with the costs of their removal.
8. Condition for rectifying defects is that the applicant makes the site/localisation where devices are
installed available, in particular, ensuring: the lift in the case of devices mounted at a height above
3m, free access to the rooms where the devices were installed and necessary revisions, dismantling
thermal insulation, disassembling suspended ceilings, disassembling other installations, if they
prevent free access to the device.

mcr FIND WING fire protection cut-off damper
MERCOR SA – The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1 15/15
9. If the device can not be repaired at the place of its installation, "MERCOR" SA reserves the necessity
of its disassembly, possible delivery to the address indicated by "MERCOR" SA and re-assembly.
The cost of this operation lies with the buyer / holder of the guarantee.
10. The warranty does not cover:
Any damage or failure of the equipment caused by improper operation, tampering, failure to
conduct periodic technical inspection and/or maintenance established in the Operating and
Maintenance Manual, section “SERVICING AND MAINTENANCE”.
Any damage beyond reasonable control of “MERCOR” SA, and specifically: caused
by force majeure, such as torrential rainfall, flooding, hurricanes, inundation, lightning
strike, power grid overvoltage, explosion, hail, collision with aircraft, fire, avalanche,
landslide and indirect damage due to those causes. Torrential rainfall is understood as
any rainfall with the effectiveness factor of 4 or higher in accordance with the definition
of the Polish Institute of Meteorology and Water Management - National Research
Institute (IMGW-PIB). If the effectiveness factor value specified in the preceding
sentence cannot be reasonably established, the actual condition and extent of damage
shall be considered at the site of their origin as the action of torrential rain. Hurricane
is understood as any wind with a minimum speed of 17.5 m/s (and damage shall be
recognised as caused by hurricanes if the effects of such weather phenomenon has
been found in the direct vicinity of the damaged property).
Damage due to failure to immediately report any defect found.
Deterioration in the quality of coatings due to natural weathering/ageing.
Defects caused by abrasive or aggressive cleaning agents.
Damage caused by aggressive external influence, specifically chemical or biological
in nature, or when the origin of which is related to the production processing or activity
carried out within the facility protected by the equipment or in its direct vicinity.
Wearing parts and consumables (e.g. gaskets/seals), unless they have defects of
workmanship and/or material.
Damage caused by improper transport, handling, unloading and/or storage of the
equipment.
Damage caused by installation of the equipment in violation of this Operating and
Maintenance Manual and/or good construction practice.
The equipment and/or parts thereof with removed or damaged nameplate (rating plate)
and/or warranty seals.
11. The buyer/warranty rights holder is required to operate the equipment properly and carry out
technical inspection and maintenance in accordance with the section “MAINTENANCE AND
SERVICING” in the following Operating and Maintenance Manual.
12. This warranty shall be made immediately void and null if:
The buyer/warranty rights holder modifies the product design without prior authorisation from
“MERCOR” SA.
Periodic technical inspection and/or maintenance is not carried out per schedule and/or is
carried out by unauthorised personnel or service providers not authorised to do so by
“MERCOR” SA and/or the equipment has not been properly operated.
Unauthorised personnel attempts any intervention in the product outside of the normal
operation and maintenance of this equipment.
The device's thermal trigger was affected by a temperature greater than Tmax (page 3 of the
Operation Manual).
13. Any circumstances listed in Item 10 will relieve “MERCOR” SA from the obligation of surety.
The relevant provisions of the Polish Civil Code shall apply to all matters not regulated in these Warranty Terms & Conditions.
Table of contents
Other mercor Fire And Smoke Damper manuals

mercor
mercor mcr FID 240 User manual

mercor
mercor mcr FID PRO Series User manual

mercor
mercor mcr WIP LD User manual

mercor
mercor mcr LAM User manual

mercor
mercor mcr FID S c/P Series User manual

mercor
mercor mcr FID S User manual

mercor
mercor mcr Prosmoke FS User manual

mercor
mercor mcr FID B User manual

mercor
mercor mcr DOR User manual

mercor
mercor mcr WIP PRO User manual
Popular Fire And Smoke Damper manuals by other brands

actionair
actionair Smoke/Shield PTC Installation and operating instructions

klimaoprema
klimaoprema FD25 product manual

GILBERTS
GILBERTS DUCTGARD manual

New York Blower
New York Blower IM-220 Installation maintenance and operating instructions

Mandik
Mandik FDMR installation instructions

System air
System air S-SA1 Handbook