UNIGUARD UG-2-A2 STAND-ALONE-UNIT
Smoke detector for duct installation.
- One-tube air sampling system
- Service alarm
- Test hole on cover
- Simple installation
- Sensitive flow indication
- Filter for dusty environments
- Simple service and maintainance
- Installer-friendly connection of cables
- Foolproof mountage of sampling tube
- Reset button on front cover
- Built-in alarm relay
FUNCTION
Uniguard has been developed to detect smoke in ventilation
ducts and combines a smoke detector and an adaptor system
where both tube and housing are specially designed for
optimum airflow through the smoke detector.
The system fulfils all the requirements for safe fire detection
with airflow speeds from 0,2 m/s to 20 m/s.
Uniguard has a built-in alarm relay to control fire-safety
dampers, to stop ventilation fans, or to activate accoustic and
optical alarms etc.
The service alarm let you know when maintenance is needed,
before a false alarm occur.
The detector has a bayonet fitting to simplify mounting and
removal.
A contaminated detector will result in increased sensitivity
and false alarms. To avoid nuisance alarms the detector has
a service alarm (green LED). This indicates that the detector
should be cleaned.
BASIC PRINCIPLES FOR POSITIONING
For the airflow through the adaptor to be representative of the
airflow in the ventilation duct, install the detector at a place
where normally flow meters etc. should be mounted, please
see our installation instructions.
You can also use your national or local rules for mountage
according to "Methods for measuring airflow in ventilation
systems".
ACCESSORIES
Filter: F1-UG/10 pack
Mounting bracket: UG-Beslag
(Forinsulated/circularducts)
Waterproof housing: UG-SH for outdoors, in
coldatticsetc.
TECHNICAL DATA
Detector type: Ionisation - UG-2-A2I
Optical - UG-2-A2O
Voltage Supply: 24VAC 100 mA ±20%
Operating temperature: -10°C to +50°C
Maximum humidity: 99% rH
Tested and approved
according to EN-54: by LPC (England), VdS (Germany)
Service alarm: Indicated with green LED
Fire alarm: Indicated with red LED
Adaptor housing: ABS
Air sampling tube: Aluminium. Standard length
0,6 m. Hole diameter 35mm.
The length of the venturi pipe shall
be choosen based upon how wide
the ventilation duct is. The venturi
pipes are available in 3 lengths;
0,6, 1,5 and 2,8 m. When the ven-
tilation duct is wider than 0,6 m
(dia), the venturi pipe should pen-
etrate the whole duct.
Please see enclosed sketch.
Shorten the pipe to correct length.
Insert the end plug.
Put on the end plastic
gasket.
Put on the rubber
gasket, TET 26-35.
Drill a hole
Ø 50 mm.
NOTE!
Drill a hole
Ø 35 mm.
Diameter of the duct bigger
than 0,6 m.
The venturi pipe should
penetrate the whole duct.
Drill a hole
Ø 35 mm.
Max diameter of the duct 0,6 m.
Use the venturi pipe 0,6 m.
Shorten the pipe, if necessary.
For ducts with a ø of less than 0,6 m use the 0,6 m tube.
For ducts with a ø of between 0,6 m and 1,3 m use the 1,5 m tube.
For ducts which are larger than 1,4 m use the 2,8 m tube.
The venturi pipe shall not
protrude more than 30 mm
through the duct wall.
Phone: +46 31-69 53 00 Fax: +46 31-29 32 91 info@calectro.com www.calectro.com
UNIGUARD UG-2-A2 STAND-ALONE-UNIT
Smoke detector for duct installation.
DIMENSIONS
(mm)
INSTALLATION
The venturi tube is made of aluminium and can easily be
shortened to suit the diameter of the duct. Hole diameter is 35
mm. With insulated or circular ducts - use the mounting bracket,
hole diameter is then 50 mm.
MAINTAINANCE
When the detector becomes contaminated, sensitivity is
increased, triggering the service alarm. This can be avoided
for a considerable time by cleaning the detector once a year
with a vacúum cleaner.
CHECKING AIR FLOW
The detector is equipped with a flow indicator which oscillates
in the air stream when the detector is correctly installed. This
gives simple confirmation that there is no leakage, and that air
from the ventilation duct is flowing through the detector.
FUNCTION TEST
When installation is complete, the detector should be tested.
This can be carried out with smoke or suitable testspray for
example RDP-300 (from Calectro), use the test hole on cover.
D o not forget to refit the plastic plug after test.
NB: When installing outdoors or in cold attics etc., where
there is a risk for condensation, this requires that the detector
is insulated from the surrounding air by means of for example
our waterproof housing UG-SH, and marked with an extra
indicator lamp, LED-01 and a sign marked "Hidden Detector".
FUNCTION
Normal operation: In normal operation the alarm relay
is energized, and the relay contacts
are closed between C and NC.
Smoke alarm: The LED of the detector is showing
red light and the relay contacts are
changing to C and NO.
Reset: After alarm the reset push-button has
to be pressed in order to have the
detector back into normal operation.
Pre-alarm: When the detector is sensing smoke or
is dirty the LED of the detector will first
show green colour before going into
alarm with red light. If the detector is
dirty, it will show green light. This is
an optical indication (a pre-alarm or
service-alarm) which means that the
detector is contamined and if it is not
cleaned, it will later on give a false
alarm.
Failure: If there is something wrong with the
detector, the alarm relay will change
contacts:
a) If the detector module is taken away
b) If the supply voltage is interrupted
WIRING DIAGRAM
Alarm relay: ONE changing contact,
max 250V, 2Amp
Note!
Changing between AC and DC is made by a jumper.
The jumper is factory set to AC.
External
reset button
Supply 24 VADC 100mA (±20%)
Alarm
output
NC
NO
C
= 24 VDC
= 24 VAC

Other CALECTRO Smoke Alarm manuals

CALECTRO Uniguard Superflow UG-3-J User manual

CALECTRO

CALECTRO Uniguard Superflow UG-3-J User manual

CALECTRO UG-5-AFR-230V User manual

CALECTRO

CALECTRO UG-5-AFR-230V User manual

CALECTRO UG-3-A4O UNIGUARD SUPERFLOW User manual

CALECTRO

CALECTRO UG-3-A4O UNIGUARD SUPERFLOW User manual

CALECTRO UNIGUARD SUPERFLOW UG-3-NS-AOS User manual

CALECTRO

CALECTRO UNIGUARD SUPERFLOW UG-3-NS-AOS User manual

CALECTRO UG-7 Series User manual

CALECTRO

CALECTRO UG-7 Series User manual

CALECTRO Uniguard 8 User manual

CALECTRO

CALECTRO Uniguard 8 User manual

CALECTRO UG-5-AFR-24V UNIGUARD SUPERFLOW User manual

CALECTRO

CALECTRO UG-5-AFR-24V UNIGUARD SUPERFLOW User manual

CALECTRO UG-3-A4O User manual

CALECTRO

CALECTRO UG-3-A4O User manual

CALECTRO Superflow UG-5-AFR-230V-MB User manual

CALECTRO

CALECTRO Superflow UG-5-AFR-230V-MB User manual

CALECTRO Uniguard Superflow UG-5-AFR Series User manual

CALECTRO

CALECTRO Uniguard Superflow UG-5-AFR Series User manual

CALECTRO Uniguard Superflow UG-3-J User manual

CALECTRO

CALECTRO Uniguard Superflow UG-3-J User manual

CALECTRO Uniguard Superflow UG-3-O User manual

CALECTRO

CALECTRO Uniguard Superflow UG-3-O User manual

CALECTRO UG-7-A6O-120V Manual

CALECTRO

CALECTRO UG-7-A6O-120V Manual

Popular Smoke Alarm manuals by other brands

Nexelec INSAFE+Origin D731D Technical guide

Nexelec

Nexelec INSAFE+Origin D731D Technical guide

Siterwell GS508C user manual

Siterwell

Siterwell GS508C user manual

Honeywell X Series manual

Honeywell

Honeywell X Series manual

Kidde KN-COB-DP2 user manual

Kidde

Kidde KN-COB-DP2 user manual

Tynetec ZXT484 Quick user guide

Tynetec

Tynetec ZXT484 Quick user guide

Edwards LaserSense HSSD-2 Installer's handbook

Edwards

Edwards LaserSense HSSD-2 Installer's handbook

RayTalk RA-635S user manual

RayTalk

RayTalk RA-635S user manual

System Sensor Innovair Flex DNRE Installation and maintenance instructions

System Sensor

System Sensor Innovair Flex DNRE Installation and maintenance instructions

AJAX FireProtect Plus quick start guide

AJAX

AJAX FireProtect Plus quick start guide

WAGNER TITANIUS TOP-SENS Technical manual

WAGNER

WAGNER TITANIUS TOP-SENS Technical manual

Sentek SK40 user manual

Sentek

Sentek SK40 user manual

family first FFP240VHX product manual

family first

family first FFP240VHX product manual

Kidde I4618 user manual

Kidde

Kidde I4618 user manual

Asante 50598 Quick guidebook

Asante

Asante 50598 Quick guidebook

FireAngel SI-601 user manual

FireAngel

FireAngel SI-601 user manual

Popp POP_004308 quick start

Popp

Popp POP_004308 quick start

SAMUEL JACKSON Argus Installation and Resource Guide

SAMUEL JACKSON

SAMUEL JACKSON Argus Installation and Resource Guide

Regin SDD-S65-RACM Instruction

Regin

Regin SDD-S65-RACM Instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.