Page 1 of 9
CX-DE1200
Delayed Egress Electro Magnetic Lock
Special Locking Arrangement
INSTALLATION INSTRUCTIONS
Electrified Locks, Relays and Timers
1- CX-DE1200 Electro Magnetic Lock Housing
assemble with main controller PCB & Magnetic Plate
1- Mounting Template
4- Adhesive door signage
1- Installation Instructions & Wiring Diagrams
1- Armature Plate Assembled Housing
& Proxy Trigger
1- Electro Magnetic Lock Screw Packaging
THIS PACKAGE INCLUDES:
1. DESCRIPTION
Intended for use in an Indoor location - Out Swing.
When an unauthorized exit is trigger, the delays exit through
the door for a period of 15 or 30 seconds. An LED bar segment
display countdown by seconds and voice messages to inform
the person planning to exit with the remaining times to unlock.
In the meantime, the person exiting must wait to allow time for
security personnel or sta to respond. The door will eventually
unlock after the 15 or 30 seconds delay time has passed,
permitting the exit. During an emergency, a signal from the
re/life safety system will release the lock promptly.
2. SPECIFICATIONS
Voltage
12/24V DC +/- 10% (Auto Sensing)
Power Suplly must be UL 294 or
UL 603 Listed with a Class 2, power
limited output
Current Draw 600mA / 350mA
Lock Output 12/24 VDC, 1A
Lock Status Relay
Rating Max. * 30 VDC, 2A, 1 pF
Alarm Output
Rating Max. * 30 VDC, 2A, 1 pF
DPS Rating Max. * 30 VDC, 0.1A, 1 pF
Bond Sensor Rating Max. * 30 VDC, 2A, 1 pF
ATS Rating Max. * 30 VAC / 42.4 VDC, 5A, 1 pF
Operating Temperature 0~55°C (32~131°F)
Operating Humidity 0~95% (non-condensing)
Dimensions
(Lock)
11” H x 3” W x 3” D
(280mm x 76mm x 74.5mm)
Dimensions
(Armature Plate)
11” H x 2-5/8” W x 1” D
(280mm x 68mm x 23.5mm)
3. DIMENSIONS
PUSH UNTIL ALARM SOUNDS.
DOOR CAN BE OPENED
IN 15 SECONDS.
PUSH UNTIL ALARM SOUNDS.
DOOR CAN BE OPENED
IN 30 SECONDS.
KEEP PUSHING.
THIS DOOR WILL OPEN
IN 15 SECONDS.
ALARM WILL SOUND.
KEEP PUSHING.
THIS DOOR WILL OPEN
IN 30 SECONDS.
ALARM WILL SOUND.
Building & Fire Life Safety Code Compliant:
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1, UFC Uniform Fire Code
CBC California Building Code
BOCA National Building Code
Chicago Building Code
THIS PRODUCT MUST BE CONNECTED INTO A FIRE ALARM SYSTEM PER NFPA
CODE OR OTHER REGULATIONS SO THAT, IN THE EVENT OF FIRE, THE TIME
DELAY WILL BE BYPASSED. CONTACT YOUR LOCAL CODE AUTHORITY TO VERIFY
COMPLIANCE WITH FIRE AND BUILDING CODES. THE DELAYED EGRESS DEVICE
SHOULD BE ROUTINELY CHECKED FOR PROPER OPERATION AND COMPLIANCE
WITH FIRE AND BUILDING CODES.
Note: * Separately-energized
UL 294 Access Control
Performance Levels: Levels:
Access Control Line Security Level I
Destructive Attack Level I
Endurance Level IV
Standby Power Level I