CAMDEN CX-WC17VR-PS Series User manual

Electrified Locks, Relays and Timers
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
1. GENERAL DESCRIPTION
The all-new Camden CX-WC17VR-PS Restroom Control Kit now comes with
the CM-221 Hands-Free Switch, which uses active infrared microburst sensor
technology and is designed to be used in ADA-compliant automatic door control
applications and access control. The CM-221 switch eliminates the spread of
germs by avoiding physical contact and provides greater convenience when
moving through the premises. For smooth operation, the CM-221 has an
adjustable time delay of 0.5 to 20 seconds and an adjustable range of 2” to 8”
(5cm to 20cm).
The CX-WC17VR-PS Restroom Control Kit is controlled by Camden’s advanced
relay logic controller, the CX-33. Camden’s CX-33 is a ‘state of the art’ logic relay
designed to support virtually any automatic door application.
The designation “PS” in the part number reects that this kit now comes pre-
wired in a metal enclosure with a power supply that is ready to accept all eld
wiring.
Operation at a Glance
The CX-WC17VR-PS has two modes: Mode 7 and Mode 8. The rst mode refers
to the “Normally Unlocked” condition, when the exterior PUSH to OPEN column
switch is pressed or waved, it triggers the door operator to open the door.
However, the second mode refers to the “Normally Locked” condition, when the
exterior PUSH to OPEN column switch is pressed or waved, it rst unlocks the
strike and triggers the door operator to open the door.
Inside the restroom, if the PUSH to LOCK column switch is pressed or waved, it
keeps the door locked in either mode and disables the exterior PUSH to OPEN
column switch. The LED light ring on the column switches turns red, indicating
the restroom is occupied. The user can either press or wave PUSH to UNLOCK
column switch as they exit the restroom. The LED light ring on the column
switches turns green, indicating the restroom is now available to be used.
Note: While exiting, the user can also use a crash bar, paddle, or doorknob
to unlock the door; in this case, the system will reset to its initial condition (mode
7 or mode 8), and the red light will turn green, allowing other users to use the
restroom.
2. MODE SETTING
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
Mode Selection
Mode selection depends on the user requirements;
• If the user wants restroom to be unlocked during idle state, use Mode 7.
• If the user wants restroom to be locked during idle state, use Mode 8.
Note: The default mode for the CX-WC17PS is Mode 7 (normally
unlocked).
There are three LED displays that will allow you to see what mode you
have selected when advancing through the modes. To change the mode of the
CX-WC17PS, simply press the MENU button once and use the UP button to
advance to the desired mode.
Mode Editing
Camden builds in typical times for lock release and door operator activation
is ready to use without changing any parameters. If you need to change the
timing or delay for an output, it can be done by pressing the “MENU” button
within the mode you selected. Once the option is selected, you can use the
“UP or DOWN” buttons to select the timing needed. The rst option (H & 1
ashing) will be how long relay 1 will be activated for (0-50 seconds). The
second option (d & 1 ashing) will be how long to wait before activating relay
2 (0-15 seconds). The third option (H & 2 ashing) will be how long relay 2
will be activated for (0-50 seconds). The fourth option (d & 2 ashing) will be
how long to wait before activating relay 3 (0-15 seconds). The fth option (H
& 3 ashing) will be how long relay 3 will be activated for (0-50 seconds). See
the table 2.1
Factory Reset (Defaulting the CX-33)
To return the CX-33 back to its factory default settings, you will need to
remove the power, then hold down the “MENU” button while powering
up the CX-33. Once started, you will see the rmware version listed then a
number “1” will be displayed. Reconnect your power and press the “MENU”
button once, then use the “UP” or “DOWN” button to advance to the desired
mode.
For proper functionality, fully test the operation of the CX-WC11PS.
Display (M) Description ( Mode you are in) Parameters (1-15 )
H, then 1 Relay 1 Hold Time 0.0 to 50 seconds
d, then 1 Relay 2 Delay Time 0.0 to 15 seconds
H, then 1 Relay 2 Hold Time 0.0 to 50 seconds
d, then 1 Relay 3 Delay Time Depends on Mode
H, then 1 Relay 3 Hold Time 0.0 to 50 seconds
dSets the display ON or OFF during operating mode ON or OFF
AInput delay on Activate. If other than 0.0 is selected, the input must
be held in for the time period chosen before the CX-33 will activate. 0.0 to 10 seconds
1Set Dry Input 1 to activate on normally open or normally closed contact. N/O OR N/C
2Set Dry Input 2 to activate on normally open or normally closed contact. N/O OR N/C
3Set Dry Input 3 to activate on normally open or normally closed contact. N/O OR N/C
4Set Dry Input 4 to activate on normally open or normally closed contact. N/O OR N/C
5Set Dry Input 5 to activate on normally open or normally closed contact. N/O OR N/C
Page 1 of 9 Page 2 of 9
Table 2.1 Dierent Modes for WC17VR-PS
3. CM-7536VR COLUMN SWITCH INSTALLATION
Code Requirements: If installed according to these instructions the CM-7536VR Column switch will meet the requirements of the California Building Code (Section
1117B.6, Date: 2009), and Section 3.8.3.3.17(b) of the Ontario Building Code.
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
CM-7536 With Touchless
Sensor CM-221
01/12/23
Angelo R.
CUST
CM-7536VR
375
8''
[955.04mm]
6''
[151.13mm]
13
4''
[44.28mm]
201
2''
[520.70mm]
24''
[609.60mm]
353
4'' [909.32mm]
33
8''
[85.17mm]
Installation Steps:
1. Take out pre-assembled unit from the box. To mount the switch, it
is required to disassemble a few components. Firstly, remove two
Phillips screw holding the top End Cap in place. Once both screws are
removed, take out the cap. Then, carefully pull out actuation bar and
place it aside so as to protect it from any surface damage.
D
C
B
A
A
B
C
D
1
2
3
4
56
7
8
87654321
NEXT ASSY USED ON
APPLICATION
MATERIAL
DRAWN
CHECKED
ENG APPR.
MFG APPR.
Q.A.
COMMENTS:
DAT E
NAME
TITLE:
SIZE
B
DWG. NO. REV
SCALE: 1:1
UNLESS OTHERWISE SPECIFIED:
SHEET 1 OF 1
DO NOT SCALE DRAWING
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL ± 1/64
ANGULAR: MACH ±0.5BEND ±
TWO PLACE DECIMAL ± 0.010
THREE PLACE DECIMAL ± 0.005
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
End Cap
Actuation Bar
2. Determine/Mark the optimum height and mounting location from the
nished oor to mount the column switch. See the illustration below
for the dimensions of the column switch.
3. Center the touchless switch over the box for wire connection, while
lining up the top edge with your mark (If installing through an in-wall
electrical box), drill a Ø 0.25” hole for wire connection (If installing
without an in-wall electrical box).
Figure 3.1 End Cap and Actuation Bar removal
Figure 3.2 Dimensions

CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
4. CX-ED2079 ‘universal’ electric strike installation
1. Firstly, verify that voltage required to operate Electric strike is compati-
ble with supply voltage of the installation.
POWER: Red/Black, Blue/Green (12 VDC)
Red, Black/Blue, Green (24 VDC)
Red/Green (Sort Black, Blue)
2. Splice the strike wire with the supplied wire and make sure to attach
provided varistor as described in connection section.
3. Make sure that the door jamb has an appropriate cutout to accommo-
date strike assembly. (Make sure to leave enough room for splicing
between power supply and electric strike wiring.)
4. For a wooden door jamb, drill holes to install the strike and nally use
supplied #12 x 1/2” machine screws to secure the strike.
CX-ED2079 ‘Universal’ Electric Strike
1. Prepare the door jambas per the appropriate drawing.
2. Install mounting brackets to jambusing M5x12 screws
and pressed metal nuts. Donot tighten.
faceplate into jamb. Add one of more spacers between
jamband mounting bracket when face plate extends
beyond the jamb. When the faceplate sits inside the
jamb, spacers must be added between the mounting
bracket & the lip bracket. Make sureclearance hole in
spacer aligns with hole in mounting bracket.
4. Connect wires coming from the low voltage side of the
transformer to wires (black)from strike.
5. Install electric strike jamb by attaching with # 10-32
screws and lockwashers.
6. Secure M5x12 screws holding mounting brackets to jamb.
4. Installation
Mounting Bracket
Spacer
Spacer (Option)
Spacer
M5x12 Flat-Head Screw (2pcs)
Jamp
M5x12 Screw
Vertical Centerline
Note: The products are intended to be installed in accordance
with the installation wiring diagram, mechanical assembly
drawings provided with each product, the local authority having
jurisdiction (AHJ) and the National Electric Code, NFPA 70.
When installed in fail secure mode, the local authority shall be
consulted with regard to the use of possible panic hardware to
allow emergency exit from the secure area.
The electric door strike shall be installed in such a way and
in such a location so as to not impair the operation of an
emergency exit device or panic hardware mounted on the door.
(86mm)
3-3/8”
(187mm)
7-3/8”
(36mm)
1-3/8”
(200mm)
7-7/8”
(86mm)
3-3/8”
(86mm)
3-3/8”
(168mm)
6-3/8”
(31mm)
1-7/32”
(31mm)
1-7/32”
(31mm)
1-7/32”
(105mm)
ESP1B + ESP2B
ESP3B
ESP4B
4-1/8”
(124mm)
4-7/8”
(89mm)
3-1/2”
(155mm)
6-1/8”
(173mm)
6-7/8”
(144mm)
5-11/16”
Note:
• The products are intended to be installed in accordance with the
installation wiring diagram, mechanical assembly drawings provided
with each product, the local authority having jurisdiction (AHJ) and
the electric code, NFPA 70. When installed in fail secure mode, the
local authority shall be consulted with the regards to the use of
possible panic hardware to allow emergency exit from the secure
area.
• The electric door strike shall be installed in such a way and in such
a location so as to not impair the operation of an emergency exit
device or panic hardware mounted on the door.
Page 3 of 9 Page 4 of 9
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
A.OLISA 24/03/22
CUST
Wave Switch wire
Cut-out
Drill a Ø 0.250'' Hole
Wall
In-wall
Electrical Box
Wall
Mounting without in-wall
electrical box Mounting with in-wall
electrical box
2 1/2''
[64.77mm]
CM-7536VR
Hands-Free
Column™
switch
CM-7536VR
Hands-Free
Column™
switch
4. Using a level tool, ensure the base unit is perfectly levelled and mark 4
mounting locations through the adjustable nylon inset screws onto the
wall surface (if mounting on drywall, use a pencil, and if mounting on
concrete wall, use a narrow sharp object for marking).
5. Drill the wall at the four marked locations and tap in the appropriate
wall plugs. We supply both drywall and concrete anchors for the
included #14 screws.
6. If mounting the Column Switch on an aluminium post or framing
section, drill and tap four holes for 1/4”-20 stainless steel machine
screws (also provided).
7. Connect all the wires coming from the CX-33PS box to the CM-221
sensor.
8. Secure the assembly with the provided mounting screw, and insert
actuation bar which was removed in step 1, and nally secure it with
End cap.
IMPORTANT: Do not apply power to the unit until you
have fully read the instructions and have made the
required adjustments.
The CX-WC17VR-PS Restroom Control Kit comes with the CX-33PS: Advanced
Logic Relay, Power Supply and Cabinet, which has a set of two terminal strips.
Each strip has a clear label for wiring, and it is also pre-wired, which eliminates
the need for a separate wiring manual for the termination point.However, later
sections of this manual include detailed wiring diagrams for reference.
The left-side terminal strip is used to power CX-33PS, the PUSH to OPEN (both
exterior and interior) column switches, PUSH to LOCK column switch, the door
position switch, and the wet trigger. The right switch of the terminal is used to
power the outputs to drive the strike (Relay 1), door operator (Relay 2), LED
light (Relay 3), and provide VDC power for the door strike.
There are six wires from CM-221 needs to be connected with terminal strips:
Wire Color (from
CM-221) Splicing With To (CX-33PS)
Red wire - +V DC
Black wire - -V DC
Yellow wire - Green LED
White wire - Red LED
Green Wire Top Switch wire Inside/Outside Push
to Open and Push
to Lock
Blue Wire Top Switch wire
IMPORTANT:
The supplied CX-TRX-5024 transformer will have its secondary terminals
wired to the terminals on the top of the left terminal strip marked as “AC”.
Next, wire the primary terminals to the AC feed to be used. Conrm your
connections and apply power by turning on the electrical panel breaker.
CONNECTIONS
Figure 3.3 Wall Mounting Options
Figure 3.3 Mounting of Base Unit
Table 3.1 Wiring Description for CM221
Figure 4.1 CX-ED2079 Strike Mounting
Figure 4.2 Mounting options for CX-ED2079
L4W 2T7
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
www.camdencontrols.com
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
Tel: (905) 366-3377
5502 Timberlea Blvd.
Mississauga, ON Canada
Angelo
08/12/22
CM-753VR Column Switch
2 1/2''
[62.0mm]
36''
[914.3mm]
36''
[914.3mm]
2 1/16''
[52.1mm]
Floor
Acuator
Base Unit
Insert
Screws
Mounting
Screw
Wall Anchors
Top Cap
Note:
While placing actuation bar back, make
sure that hanger sits perfectly into the slot.
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
87654321
NEXT ASSY USED ON
APPLICATION
MATERIAL
DRAWN
CHECKED
ENG APPR.
MFG APPR.
Q.A.
COMMENTS:
DAT E
NAME
TITLE:
SIZE
B
DWG. NO. REV
SCALE: 1:1
UNLESS OTHERWISE SPECIFIED:
SHEET 1 OF 1
DO NOT SCALE DRAWING
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL ± 1/64
ANGULAR: MACH ±0.5BEND ±
TWO PLACE DECIMAL ± 0.010
THREE PLACE DECIMAL ± 0.005
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
CAMDEN DOOR CONTROLS. ANY
REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN
PERMISSION OF CAMDEN DOOR
CONTROLS IS PROHIBITED.
5502 Timberlea Blvd.
Mississauga, ON Canada L4W 2T7
Tel: (905) 366-3377
www.camdencontrols.com
Hanger
Slot
End Cap
End Cap
Slot
Hanger

CONNECTIONS OPERATIONS
A Varistor is provided to protect strikes from large volume spike. Connect
varistor between the two input wires. Connection of the varistor varies
based on input voltage. Please refer following table for more details;
Power Varistor Connection
+ve end -ve end
12V Red/Black Blue/Green
24V Red Green
Note:
• For UL 294 and UL 1034 compliance, the door strikes are to be
powered via a UL 294 or UL 603 class 2 power limited output from
a control panel and/or power supply. In addition, when powered
by AC or DC, the units must have a UL-regulated UL 294 or UL 603
power limited class 2 output rated at 12 or 24 volts, as well as an AC
on indicator.
Red
Black
Blue
Green
Black
Red
Blue
Green
Black
Red
Blue
Green
(+12V)
( - )
(+24V)
( - )
12V
24V
Varistor
Varistor
Power
Power
POWER
12VDC
Red/Black: +12V
Blue/Green: Ground
A varistor is provided to protect strike from spikes.
Connect varistor between input wires.
Fail SafeChanging
Fail Secure
24VDC
Red: +24V
Black/Blue: -
Green: Ground
How to modify fail-safe to fail-secure or vice versa.
1. Loosen the screw as per the product diagram below.
2. Rotate the set plate 180°and slide the plate until
it is properly seated.
3. Tighten the screw.
Note: For UL 294 / UL 1034 compliance the door strikes are to be
powered via a UL 294/ UL 603 class 2 power limited output from a
control panel and or power supply. Furthermore, when powered
by AC/DC, the units shall use a UL regulated UL 294/UL 603 power
limited class 2 output rated 12/24V with AC on indicator.
Red
Black
Blue
Green
Black
Red
Blue
Green
Black
Red
Blue
Green
(+12V)
( - )
(+24V)
( - )
12V
24V
Varistor
Varistor
Power
Power
POWER
12VDC
Red/Black: +12V
Blue/Green: Ground
A varistor is provided to protect strike from spikes.
Connect varistor between input wires.
Fail SafeChanging
Fail Secure
24VDC
Red: +24V
Black/Blue: -
Green: Ground
How to modify fail-safe to fail-secure or vice versa.
1. Loosen the screw as per the product diagram below.
2. Rotate the set plate 180°and slide the plate until
it is properly seated.
3. Tighten the screw.
Note: For UL 294 / UL 1034 compliance the door strikes are to be
powered via a UL 294/ UL 603 class 2 power limited output from a
control panel and or power supply. Furthermore, when powered
by AC/DC, the units shall use a UL regulated UL 294/UL 603 power
limited class 2 output rated 12/24V with AC on indicator.
How to change from fail-safe to fail-secure and vice versa
• Loosen the screw as per the product diagram below.
• Rotate the set plate 180° and slide the plate until it is properly
seated.
• Tighten the screw.
ORDERING INFORMATION FOR PART REPLACEMENT
ITEM PART NUMBER DESCRIPTION
1 60-31A083 Commutateur de capteur sans contact avec contrôle LED externe
260-40E036 Advanced Logic Control Relay And 2 Amp Power Supply In Pre-Wired Metal Cabinet
3 CX-MDA Magnetic Door Contact
4CX-ED2079 Grade 2 Universal Electric Strike
5 CM-7536/4 36’’ Column “Push To Open” Switch
6 CM-7536/8B 36’’ Column ‘’Push To Lock’’ Switch
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
Notes :
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
Questions? Call us toll-free at 1-877-226-3369 or technical support 905-366-3377 (ext. 505)
Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
Opening New Doors to
Innovation, Quality and Support!
File: WC17VR-PS.indd
Rev.: December 7th 2022
Part No: 40-82B271VR
Page 5 of 9 Page 6 of 9
Figure 4.3 Connection for CX-ED2079
Figure 4.4 Fail Safe and Fail Secure mechanism for CX-ED2079

CX-WC17VR-PS Wiring Diagram
FILENAME:
DRAWING No:
SCALE: NONE DRAWN BY: REV:DATE:
CAMDEN DOOR CONTROLS
5502 Timberlea Blvd
Mississauga, Ontario
L4W 2T7
JML Aug 24, 2022 1
CX-WC17VR-PS Wiring Diagram
Notes
1. CX-33 can be set to Mode 7 (Normally Unlocked)
or Mode 8 (Normally Locked).
2. Mode 7 = Set Strike to Fail Safe.
3. Mode 8 = Set Strike to Fail Secure.
Door Position Switch
Transformer
CX-TRX-5024
24 VAC, 50 VA
CM-7536VR/4
Outside
Push to Open
CM-7536VR/4
Inside
Push to Open
CM-7536VR/8B
Push to Lock
Electric Strike
CX-ED2079
Wire MOV
directly to
strike or
magnet
120 VAC
N.C.
Model: 60-40E033
AC
AC
Outside
Push To Open
Inside
Push To Open
Push To
Lock
DPS NC
DPS COMM
+ WET
-INPUT
+ Lock
+ Strike
-Strike
*
Door
Operator
*
Green LED
Red LED
+ VDC
- VDC
PUSH
TO OPEN
MOV
Door Operator
PUSH
TO OPEN
PUSH
TO
LOCK
*
12 to 24 V DC (+)
0 V DC (Ground) (-)
Green LED
Red LED
Relay - Normally Open
Relay - Common
Relay - Normally Closed
CM221 Mode Pins:
OPEN (Default position) = Internal mode;
LED colors will be controlled by the IR Sensor
SHORTED = Extermal mode; LED colors will be
controlled by Yellow and White wires.
Distance Adjustment
(2” to 8”, 5 to 20 cm)
Turn clockwise
to increase range
Time Adjustment
(0.5 to 20 seconds)
For ToggleTurn
clockwise to increase
time delay
A B C
Page 7 of 9
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS

FILENAME:
DRAWING No:
SCALE: NONE DRAWN BY: REV:DATE:
CAMDEN DOOR CONTROLS
5502 Timberlea Blvd
Mississauga, Ontario
L4W 2T7
JML Aug 24, 2022 1
CX-WC17VR-PS Wiring Diagram
Model: 60-40E033
AC
AC
Outside
Push To Open
Inside
Push To Open
Push To
Lock
DPS NC
DPS COMM
+ WET
-INPUT
+ Lock
+ Strike
-Strike
*
Door
Operator
*
Green LED
Red LED
+ VDC
- VDC
*
CM221
Top Switch
Bottom Switch
Splice
12 to 24 V DC (+)
0 V DC (Ground) (-)
Green LED
Red LED
Relay - Normally Open
Relay - Common
Relay - Normally Closed
CM221 Mode Pins:
OPEN (Default position) = Internal mode;
LED colors will be controlled by the IR Sensor
SHORTED = Extermal mode; LED colors will be
controlled by Yellow and White wires.
Distance Adjustment
(2” to 8”, 5 to 20 cm)
Turn clockwise
to increase range
Time Adjustment
(0.5 to 20 seconds)
For ToggleTurn
clockwise to increase
time delay
CM-7536VR/4
Outside
Push to Open
CM-7536VR/4
Inside
Push to Open
CM-7536VR/8B
Push to Lock
A
B
C
CX-WC17VR-PS Wiring Diagram (CM-7536VR Detail)
Page 8 of 9
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS

SYSTEM OPERATION
OUTSIDE INSIDE
120V AC/15A
DEDICATED
CIRCUIT
5
WIRE SPECIFICATION
A 2 x 18 AWG
B 2 x 22 AWG
C 6 x 20 AWG
B
C
4
2
CX-WC17VR-PS EQUIPMENT PACKAGE:
1 CX-33PS (60-40E033) - POWER SUPPLY CABINET
WITH CX-TRX-4024 - 40VA, 24 VAC TRANSFORMER
2 CM-7536VR/4 - 36'' COLUMN "WHEELCHAIR'' SYMBOL AND "PUSH TO OPEN''
GRAPHICS WITH MOUNTED VALUEWAVE™ HANDS FREE SWITCH AND SIGN
3 CM-7536VR/8B - 36'' COLUMN ''LOCK'' SYMBOL AND ''PUSH TO LOCK''
GRAPHICS SWITCH WITH MOUNTED VALUEWAVE™ HANDS FREE SWITCH
AND SIGN
4 CX-MDA - MAGNETIC DOOR CONTACT
5 CX-ED2079 - GRADE2 UNIVERSAL ELECTRIC STRIKE
ADDITIONAL PARTS REQUIRED
BUT NOT INCLUDED WITH THE CX-WC17VR-PS
6 DOOR OPERATOR - SUPPLIED BY OTHERS
3
B
A
C
6
A
1
CX-WC17VR-PS OPERATION:
A. THE DOOR IS NORMALLY CLOSED AND UNLOCKED.
B. OPERATING THE EXTERIOR ACTIVE SWITCH OPENS THE
DOOR.
C. ONCE INSIDE AND THE DOOR IS CLOSED, PRESSING THE
COLUMN SWITCH WITH THE 'LOCK' SYMBOL
AND 'PUSH TO LOCK' LOCKS THE DOOR, THE LIGHT RING
AROUND THE VALUEWAVE™ HANDS FREE SWITCH
TURNS FROM GREEN TO RED.
D. PRESSING THE INTERIOR 'WHEELCHAIR' SYMBOL AND
'PUSH TO OPEN' COLUMN SWITCH UNLOCKS THE DOOR,
DEACTIVATES AND RESETS THE SYSTEM
E. IF THE DOOR IS OPENED MANUALLY TO EXIT THE
RESTROOM, THE OVERHEAD MAGNETIC CONTACT SWITCH
RESETS THE SYSTEM.
C
Spec Ref # CXWC17VR-PS
2
DOOR LOCKED WHEN RED
UNLOCKED WHEN GREEN
CX-WC17VR-PS SERIES RESTROOM KIT
INSTALLATION INSTRUCTIONS
Page 9 of 9
Table of contents
Other CAMDEN Door Lock manuals

CAMDEN
CAMDEN CX-EPD1289L User manual

CAMDEN
CAMDEN CX-ED1259-L User manual

CAMDEN
CAMDEN CX-ED2071 User manual

CAMDEN
CAMDEN CX-93M-26LS User manual

CAMDEN
CAMDEN CX-ED2079-1 User manual

CAMDEN
CAMDEN CX-ED1259L User manual

CAMDEN
CAMDEN CX-ED1410 User manual

CAMDEN
CAMDEN CX-DE1200 User manual

CAMDEN
CAMDEN CX-ED1079L User manual

CAMDEN
CAMDEN CX-EPD-1289L User manual
Popular Door Lock manuals by other brands

ACCESS CONTROL SOLUTION
ACCESS CONTROL SOLUTION Eternity 4 manual

Transmitter Solutions
Transmitter Solutions GEM-300 installation manual

Schlage
Schlage SCHLAGETOUCH user guide

Assa Abloy
Assa Abloy Yale PAS3621 quick start guide

Simons Voss
Simons Voss PegaSys Door Handle 4.1 Reader on both sides quick guide

Bg
Bg BG4000 user manual