Analogue inputs
analogue conversion 10 bit A/D converter in the CPU
type universal:(inputsB1,B2,B3,B6,B7,B8)REHAUNTCtemperaturesensor(-50T90°C;R/T10
kΩat25°C),HTNTC0T150°C,voltage:0to1Vdc,0to5Vratiometricor0to10Vdc,current:
0 to 20 mA or 4 to 20 mA, selectable via software. Input resistance in 0 to 20 mA= 100Ω
passive: (inputs B4, B5, B9, B10) REHAU NTC temp. sensor (see universal type),
PT1000(-100T200°C;R/T1000Ωat0°C)orvoltage-freedigitalinput(5mA),selectablevia
software;
maximum number 5,8,10,ontheSMALL,MEDIUMandEXTRALARGEN.O.,LARGEandEXTRALARGEN.C.
boards respectively
time constant for each input 0.5 s
precision ± 0.3 % of full scale
classication of the measuring
circuits (CEI EN 61010-1)
Category I
WARNING: the 21 Vdc available at the +Vdc terminal (J2) can be used to power any active probes, the maximum
current is 150 mA, thermally protected against short-circuits. To supply the ratiometric 0 to 5 V probes, use the
+5VREF (Imax: 60 mA) present at terminal J24.
Analogue outputs
type 0 to 10 Vdc optically-isolated
maximum number 4,4,6,ontheSMALL,MEDIUMandEXTRALARGEN.O./N.C.,LARGEboardsrespectively
power supply external 24 Vac/Vdc
resolution 8 bit
maximum load 1 kΩ (10 mA)
precision ± 2 % of end scale on outputs: Y1, Y2, Y3 and Y4
-2%/+5% of end scale on: Y5 and Y6
Digital outputs
type relay
maximum number 8, 13, 18, 27, 29, on the SMALL, MEDIUM, LARGE, EXTRALARGE N.C., EXTRALARGE N.O. boards respectively
For the requirements refer to Figs. 3 to 5 (reference NO*, NC* and C*). Note the presence of outputs with changeover
contacts kept separately (that is, without the poles shared between dierent outputs). Groups from 2 to 5 outputs have 2
“common”polesforeasyassembly.
Make sure that the current running through the common terminals does not exceed the rated current of each individual terminal,
that is 8A.
Insulation distance the outputs can be divided into groups. There is double insulation between groups (between cells in
the table).
Note: the relays in the same group must have the same power supply (24 or 230 Vac).
Makeup of the groups version relays with same insulation
SMALL 1…7 8 - - -
MEDIUM 1…7 8 9…13 - -
LARGE 1…7 8 9…13 14…18 -
EXTRALARGE N.O. 1…7 8 9…13 14…16 17…20 21…24 25…29
EXTRALARGE N.C. 1…7 8 9…13 14…16 17…20 21…24 25…27
Note: the relays in the individual cells of the table have basic insulation between them, while
between groups (cell-cell) there is double insulation.
Changeover contacts 1,3,5,ontheSMALL,MEDIUMandEXTRALARGEN.O./N.C.,LARGEboardsrespectively
Switchable power warning: the relay outputs have dierent characteristics according to the model of pCO3
relay
type A
type of relay:SPDT, 2000 VA, 250 Vac, 8 A resistive
pCO3approval: UL873: 2.5 A resistive, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cycles)
EN 60730-1: 2 A resistive, 2 A inductive, cosϕ= 0.6, 2(2) A (100000 cycles)
relay
type B
type of relay: SPDT, 1250 VA, 250 Vac, 5 A resistive
pCO3approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cosϕ= 0.6, 1(1) A (100000 cycles)
relay
type C
type of relay:SPDT, 1250 VA, 250 Vac, 5 A resistive
pCO3approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cosϕ= 0.6, 1(1) A (100000 cycles)
SSR outputs 1:SMALL(output7);2:MEDIUM-EXTRALARGEN.O./N.C.(outputs7,12);3:LARGE(OUTPUTS7,12,
14),operatingvoltage,24Vac/Vdc;maximumpower:10W