manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CDVI
  6. •
  7. Control Unit
  8. •
  9. CDVI CA-A470-A User manual

CDVI CA-A470-A User manual

Introduction
Connected to the CT-V900 controller’s expansion bus, the
2-Door Expansion Module (CA-A470-A) supports two
readers, two BCD keypads, four zone inputs, 6 outputs
and two locking devices.
Specications
CA-A470-A Specications:
Readers: connect 2 per module
Keypads: connect 2 per module
Inputs: 4 standard without ATZ, 1 tamper
Outputs: 6 (open collector)
Lock Outputs: 2 lock outputs (Form C relays)
each: 15A @ 16VDC (resistive)
AC Power: 16VAC, 40VA max.
Frequency: 50Hz/60Hz
Aux. Current: 500mA (max.)
Battery: 12VDC, 7Ah
low battery = 10.2VDC
ow battery restore = 12.2VDC
low battery cut-off = 8.5VDC
Communication: expansion bus (E-Bus), RS-485, Plug
and Play, 3 modules per CT-V900
Operating temp.: 5°C to 55°C (41°F to 133°F)
Assign Address (1 and 2)
DIP switches 1 and 2 determine the 2-Door
Expansion Module’s address in the network,
regardless of the order that they are connected
to the controller. Centaur recognizes the doors
according to the DIP switch settings as shown in
Figure 1.
Figure 1: Setting the network address
“No Card”
Access is denied to all cards and doors
are locked until communication is restored.
“2 Cards”
Access is granted only when 2 cards of
a valid format are presented to the reader.
“All Cards”
Access is granted when any card with
a valid format is presented to the reader.
“Unlock Door”
Doors are unlocked until communication
is restored.
Figure 3: Setting the A+ and B- jumpers
350mA/700mA Battery Charging Jumper
The 350mA/700mA Jumper allows you to select the
charging current for the backup battery of the 2-Door
Expansion Module. Charging the battery at 350mA takes
longer, but consumes less power. Charging the battery at
700mA takes less time, but consumes more power.
Figure 4: Setting the 350mA/700mA jumper
Programming in Centaur
Using the Centaur Access Control Software, program the
inputs, outputs, readers, and keypads connected to the 2-
Door Expansion Module. The options are explained in the
Centaur Access Control Software Reference Manual.
Centaur will identify the 2-Door Expansion Module by its
address (see DIP Switches 1 to 4) and will recognize the
devices as follows:
DIP Switches
In order for new DIP switch settings to take effect,
the 2-Door Expansion Module’s power must be
disconnected and then reconnected.
CA-A470-A Instructions
2-Door Expansion Module
31, avenue du Général Leclerc - 93500 PANTIN FRANCE
Tél. : 33 (0)1 48 91 01 02 - Fax : 33 (0)1 48 91 21 21
De-energized: no power in normal state; requires
power to activate.
Energized: power in normal state; remove power
to activate.
Lock #1 = DIP switch 3
Lock #2 = DIP switch 4
ON = Energized:
During a communication failure, the normal state of the
lock output is Energized. When Lock #1 or Lock #2
is activated, power is removed from the corresponding
lock output to unlock the door. Activation depends
on the setting of the DIP switches 5 & 6 (Access during
Communication Failure).
OFF = De-energized:
During a communication failure, the normal state of the
lock output is De-energized. When Lock #1 or Lock #2
is activated, power is applied to the corresponding lock
output to unlock the door. Activation depends on the setting
of the DIP switches 5 & 6 (Access during Communication
Failure).
Lock State during Communication Failure
DIP switches 3 and 4 determine the state
of Lock #1 and Lock #2 ONLY during a
communication failure between the 2-Door
Expansion Module and the controller
(CT-V900-A). Normally, the lock outputs
follow the Lock Control for the CT-V900-A.
Therefore, the DIP switches should have the same setting
as the Lock Control for the corresponding doors in Centaur.
CT-V900
Door 1
CA-A470-A
Door 4 Door 3
Door 2
CA-A470-A
Door 4 Door 3
CA-A470-A
Door 4 Door 3
Address 3
Add 1 = OFF
Add 2 = ON
Address 2
Add 1 = OFF
Add 2 = ON
Address 1
Add 1 = OFF
Add 2 = ON
Access during Communication Failure (5 and 6)
DIP switches 5 and 6 determine the access
to the protected doors during a communication
failure.
Activate Output on Communication Failure (7)
DIP switch 7 determines if OUT5 and OUT6 will
pulse during a communication failure. When DIP
switch 7 placed in the ON position, the outputs on
the device(s) connected to the OUT5 and OUT6
terminals will pulse. For example, the LED on
the reader can pulse to advise users that a
communication failure has occurred.
DIP Switch (8)
For future use.
EOL Jumper
Place the EOL jumper ON if the 2-Door Expansion Module
is at the beginning (Start Point) or at the end (End Point) of
the E-bus Network (see Figure 2). Otherwise, place the
EOL jumper OFF.
Figure 2: Setting the Jumpers
5 = off (0)
6 = off (0)
5 = on (1)
6 = off (0)
5 = off (0)
6 = on (1)
5 = on (1)
6 = on (1)
During a Communication Failure:Setting
Switch
High/Low Bias Jumpers
Place the A+ and B- jumpers on LOW only if the 2-Door
Expansion Module is at the beginning (Start Point) of the
E-bus Network. Otherwise, place the A+ and B- jumpers
on HIGH (see Figure 2 and Figure 3).
START POINT
END POINT
High/Low Bias Jumpers
A+ = Low
B- = Low
EOL Jumper
EOL = On
High/Low Bias
Jumpers
A+ = High
B- = High
EOL Jumper
EOL = Off
High/Low Bias
Jumpers
A+ = High
B- = High
EOL Jumper
EOL = Off
High/Low Bias
Jumpers
A+ = High
B- = High
EOL Jumper
EOL = On
CA-A470-A CA-A470-A CA-A470-A
Doors cannot be dened as Door Type Elevator
(Door Properties window, General tab, Door
Type: Elevator) and the module does not support
Interlock Inputs (Door Properties window, Inputs
and Outputs tab, Interlock Input).
Other modules in the system cannot activate the 2-
Door Expansion Module’s outputs.
The 2-Door Expansion Module does not support
Zone Doubling (see Figure 6).
Jumpers set to low
Jumpers set
as 350mA
Jumpers set
as 700mA
Jumpers set to high
Door 5
Door 6
Input 21
Input 22
Input 23
Input 24
Output 13
Output 14
Output 15
Output 16
Output 17
Output 18
Address 1
Door 3
Door 4
Input 17
Input 18
Input 19
Input 20
Output 7
Output 8
Output 9
Output 10
Output 11
Output 12
Address 1
Doors
Keypad/Reader 1
Keypad/Reader 2
Inputs
Z1
Z2
Z3
Z4
Outputs
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
Door 7
Door 8
Input 25
Input 26
Input 27
Input 28
Output 19
Output 20
Output 21
Output 22
Output 23
Output 24
Address 1
Figure 6: Connection drawing of the CA-A470-AFigure 5: CA-A470-A indicators
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as spe-
cically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and tness for
a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not
manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to
operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller’s option, any product not meeting the specications. Returns
must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct
or indirect or consequential or incidental, including without limitation, any damages for lost prots stolen goods, or claims by any other party, caused by defective goods or
otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold. Notwithstanding the preceding paragraph, the Seller’s maximum
liability will be strictly limited to the purchase price of the defective product. Your use of this product signies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.
© 2006 CDVI. All rights reserved.
Centaur is a trademark or registered trademark of CDVI or its afliates in Canada, the United States and/or other countries.
The reader LEDs can be used to verify the reader’s connections and programming. If no ashing occurs when a card
is presented to the reader, the reader may be installed incorrectly. A short ash indicates that the reader is correctly
installed, but the card is the wrong type or that the reader was incorrectly programmed.
24VDC 24VDC Power Supply
(Optional connection method)
V-
V+
V-
LOCK 2
KEYPAD 2
(BCD)
16V Transformer
40VA
Gell Cell BAttery
12V, 7 Ah
E-BUS :
To CT-V900 or to
other CA-A470-A
E-BUS
Connect to tamper
switch (N.C.)
Terminals for
KEYPAD 2
See inputs in Centaur Software
manual: setting ATZ 2R Connection
Input 1
1KΩ
1KΩ
1KΩ
OR
EOL
Z
COM
OR
Z
COM
See inputs in Centaur Software
manual: setting ATZ 3R Connection
See inputs in Centaur Software
manual: setting NC Input Connection
Reader and keypad wiring may differ
from the diagram. Please consult
your dealer for details.
Terminals for KEYPAD 1
READER 1
BROWN
RED
ORANGE
YELLOW
WHITE
GREEN
BLACK
RED
YELLOW
BROWN
WHITE
GREEN
BLUE
ORANGE
BLACK
12VDC
LOCK 1
+
SP
+12V
R1/KPD
R1/KPC
R1/KPB
R1/KPA
OUT2
OUT1
R1/D1
R1/D0
R1/0V
R1/+5V
SP
+12V
R2/KPD
R2/KPC
R2/KPB
R2/KPA
OUT4
OUT3
R2/D1
R2/D0
R2/0V
R2/+5V
AC
AC
BAT+
BAT-
V+
V+
V-
V-
OUT6
OUT6
A+
B-
GND
TAMPER
TAMPER
D1NC
COM
D1NO
D2NC
COM
D2NO
Z1
COM
Z2
Z3
COM
Z4
CA-A470-A
LOCK#1
AC OK
EOL
BACKUP
SWITCH
ADD 1
SW1
ADD 2
SW2
L1Energize
SW3
L2Energize
SW4
BACKUP1
SW5
BACKUP2
SW6
PULSE 5&6
SW7
N/D
SW8
READER#1
DATA
READER#2
DATA
NO CARD
LOW HIGH
TX RX
E-BUS
B-
A+
2 CARDS
ALL CARDS
UNLOCK DOOR
2
0
0
1
1
1
0
1
0
1
AUX OK
COMM
CHECK BATT
BATT TR BL
LOCK#2
STATUS
JP120
350mA/700mA
ON
1 2 3 4 5 6 7 8
+
SP
+12V
R1/KPD
R1/KPC
R1/KPB
R1/KPA
OUT2
OUT1
R1/D1
R1/D0
R1/0V
R1/+5V
SP
+12V
R2/KPD
R2/KPC
R2/KPB
R2/KPA
OUT4
OUT3
R2/D1
R2/D0
R2/0V
R2/+5V
AC
AC
BAT+
BAT-
V+
V+
V-
V-
OUT5
OUT6
A+
B-
GND
TAMPER
TAMPER
D1NC
COM
D1NO
D2NC
COM
D2NO
Z1
COM
Z2
Z3
COM
Z4
CA-A470-A
LOCK#1
AC OK
EOL
BACKUP
SWITCH
ADD 1
SW1
ADD 2
SW2
L1Energize
SW3
L2Energize
SW4
BACKUP1
SW5
BACKUP2
SW6
PULSE 5&6
SW7
N/D
SW8
READER#1
DATA
READER#2
DATA
NO CAR D
LOW HIGH
TX RX
E-BUS
B-
A+
2 CARD S
ALL CARDS
UNLOCK DOOR
2
0
0
1
1
1
0
1
0
1
AUX OK
COMM
CHECK BATT
BATT TRBL
LOCK#2
STATUS
JP120
350mA/700mA
ON
1 2 3 4 5 6 7 8
Green “READER#2 DATA” and “READER#1 DATA” LED:
Long ash = Receiving card read
Short ash = Receiving card read, but the system
does not recognize the card’s format
OFF = Not receiving card read
Green “AC” LED:
ON = AC power
OFF = Power failure
Green “AUX” LED:
ON = Auxiliary power
OFF = Auxiliary power failure
Red “COMM” LED:
ON = Communication failure
OFF = OK
Green “CHECK BATT” LED:
ON = Battery verication in
progress (every minute)
Red “BATT TRBL” LED:
ON = Battery low or disconnected
Green “STATUS” LED:
Flash = Module OK
Slow ash = Communication failure
(see also “COMM” LED)
Green “LOCK#1” and “LOCK #2” LEDs:
ON = Relay activated.
Red “TX” LED and green “RX” LED:
ON = Communication OK (may icker)
OFF = Communication failure
Warning
2-Door Expansion Module (CA-A470-A)
16Vac Transformer Only
The use of a transformer with a rating other 16Vac
can severaly damage the module.
Firmware Requirements
The 2-Door Expansion Module can only be used
with CT-V900-A rmware version R2-C3-05 or higher.
Software Requirementrs
The 2 -Door Expansion Module can only be used
with Centaur version 3.0 build 400 or higher.

Other manuals for CA-A470-A

1

Other CDVI Control Unit manuals

CDVI CA-A470-A User manual

CDVI

CDVI CA-A470-A User manual

CDVI TPV User manual

CDVI

CDVI TPV User manual

CDVI ARD2/12 User manual

CDVI

CDVI ARD2/12 User manual

CDVI ATRIUM ADH10 User manual

CDVI

CDVI ATRIUM ADH10 User manual

CDVI ATRIUM A22K User manual

CDVI

CDVI ATRIUM A22K User manual

CDVI SASIC User manual

CDVI

CDVI SASIC User manual

CDVI CA-ETHR-A User manual

CDVI

CDVI CA-ETHR-A User manual

Popular Control Unit manuals by other brands

Walther Systemtechnik VMS-08 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-08 Assembly instructions

Avaya JBM24 Using instruction

Avaya

Avaya JBM24 Using instruction

Backflow Direct Magnum 20 Maintenance instructions

Backflow Direct

Backflow Direct Magnum 20 Maintenance instructions

Siemens ZAM-180 installation instructions

Siemens

Siemens ZAM-180 installation instructions

Lantronix PremierWave user guide

Lantronix

Lantronix PremierWave user guide

pumpa PC-58 Translation of the original instruction manual

pumpa

pumpa PC-58 Translation of the original instruction manual

GTE FST-75 operating instructions

GTE

GTE FST-75 operating instructions

Surefire BMS-300 Installation and operation manual

Surefire

Surefire BMS-300 Installation and operation manual

Timotion TC16P Series user manual

Timotion

Timotion TC16P Series user manual

CAME BPT DMVC/08 manual

CAME

CAME BPT DMVC/08 manual

FrSky TWIN Lite Pro instruction manual

FrSky

FrSky TWIN Lite Pro instruction manual

Siemens FDCI723 Installation

Siemens

Siemens FDCI723 Installation

Orbinox SG Series Installation, operation & maintenance manual

Orbinox

Orbinox SG Series Installation, operation & maintenance manual

Tyco DPV-1 manual

Tyco

Tyco DPV-1 manual

Danfoss RLV-X instructions

Danfoss

Danfoss RLV-X instructions

Kentec Electronics 723 Information guide

Kentec Electronics

Kentec Electronics 723 Information guide

Ludl Electronic Products MAC 2000 Configuration manual

Ludl Electronic Products

Ludl Electronic Products MAC 2000 Configuration manual

EOS EmoStyle Di Installation and operation manual

EOS

EOS EmoStyle Di Installation and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.