  9. Chenzhu GS8558-EX User manual

Chenzhu GS8558-EX User manual

GS8558-EX
GYB15.1559
CZ.GS8558-EX.11(S)E-3.0/17.04
5
4
1
2
3
3
2
1
XK06-014-00557
Connections
(1)
(2).
(3).
(4).
. This barrier adopts knock-down connector with screw terminals. The
intrinsically safe(IS for short) terminals (blue plugs) should be connected
to hazardous area devices and the non-IS ones (green plugs)to the safe
area devices.
Choose for the harzardous area the blue-marked wires. Its minimum
2
cross section area should be 0.5 mm ,and minimum dielectric strength
should be 500V.
The wirings in safe area and hazardous area must be separated, and
both have protection bushes.
A length of 8mm bared wire is locked by the M3 bolt. See as shown
below.
Installation
The isolated barrier should be located at safe area, according to the
related requirements in IEC60079-17(EN60079-17)and IEC60079-
19(EN60079-19).
GS8500-EX series isolated barrier are designed for mounting on 35mm
DIN guide rail.
Installation according to the following steps:
(1). First make the bus-powered outlet locked into the guide rail;(If no bus-
powered function,omit this step);
(2). Make the upside of the barrier locked into the guide rail;
(3). Push the downside of the barrier in the rail.
Disassembly
(1).Insert a screwdriver (its edge length≤6mm)into the downside metal lock
of the barrier;
(2).Push the screwdriver upwards,then prize the metal lock downwards;
(3).Take the barrier out of the guide rail.
(1).Before using, please check again whether the module’s Ex-proof rating
accords to the operation conditions, and also wiring and polarity are correct.
(2).It is disallowable to test insulativity among the terminals with a
megameter. If necessary, the wires must be cut off before testing ,or the
internal fuse would blow.
(3).Every product has been test strictly before leaving factory. If users find
any abnormality in the module, please contact the nearest agent or our
company.
(4).In 5 years from the delivery date, if the product works improperly during
normal operation, we will repair or replace it without payment.
Non-intrinsically safe terminals Intrinsically safe terminals
Maintenance
Isolated Barrier
User Manual
Caution
Please check whether the product type on the package accords
to the ordering contract;
Read this manual carefully before installation or using. If there is
something unclear, please dial technic support hotline-400 881 0780;
Isolated barrier should be located in the safe area;
Supply voltage is 24VDC, 220VAC is forbidden;
Users are not allowed to dismantle or repair the barrier otherwise
it will induce malfunction.
Please read the instruction manual carefully before use the product,
and please safekeeping.
YEAR
YEAR
WARRANTY
WARRANTY
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
Email:chenzhu@chenzhu-inst.com
http://www.chenzhu-inst.com
M3
8.0
National Supervision and Inspection Center for Explosion Protection
and Safety of Instrumentation(NEPSI)
Compliancy with standard: GB3836.1、GB3836.4 and GB3836.20
Ex-marking: [Ex ia Ga] ⅡC
maximum voltage: Um=250V
Intrinsic safety parameter:(7,8 terminals)
Uo=1.2V, Io=0.2mA, Po=0.06mW
ⅡC:Co=100μF , Lo=100mH
ⅡB:Co=300μF , Lo=300mH
ⅡA:Co=800μF , Lo=800mH
(1) For distributed inductance and capacitance e.g. as in a cable, allow
the values of capacitance and inductance;
(2) For circuits containing up to 1 % inductance or up to 1%
capacitance with a cable, allow the values of capacitance and inductance;
(3) For connection of the combined inductance and capacitance where
both are greater than 1% of the allowed value (excluding the cable), allow
up to 50% each of the values of capacitance and inductance.
Largest external capacitance (Co) and inductance (Lo) numerical
attention when using the following requirements:
Application
Dimensions
118.9mm×106.0mm×12.5mm
1 2 3
Safe-area
Hazardous-area
Summarize Operation Conditions
Specification
Vibration sensor input
hazardous area can be 1:1 safe area, can
transmit AC and DC signals. Input circuit,output circuit and power supply
are each galvanically isolated.
isolated barrier, voltage signal outputed by
sensor in transmission to
(1). The air should not contain any medium corrupting the coat of
chrome,nickel and silver.Moreover,violent quiver and impact or any cause
of electromagnetic induction (such as big current or spark,etc.)must be
avoided when using.
(2). Operating temperature: -20℃~+60℃
(3). Storage temperature: -40℃~+80℃
(4). Relative humidity: 10%~90%
Intrinsic safety explosion protection loop system
Special requirements have to be confirmed before using the intrinsically
safe explosion loop system(intrinsically circuit) which connected by isolated
barrier and intrinsically safe apparatus in field:
(1) The explosion level of intrinsically safe apparatus should meet the
requirements of operation conditions. The apparatus should pass the
explosion protection test and get the certificate by state-authorized
explosion-proof product certification bodies.
(2) The intrinsic safety parameters of isolated barrier and intrinsically
safe apparatus both are sure, and comply with 12.2.5 of GB 3836.15-2000.
(3)If any parameters are unclear, the system has to be confirmed by
state-authorized explosion-proof product certification bodies.
Safety Certificates
Number of channels: 1
Supply voltage: 20~35V DC
Current consumption:≤40mA
Safe-area output:
Signal: -10V +10V
Load resistance: RL≥20kΩ
Hazardous-area input:
Signal: -10V +10V
Impedance: 10kΩ
DC Transfer accuracy: <±0.2%F.S.
AC Transfer accuracy: 0Hz 600Hz ±0.2%F.S.
600Hz 10kHz -1.5% + 0.2%F.S.
Phase response: Less than 10us is equals to
-0.72 00Hz
-2 00Hz
-3.6 kHz
-36 0kHz
Voltage bandwidth: -3dB≤40kHz
Temperature drift: 0.005%/℃(-20℃60℃
Power supply protection: Protect the barrier form reverse supply voltge
destroy
Electromagnetic compatibility:According to GB/T 18268(IEC 61326-1)
Dielectric strength:
Between non-intrinsically safe circuits and intrinsically safe circuits≥
2500VAC
Between power supply part and non-intrinsically safe part≥500VAC
Insulation resistance:
Between non-intrinsically safe part and intrinsically safe part≥100MΩ
Between power supply part and non-intrinsically safe part≥100MΩ
Weight: Approx.100g
Suitable location:
Mounting in non-hazardous area, and connected to the IS apparatus in
zone 0 hazardous area.
Suitable IS apparatus:
~
~
~
~ ~
~+)
°2
°6
°1
°1
Vibration sensor
IN OUT
Monitoring
equipment
2(-)
1(+)
-+
7(+) 6(-)
8(-) 5(+)
Vibration
sensor
GS8558-EX
Power supply
Power supply

This manual suits for next models

1

Other Chenzhu Surge Protector manuals

Chenzhu CZLB-160/440 Series User manual

Chenzhu

Chenzhu CZLB-160/440 Series User manual

Chenzhu CZLB-80/440 Series User manual

Chenzhu

Chenzhu CZLB-80/440 Series User manual

Chenzhu CZLB-160/440 Series User manual

Chenzhu

Chenzhu CZLB-160/440 Series User manual

Chenzhu CZLB-EX Series User manual

Chenzhu

Chenzhu CZLB-EX Series User manual

Chenzhu CZLBX-48-S Series User manual

Chenzhu

Chenzhu CZLBX-48-S Series User manual

Chenzhu GS8568-EX User manual

Chenzhu

Chenzhu GS8568-EX User manual

Chenzhu GS8567-EX User manual

Chenzhu

Chenzhu GS8567-EX User manual

Chenzhu GS8515-EX User manual

Chenzhu

Chenzhu GS8515-EX User manual

Chenzhu CZLBX-48 Series User manual

Chenzhu

Chenzhu CZLBX-48 Series User manual

Chenzhu CZLB series User manual

Chenzhu

Chenzhu CZLB series User manual

Popular Surge Protector manuals by other brands

Adcom ACE-315 owner's manual

Adcom

Adcom ACE-315 owner's manual

Asco Series 300 Installation & operation manual

Asco

Asco Series 300 Installation & operation manual

Axis TU8001 installation guide

Axis

Axis TU8001 installation guide

ABB REU615 Applications manual

ABB

ABB REU615 Applications manual

Kathrein KAZ 10 manual

Kathrein

Kathrein KAZ 10 manual

Total Protection Solutions TK-CT2-190TLP1-TB Installation, operation and maintenance manual

Total Protection Solutions

Total Protection Solutions TK-CT2-190TLP1-TB Installation, operation and maintenance manual

OPTI-UPS SBAH-821 Specification sheet

OPTI-UPS

OPTI-UPS SBAH-821 Specification sheet

Philips SPP2307WC Specifications

Philips

Philips SPP2307WC Specifications

Monster POWER SHIELD XL user manual

Monster

Monster POWER SHIELD XL user manual

socomec SURGYS E10 quick start guide

socomec

socomec SURGYS E10 quick start guide

Patton electronics 533 user manual

Patton electronics

Patton electronics 533 user manual

SC&T SP003 user manual

SC&T

SC&T SP003 user manual

Rice Lake TP232 installation guide

Rice Lake

Rice Lake TP232 installation guide

Savio LZ-12 user manual

Savio

Savio LZ-12 user manual

Monster Power PowerCenter HTS 2600 MKII owner's manual

Monster Power

Monster Power PowerCenter HTS 2600 MKII owner's manual

Bits Limited Smart Strip user guide

Bits Limited

Bits Limited Smart Strip user guide

Bauhn ASPP8-0421-W user guide

Bauhn

Bauhn ASPP8-0421-W user guide

Austere VII Series user guide

Austere

Austere VII Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.