Typical applications
Single phase system
Main technical parameters
Installation
Overcurrent
protection device
SPD
Devices
Protected
<10m
C
b
a
c
Normal connection
SPD
C
Dimension
When install SPDs, the connection cable should be as short as
possible. As the diagrams shown below, L( in normal
connection) should be less than 0.5 meters. Cable between SPD
and the protected device should be less than 10m. The housing of
the protected device should be grounded via SPD terminals.
L=a+b+c
In case of the main circuit broken because of a failed SPD, a
protection device such as air switch or fuse should be installed
before the SPDs. According to our tests, protection devices with a
nominal current of 100A are recommended. The cross sectional
area of the upper (for L/N connection) cable should be no less than
2
6mm and the cross sectional area of the cable for grounding should
2
be no less than 10mm .
L
Devices
Protected
PE
L
N
220VAC
Main switch
Overcurrent
protection device
Devices
Protected
General
V connection
1 2 3
CZLB-160/440/2P
Nominal operating voltage Un: 220VAC
Max. operating voltage Uc: 440VAC
Nominal discharge current In (8/20us): 80kA
Max. discharge current Imax (8/20us): 160kA
Protection level Up: <2.8kV
Response time: <25ns
Leakage current: <20uA
Status indication: Blank:OK
Red:failed
Ambient temperature: -40℃~70℃
Relative humidity: 10%-90%
Air switch or fuse: 100A
2
Connection cable sectional area L/N: ≥6mm
2
Connection cable sectional area PE: ≥10mm
Housing protection level(IEC60529): IP 20
Housing material flame-retarded level(UL94): PBT/V0
Installation: Standard 35mm DIN rail
Testing standard: GB 18802.1/IEC 61643-1
Performance test: Shanghai Lighting Protection Center
Impulse current Iimp (10/350us): 15kA
CZLB -160 /440 series AC power supply SPDs are designed
according to the domestic criterials. It enables the connection
between the power supply system and an equipotential network
instantaneously when the surge occurs and limit the residual voltage
to a certain level to protect the devices protected. Normally, it is
used in lighting protection zone 1. For better protection effect, SPDs
with different protection levels should be used downstream.
Schematic diagram
36mm
91mm
63mm
CZLB-160/440 series SPDs are delivered in single pieces. They
should be connected by a bus-bar and then you can choose any piece
for ground connection. Otherwise you need to ground all pieces.
Loosen all the screws completely before you put the bar in and then
tighten the screws except the one you chose for ground connection.
Bus-bar installation
Bus Bar
Grounding Calble
PE
L/N
Red
Blank F1
Rv
CZLB-160/440
<10m
Surge
Surge
LN