1 2 3
Model designations
CZLBX-48 - □ □
CZLBX s eries SPD
Max. operating voltage
Note:Please tell us when you need a different thread require. Wire
2
size 32/0.2(1.0mmm , 18AWG), length 150mm. Either screw on the
shell or earthing terminal within the instrument can connect to
ground.
National Quality Supervision and Inspection Center for Products of
Process Automation Instrumentation
Cerfication standards:
GB/T 20438.1(IEC 61508-1)
GB/T 20438.2(IEC 61508-2)
GB/T 18802.21(IEC 61643-21)
Functional safety level:SIL3
Safety cerfication
Summarize
(1).No signal attenuation.
(2).Maximum discharge current is 20kA.
(3).Get double certifications which are Intrinsic Safety and Flame proof,
suitable for every occasions.
(4).Choose a variety of thread sizes for your require, suitable for all types of
equipment.
CZLBX-48-S serials SPD are part of field-installed.There are mainly
used to protect device such as transimitters、solenoid valve flowmeter、
RS232、RS485 and other equipments.A main objective is to avoid
damage caused by lightning strikes.The connecting ground by Yellow-
Green wires or .It can be used in 0 zone、
1zone、2zone、ⅡA、ⅡB、ⅡC、T4~T6 hazardous zone.
earthing terminal with the shell
Specification
Dimensions
Explosion-proof parameters
EX-standards:
Ex ia IIC T4~T6 Ga
Ex d IIC T4~T6 Gb
Cerfication standards:
GB3836.1-2010(IEC 60079-0)
GB3836.2-2010(IEC 60079-1)
GB3836.4 -2010(IEC 60079-11)
Explosion-proof parameters:
China National Quality Supervision and Testcentre for Explosion
Protected Electrical Products(CQST).
Rated operating voltage Un (DC):
Max. operating voltage Uc (DC) :
Rated operating current IL:
Rated discharge current In(8/20us):
Max. discharge current Imax(8/20us):
Total discharge current Itotal(8/20us):
Protection level Up(8/20us, line to line):
Protection level Up(8/20us, line to ground):
Response time (line to line):
Response time (line to ground):
Bandwidth(-0.5dB):
Resistance per path:
Leakage current:
Temperature range:
Relative humidity:
Material:
Degree of protection:
Test standards:
Lightning protection performance test:
24V
48V
400mA
10KA
20KA
40KA
60V
600V
1ns
100ns
2MHz
2.2Ω
<2uA
-40℃~+85℃
5%~95%
304 stainless steel
IP65
GB 18802.21
IEC 61643-21
Shanghai lightning protection
Thread Standards:
2、1/2" NPT
3、3/4" NPT
4、Pg 13.5
1、M20×1.5
5、G 1/2"
6、G 3/4"
external thread internal thread
Depth:14mm
45mm
28mm84mm
13mm
11mm13mm 26mm
3:3-Wire
Blank:2-Wire
4:4-Wire
S:Cascade model
Blank:Parallel model
50V 32mA 0.4W
Type
CZLBX-48-S
CZLBX-48-S3 50V 16mA 0.2W
Li
0uF 0mH
0mH
Ci
0uF
Pili
Ui
Customer can specify the thread standards:
□ M20×1.5(International)
□ 1/2" NPT(American)
□ Pg13.5(German)
□ G1/2"(British)
□ 3/4" NPT(American)
□ G3/4"(British)