Specification
Leakage current
Protection level
Up(line to line)
Protection level
Up(line to ground)
Rated operating
voltage Un
Max.operating
voltage Uc
Model designations
1 2 3
Type
Parameter
40V 60V
600V 600V
5VDC
6VDC
24VDC
32VDC
CZLB-5-EX(T2)
CZLB-5-EX(R3)
<3uA <1uA
CZLB-24-EX(B2)
CZLB-24-EX(B3)
CZLB - □ - □ (□ □)
CZLB s eries
2:2-Wire
3 : 3-Wire
Operating voltage
Blank:General type
B:Transmitters
R:Thermocouples
T : Communication s ignals
EX:Instrinsic safety type
Dimensions
SPD Protected
device
Earthing system
Note:Put the line to connect SPD grounding and the protected
equipment shell,then If the protected equipment without a grounding
end, only make the surge protective devices connected to earth
2
ground. The grounding wire should adopt the diameter of 2.5mm
cable.When you connected to grounding by terminal or the mounting
rail,the grounding wire should adopt the diameter of cable.
2
4~6mm
National Quality Supervision and Inspection Center for Products of
Process Automation Instrumentation
Cerfication standards:
GB/T 20438.1(IEC 61508-1)
GB/T 20438.2(IEC 61508-2)
GB/T 18802.21(IEC 61643-21)
Functional safety level:SIL3
Safety cerfication
Summarize
(1).Easy replacement of protection modules.
(2).Space-saving :case width of only 7.6mm.
(3).Earthing via DIN Rail to simplify field wiring.
CZLB-EX series SPD is mainly used to protect the transmitters、switches、
frequency signal、communication equipments、DC power supply,etc. Two-
part design comprising a base part and a protection module.
Features:
Rated discharge current
Max. discharge current Imax:
Resistance per path:
Voltage bandwith (-0.5dB)
Max.operating current IL:
Response time:
Ambient temperature
Relative humidity
Dimensions(L x W x H)
Connections
Max.sectional area
Installation
Test standards
In:
Total discharge current Itotal:
:
:
:
:
:
:
:
:
5kA(
20kA(8/20us)
-40℃ ~+85℃
10%~90%
92.4mm×7.6mm×97.7mm
2.5mm
DIN 35mm
GB/T 18802.21
IEC 61643-21
Shanghai lightning protection
centre
8/20us)
10kA(8/20us)
1Ω/line
10MHz
250mA
<1ns
Screw connection
2
Lightning protection performance test:
Typical application
97.7mm
92.4mm
35.0mm
7. 6 m m
6
1
2
4
5
3
Function principle diagram
Input
Output
DIN rail
4
5
1
2
1
2
3
4
5
6
DIN rail
EX-standards:
Ex ia IIC T4~T6 Ga
Cerfication standards:
GB3836.1-2010(IEC 60079-0)
GB3836.4 -2010(IEC 60079-11)
Explosion-proof parameters:Ci≈0uF Li≈0mH
Explosion-proof parameters
Nati o n a l Supe r v i sion a n d I n spec t i o n Cent e r f o r Exp l o s i on
Protection and Safety of Instrumentation(NEPSI).
Ui=6V(CZLB-5-EX)
T4
Pi=1.3W(-40°C~+40°C)
Pi=1.0W(-40°C~+60°C)
T5
Pi=1.2W(-40°C~+60°C)
T6
Pi=1.0W(-40°C~+60°C)
li=250mA
Ii=100mA
GYB12.1381X
GYB12.1383X
Ui=29V(CZLB-24-EX)
Output
Input
Surge
Terminal or the mounting rail
DIN rail
Protected device
CZLB-□X( 2□-E □ ) CZLB □X( 2- □-E □ )
Protected device
Hazardous area Safe area
DCS
PLC
PCS
FGS
ESD
1
2
4
5
SPD
4
5
1
2
SPD
DCS
PLC
PCS
FGS
ESD
5
6
4
2
3
1
SPD 2
3
1
5
6
4
SPD
Equipotential bonding(if required)
Equipotential bonding(if required)
DIN rail
CZLB □X( 3- □-E □ )
Protected device
CZLB □X( 3- □-E □ )
Protected device
DIN rail DIN rail
Isola tor
barri er
Isola tor
barri er