Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers -ZW, -HV/-HVG, -DATA are fitted with Zoneworks communications modules
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning thesupplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Un-commissioned
With network connectivity
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Un-commissioned
Without network connectivity
Batt plugged-in: yellow 250mS,
green 250mS, yellow 250mS, green
250mS, green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
Emergency Light Test In Progress
LED flashes at yellow 5s , 0ff 1s
Emergency Light Test In Progress
LED flashes at yellow 1s , 0ff 1s
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitateconnection
and integration to 3rd Party Lighting ControlSystems. Before installing the -DALI luminaire, please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
Commissioned/ Un-commissioned
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
Lamp and Status LED Flash for 30 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Argonaut PRO Weatherproof Emergency LED Batten
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
Website: www.clevertronics.com.au
Email: info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
New Zealand
Phone: +64 800 548 448
Designed in Australia to comply with the requirements
of AS/NZS2293.3: 2018, AS CISPR 15: 2017
Models: ARGOPRO-600-xx-L10POD-zz
NOTE: Standard product codes with this symbol are enabled with Clevertest Plus capability.
Please refer to the operation guide supplied with the product for details.
Replacement Emergency LED Board
Replacement 240V Driver (-SEN version only)
Replacement 240V Driver (-DD version only)
Replacement Emergency Driver
Replacement Emergency Driver (-SEN, -HV only)
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
Note: This luminaire (with reinforced insulation between control/LED terminal and AC Supply) contains non-
user replaceable light source and battery –to be replaced (if required, refer installation instructions for
battery replacement) by the manufacturer or his service agent or a similar qualified person.