Comelit 41CPE012EN User manual

Attention:
This manual contains information on limitations regarding product use and function and information
on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
The information in this manual is a subject to change without notice!
ATENA EASY
41CPE012EN
METALLIC ADDRESSABLE PANEL
INSTALLATION MANUAL

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
2
Table of Contents
1. INTRODUCTION ...........................................................................................................................................................4
1.1. General Description.......................................................................................................................................4
1.2. General Specifications...................................................................................................................................4
1.2.1 General Technical Specifications ...................................................................................................4
1.2.2 Possible Hardware Configurations .................................................................................................5
1.2.3 Environment....................................................................................................................................5
1.2.4 Electrical Characteristics ................................................................................................................5
2. INSTALLATION.............................................................................................................................................................7
2.1. Wall Mounting................................................................................................................................................7
2.2. System Components .....................................................................................................................................8
2.2.1 Front panel......................................................................................................................................8
2.2.2 Configuration of the basic modules ..............................................................................................10
2.2.3 Description of the main PCB (control panel) ................................................................................10
2.3. Connection of Signaling Devices.................................................................................................................12
2.3.1 Connecting of Sounders...............................................................................................................12
2.3.2 Connecting of Signaling Devices..................................................................................................12
2.3.3 Connecting to the Specialized Inputs...........................................................................................12
2.3.4 Loop Controller.............................................................................................................................13
2.4. Connecting to the Main Power Source........................................................................................................14
2.5. Connecting the Accumulator Battery...........................................................................................................14
2.6. Connecting a Heat Printer ...........................................................................................................................15
2.7. Connecting a Network Module.....................................................................................................................15
3. PROGRAMMING TYPES............................................................................................................................................16
3.1. Programming via AtenaProg Software ........................................................................................................16
3.2. Programming via Panel’s Keyboard ............................................................................................................16
3.3. Firmware Update .........................................................................................................................................16
3.3.1 Firmware Update from Computer.................................................................................................16
3.3.2 Firmware Update from USB Drive................................................................................................17
3.3.3 Copying Image File from the Panel to USB Drive........................................................................17
4. FULL HARDWARE RESET ........................................................................................................................................17
5. PROGRAMMING OF ATENA EASY FIRE ALARM PANEL......................................................................................18
5.1. General Information for Programming and Operation.................................................................................18
5.2. Codes and Access Levels ...........................................................................................................................18
6. DESCRIPTION OF THE OPERATION MODES .........................................................................................................20
6.1. Review of Alarm Events...............................................................................................................................20
6.2. Review of Fault Events................................................................................................................................20
6.3. Review of Disablements..............................................................................................................................21
6.4. Review of Running Tests.............................................................................................................................21
6.5. Review of Warning Messages.....................................................................................................................22
6.6. Silencing the Internal Buzzer.......................................................................................................................23
6.7. Silencing the Sounders................................................................................................................................23
6.8. Activate Evacuation.....................................................................................................................................23
6.9. Resetting the Panel .....................................................................................................................................23
6.10. Indication Test ...........................................................................................................................................23
7. DESCRIPTION OF THE PROGRAMMING MENUS...................................................................................................24
7.1. View History Log Menu................................................................................................................................24
7.1.1 Review of Full Events List ............................................................................................................24
7.1.2 Review of List of Events by Date..................................................................................................25
7.1.3 Deleting the Events in the LOG file ..............................................................................................25
7.1.4 Printing Events..............................................................................................................................25
7.1.5 Printer Settings .............................................................................................................................25
7.2. Zones Menu.................................................................................................................................................26
7.2.1 General Submenus.......................................................................................................................26
7.2.2 Zones Testing...............................................................................................................................26
7.2.3 Disabling Zones............................................................................................................................27
7.2.4 Programming Zone Parameters...................................................................................................27
7.2.5 Zone Name...................................................................................................................................27
7.2.6 Zone Operation Modes.................................................................................................................27
7.2.7 Programming Delays Т2...............................................................................................................28
7.2.8 Arranging Zones in Groups ..........................................................................................................29
7.3. Devices Setup Menus..................................................................................................................................29
7.3.1 Submenus for General Setting .....................................................................................................29

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
3
7.3.2 Saving the New Found Devices ...................................................................................................30
7.3.3 Deleting Devices...........................................................................................................................30
7.3.4 Disabling Devices .........................................................................................................................30
7.3.5 Fixing of Wrong Type Devices......................................................................................................31
7.3.6 Programming of Device Parameters ............................................................................................31
7.4. Addressing Menus.......................................................................................................................................39
7.4.1 Set Address ..................................................................................................................................40
7.4.2 Change Address...........................................................................................................................40
7.4.3 Self-Addressing ............................................................................................................................40
7.5. Panel Outputs Menus..................................................................................................................................41
7.5.1 Sounders Outputs.........................................................................................................................42
7.5.2 Extinguishing Output.....................................................................................................................42
7.5.3 Fire Output....................................................................................................................................42
7.5.4 Fault Output..................................................................................................................................43
7.5.5 Relay Outputs...............................................................................................................................43
7.6. General Settings Menu................................................................................................................................43
7.6.1 Access Codes...............................................................................................................................44
7.6.2 Setting the Date and Time............................................................................................................45
7.6.3 Setting Day/ Night Alarm Modes ..................................................................................................45
7.6.4 Panel General Settings.................................................................................................................46
7.6.5 Delay Т1 .......................................................................................................................................46
7.6.6 Sounders Mode ............................................................................................................................46
7.6.7 Company Logo .............................................................................................................................47
7.7. Save Configuration Menu............................................................................................................................48
7.8. Restore Defaults Menu................................................................................................................................48
7.9. Software Revision........................................................................................................................................48
7.10. Network......................................................................................................................................................48
7.10.1 Network Settings.........................................................................................................................48
7.10.2 Panels Settings...........................................................................................................................49
7.11. Active Isolators Menu ................................................................................................................................49
7.12. Access Level 1...........................................................................................................................................49
APPENDIX А...................................................................................................................................................................50
APPENDIX B...................................................................................................................................................................52
APPENDIX C...................................................................................................................................................................52
APPENDIX D...................................................................................................................................................................53
APPENDIX E ...................................................................................................................................................................54
DoP No: 002
Comelit Group S.p.A.
Via Don Arrigoni 5 - 24020 Rovetta S. Lorenzo BG Italy tel. +39 0346 750 011 - fax +39 0346 71436 email:
EN 54-2:1997/A1:2006/AC:1999; EN 54-4:1997/A2:2006/AC:1999
41CPE012EN
Intended for use in fire detection and fire alarm systems in and around buildings.
Essential Characteristics
Performance
Performance under fire conditions
Pass
Response delay (response time to fire)
Pass
Operational reliability
Pass
Durability of operational reliability and response delay: temperature resistance
Pass
Durability of operational reliability: humidity resistance
Pass
Durability of operational reliability: vibration resistance
Pass
Durability of operational reliability: electrical resistance
Pass

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
4
1. INTRODUCTION
1.1. General Description
Atena Easy is an addressable fire panel with maximum coverage of 48 zones and up to 2 loops. The panel supports
communication protocol Comelit and operation with Comelit addressable device series.
Every Loop provides up to 250 devices (detectors and modules, regardless of the type).
An arbitrary number of devices can be added to each zone thus ensuring the easy adaptation of the system to any type
of configuration.
To avoid or significantly diminish problems when mounting the system it must be carefully planned prior to installation.
This includes: setting an address for every device and planning a name of maximum 40 digits (including the
spaces) for each address, thereby ensuring easy access to the device.
According to the acting standards for establishing fire systems and the plan of the building, the devices must
be grouped in zones.
1.2. General Specifications
The front panel consists of LCD module (4 rows x 40 symbols), functional buttons and system status LED indication.
Separate access level passwords provide access to the functions of the panel.
The fire alarm panel is designed on module structure as in the metal cabinet there are provided additional places for
mounting of a second loop controller for Loop 2 (Loop 1 is built-in the main PCB), a communication module and
redundant network module.
The panel has a built-in real time clock and calendar, allowing day and night time modes of work.
Switching over between the two modes can be automatic or manual. Events like FIRE, RESET, FAULT, etc., are saved
in the memory, thereby creating an event log-file. It contains the time and date, the address of the device, the name of
the device, the zone number, the name of the zone, etc.
1.2.1 General Technical Specifications
Loops - 1 to 2:
oLoop 1 is built-in in the main board
oLoop 2 –optional, separately mounted to the main control panel
Number of loop devices:
oUp to 250 devices (modules and/ or detectors regardless of the type) for every loop (max. 500 for the
entire system)
48 operation zones (Note: Zone numbers 17-48 do not cover the requirements of EN54-2/4. There is no LED
indication for the status of zones 17-48 on the front panel.)

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
5
9 groups for zones’ organization
5 monitored potential outputs:
oSND1 (Sounder 1)
oSND2 (Sounder 2)
oFIRE
oFAULT (The output is deactivated in case of fault event.)
oEXT (Extinguishing/ Fire Protection –An output for sending an fire alarm signal to automatic fire
extinguishing system)
3 specialized inputs:
oIn AmC* (Input Alarm Confirmation)
oIn PC* (Input Protection Alarm Confirmation)
oIn FP* (Input Fault Protection Panel)
* Covers the requirements on standard VdS 2540
4 non-monitored, programmable relay outputs with parameters: 15A@24VDC
Display –letter and digits LCD module (4 rows х 40 symbols)
Built-in real time clock, supported from integrated lithium battery - 3V, CR3032 type
Memory log file for up to 10000 system events
Comprehensive day/night mode facility
2 Steps of alarm levels (T1 and T2)
Supports external thermo printer
Multilanguage support for operation menus
Easy software update via computer or USB drive
Designed according the requirements of EN54-2/4
Metal box cabinet for wall mounting: bottom (306х412х81mm) and cover (310х416mm)
1.2.2 Possible Hardware Configurations
Minimal Configuration
oControl panel (main PCB with one built-in loop controller)
oIndication (indication PCB with mounted LCD module)
oPower supply source
Maximal Configuration
oControl panel (main PCB with one built-in loop controller)
oIndication (indicator PCB with mounted LCD module)
oPower supply source
oLoop controller (for the second loop)
oCommunication module
oRS485 Redundant Network controller
1.2.3 Environment
Degree of protection: IP30
Operation temperature: -5ºС up to +40ºC
Relative humidity: до 95% (without condense)
Storage temperature: -10ºС up to +60ºC
Weight (without the battery): ~ 4.2 kg.
1.2.4 Electrical Characteristics
Earth Connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total resistance in
the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle input of the fire panel
terminal –see also item 2.4 Main power connection.
ATTENTION: Do not instal the fire panel near power electromagnetic fields (radio equipment,
electric motors, etc.)!

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
6
Main power supply
In normal operating conditions, the fire panel is powered from the mains voltage line. In case of mains voltage line loss
the fire panel is equipped with one rechargeable battery. The characteristics of the main power supply are as follows:
Main power supply: 90 264 VAC
Frequency: 47 440 Hz
Electrical output: 4.2 А
Backup (accumulator) power supply
Voltage output (U): 13,65V
Accumulator battery: 1 x 12V / 18Ah, sealed lead-acid type rechargeable battery
Internal resistance of the accumulator battery Ri: < 0.3Ω
Max. dimensions of the accumulator battery: 167х181х76mm
Type of the battery connection: with a cable lug, Ø5mm (M5) or cable shoe (according the type of the battery
terminals)
Loading capacity
Max. loading capacity of one loop: 500 mA DC
Max. loading capacity of AUX output: 500 mA DC
Max. loading capacity of outputs SND1 and SND2: 500 mA DC
Max. loading capacity of outputs FIRE, FAULT and EXT: 300 mA DC
Max. total loading capacity (sum of the four mentioned above): 2.0 A DC
Programmable relay outputs: 15A@24VDC
Consumption
From the main power supply in standby mode:
oFor a minimum configuration: 60 mA AC
oWith mounted second loop controller: 65 mA AC
From the backup power supply in FAULT mode and generated message ‘AC loss’:
oFor a minimum configuration: 125 mA DC
oWith mounted second loop controller: 213 mA DC
List of the used fuses
Main power supply: 4А, Т type, glass time-delay fuse, size 5х20mm
AUX output: 0,5А, PTC type, resettable fuse
Outputs: 0.3А, PTC type, resettable fuse
Accumulator: 7.0А, PTC type, resettable fuse
List of spare parts kit:
1
Resistor 10k ± 5%, 0.25W
6 pcs
2
Resistor 47k ± 5%, 0.25W
4 pcs
3
Resistor 20k ± 5%, 0.25W
3 pcs
4
Screw 4.2х38, cross slot DIN7981
4 pcs
5
Anchor 6х30mm
4 pcs
6
Fuse 4А, glass time-delay type 5x20mm
(for the power supply)
4 pcs
ATTENTION!
Qualified specialists only should install the panel.
The electronic components of the panel are vulnerable to electrostatic discharge.
Never add or turn off components which are being power supplied!

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
7
2. INSTALLATION
2.1. Wall Mounting
• The panel must be installed in a clean dry place and must not be subjected to impact or vibrations (Figure 1). It must
be situated far from heating appliances. The temperature must be within -5ºС and + 50ºC. The fire panel is not
waterproof!
• Unpack the panel and observe for visible damages due to bad transport or incorrect storing.
• Open the front cover and disconnect the flat indication cable and the earthling point (Figure 2).
Figure 1 Figure 2
•Remove the front cover as dismount the side hinges (Figure 3).
Figure 3
• Choose inlets for the main power supply cable, loops, sounders, control devices, etc. Remove the metal cap element
just from those holes for cable running (Figure 4).
Figure 4 –Elements of the metal bottom:
а) View from above;
b) Front view;
c) View from below.
1 –Main mounting holes.
2 –Holes for cable running.
3 –Holes for main power supply cable running, protected with a metal cap
element.
4 –Additional holes for cable running, protected with a metal cap element.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
8
•Use the template in the set to fix the mounting holes of the metal box on the wall.
•Drill holes (suitable for anchors Ø6mm) on the wall and fix the metal box.
• Route the external cables onto the back box, make off connection glands etc., BUT DO NOT make any connections
at this stage. ENTER THE MAINS CABLE THROUGH ITS OWN CABLE ENTRY POINT AND KEEP MAINS WIRING
AWAY FROM SYSTEM AND OTHER LOW VOLTAGE WIRING.
• Connect the mains supply and earth to the power supply terminal (see Figure 16), BUT DO NOT apply the main
electrical supply at this stage.
• Place the battery in an upright position.
• Mount the front cover back to the bottom as mount the hinges in the reverse order of that described on Figure 3.
• Connect back the flat cable for the indication and the earthling point (Figure 2).
• Proceed with initial power up of the system and testing.
• When you finish with power up and testing steps and the panel is normal operation mode you must fix the front cover
to the bottom with the two screws from the spare parts kit.
2.2. System Components
2.2.1 Front panel
Description of the front panel elements:
1 –LED indication for the system status. The
descriptions are printed on the paper label and
can be changed if needed, including for
language change. The paper label is placed in a
special opening on the inner side of the indicator
PCB, over the flat cable for the indication.
2 –LED indication for the used zones
3 –Letters and digits LCD-module (4х40)
4 –Functional digits buttons
5 –Control and navigation buttons
Figure 5
1 –Description of system status LED indication:
LED
Indication/ Description
GENERAL FIRE (red)
Lights on permanently in case of fire alarm event –fire alarm signal from an
automatic or manual call point, or other auxiliary device connected to a panel
input.
GENERAL FAULT (yellow)
Lights on permanently in case of fault event in the system.
SYSTEM FAULT (yellow)
CPU FAULT. Lights on permanently in case of main microprocessor fault.
DELAY (yellow)
Lights on permanently in daytime mode and set time delay for one or several
outputs.
DISABLE (yellow)
Light on permanently in active disablement in the system.
TEST (yellow)
Light on permanently in system test mode.
SOUNDERS FAULT/ DISABLED
(yellow)
The LED will be active in case of fault or disablement of the sounders circuits.
The indication is as follows:
- Blinking in case of fault event in the sounder circuits.
- Lighting on when the sounder circuits are disabled.
FIRE CONFIRMED (yellow)
FIRE ALARM CONFIRMATION. Lights on permanently in activation of the
specialized “In AmC”input –see the description on page 12.
FIRE OUTPUT FAULT/
DISABLED (yellow)
The LED will be active in case of fault or disablement of the FIRE relay output.
The indication is as follows:
- Blinking in case of fault event.
- Lighting on when the output is disabled.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
9
PROTECTION CONFIRMED
(yellow)
EXTINGUISHING STARTED CONFIRMATION. Lights on permanently in
activation of the specialized “In PC” input –see the description on page 12.
PROTECTION PANEL FAULT
(yellow)
EXTINGUISHING SYSTEM FAULT. Lights on permanently in activation of the
specialized “In FP” input –see the description on page 12.
POWER ON (green)
MAIN POWER SUPPLY ON. Lights on permanently in presence of 230V main
power supply.
SILENCE ALARM (yellow)
THE SOUNDERS ARE SILENCED. Lights on permanently when the sounders
are silenced (the LED is situated next to the button).
2 –Description of the zone LED indication:
LED
Indication/ Description
Zone indicators (red)
1 - 16
FIRE IN A ZONE. Lights on permanently in case of fire alarm in zones 1-16.
Blinking when zones 1-16 are in test mode.
Note: For zones from 17 to 48 there is no LED indication.
3 –Description of the LCD-module
The Atena Easy fire alarm addressable panel is equipped with letter-digit LCD-module (4 rows x 40 symbols). The user
can enter device and zone names using the navigation and control buttons. The display has an adjustable backlight
with 20 levels of intensity.
4 –Description of the functional digit buttons:
Button
Description
Functional digit buttons
1 - 4
The buttons are active at access levels 2 and 3, and have the following meaning:
- Introducing of access codes.
- Functional submenu entry.
- Changing of value or parameter status.
5 –Description of control and navigation buttons:
Button
Action
Description
Silence Buzzer
The button is active at access levels 1, 2 and 3. The button functionality is
deactivation of the internal buzzer.
Silence
Sounders
The button is active at access levels 2 and 3. The button functionality is
deactivation of the sounders in case of fire alarm event. After pressing the button
the LED next to it is lighting in yellow.
Reset
The button is active at access levels 2 and 3. The button functionality is resetting
the panel without switching off the main power supply.
Evacuation
The button is active at access levels 1*, 2 and 3. The button immediately activates
the sounders –the sounder delay is ignored if present.
* In case of fire alarm event in a zone and set sounder delay.
Buzzer and LED
general test
The button will activate all LEDs on the front panel –for events and zones, as and
the internal buzzer. The next pressing of the button deactivates the test.
ENTER
(Confirmation)
The button is active at access levels 1, 2 and 3. Use the button to confirm the
entered values and parameters; in the devices and zones menus use the button to
enter in a submenu for name and status changing.
CANCEL
(Rejection)
The button is active at access levels 1, 2 and 3. Use the button to reject the entered
values and parameters; one step back to the previous menu.
Navigation
buttons
The button is active at access levels 2 and 3. Use the arrows to scroll over the
menus; in the programming menus the buttons has a specific function for changing
values and switching between the editable fields.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
10
2.2.2 Configuration of the basic modules
Figure 6 –Configuration of the modules in the box:
1 –Main PCB (control panel)
2 –Second loop controller (optional, it may not be present in your
system configuration)
3 –Power supply unit
4 –Terminal 230V for connection of the main power supply cable
5 –Place for accumulator battery, 1 х 12V/ 18Ah
6 –Place for mounting of a communication module
7 –Place for mounting of redundant network module
2.2.3 Description of the main PCB (control panel)
Figure 7 –Main PCB of the Atena Easy fire alarm panel
Description of the terminal row (left to right):
RELAY 1 - 4 –Programmable volt free change over relay contacts each, 24VDC@15A. Each relay has one
NO (normal open) and one NC (normal closed) contact with common lead on a terminal. When a relay output
is activated the NO contact is closed and the NC contact is opened.
FAULT –Potential, monitored output for connection of auxiliary devices, 24 VDC/ 0.3А. This output is
deactivated in case of system trouble or fault.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
11
EXT - Potential, monitored output for fire extinguishing, 24 VDC/ 0.3А. This output is activated in case of a fire
alarm condition.
FIRE –Potential, monitored output for connection of auxiliary devices (signaling devices for example), 24 VDC/
0.3А. This output is activated in case of fire in the premises.
AUX –Potential output for power supply of auxiliary devices, 24 VDC/ 0.5А.
SND 1, SND 2 –Potential, monitored outputs for connecting sounders, 24 VDC/ 0.5А.
IN PC (Input Protection Alarm Confirmation) –Input for monitoring of signal “Confirmation for extinguishing
started in the site”sent by extinguishing control panel.
IN FP (Input Fault Protection Panel) –Input for monitoring of signal “Fault”sent by extinguishing control panel.
IN AmC (Input AlarmConfirmation) –Input for monitoring of signal “Alarm confirmation”sent by extinguishing
control panel.
LOOP 1 (-LOOP+ / +ERT / -LOOP+) –Terminal row for connecting Loop 1 in the system.
LOOP 2 –Interface connector for adding Atena Easy loop (for Loop 2) in the system configuration.
INDICATION –Interface connection for the indication module.
POWER –Interface connection for the main power supply unit.
JP7 –Jumper for enable/ disable the built-in battery for supporting the real time clock in case of main and
backup power supply failure.
PRINTER - RS232 interface connector for heat-printer.
USB UTG –Micro USB A/B connector for firmware update of the main microprocessor via PC or USB flash
drive; suitable also for programming via AtenaProg software.
BATT –Connector with wires (red and black) for connection to the accumulator battery. The type of connection
is according the battery terminals –to every cable shoe is added a separate cable lug connector Ø5mm (M5).
Restore Defaults –Jumper for full hardware reset of the panel and restoring the factory default settings.
Earth Fault –Jumper for enable/disable indication for earth fault.
Example: If you want to enable the earth fault indication set a jumper on Earth Fault terminals.
NET –Interface connector for a redundant network module to the system configuration.
Ajax–Interface connector for adding of a communication module to the system configuration.
Fuses:
AUX –0.5А, PTC type, resettable
FAULT, EXT, FIRE –0.3A, PTC type, resettable
BATT –7A, PTC type, resettable
LED indication:
LED 1 (red) –Indication for scanning the devices connected to Loop1. In normal operation mode the LED
lights on continuously in 10 seconds intervals.
LED 2 (green) –Indication for data transfer between the main microprocessor of the panel and the controller
for Loop 1. In normal operation mode is constantly blinking.
Temperature sensor:
The temperature sensor is used for measurement of the battery temperature. The sensor is mounted at the end of the
wires couple, factory connected to “Temperature sensor” terminal on the panel’s PCB.
The temperature sensor should be placed behind or under the accumulator battery.
Figure 8 –Internal structure
of relay output
Figure 9 –Connection to the
loop controller

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
12
2.3. Connection of Signaling Devices
The monitored outputs SND, at activation, provide 24VDC@0,5A to the load connected between
them and GND*.
The monitored outputs FAULT, EXT and FIRE, provide 24VDC@0,3A to the load connected
between them and GND*.
It is necessary to connect in parallel to the last device in the loop a 10k terminate resistor,
so to ensure that the panel is able to detect any break or short circuit in the loop –see Figures 10
and 11!
*The grounding point of the panel.
2.3.1 Connecting of Sounders
To every monitored output SND could be connected several sounders - Figure 10. The maximum number of sounders
that could be connected in the circuit depends on their total current consumption, which must not exceed 0,5A.
Before connecting the last sounder in the circuit, parallel to it must be added resistor 10k.
Figure 10 –Connecting sounders to SND output
2.3.2 Connecting of Signaling Devices
To every monitored output FAULT, EXT and FIRE could be connected signaling and other control devices –Figure 11.
The maximal consumption of the devices should not exceed 0.3А.
Before connecting the last device in the circuit, parallel to it must be added resistor 10k.
Figure 11 –Example for connecting of end device (an illuminated exit sign) to the Monitored FIRE Output.
2.3.3 Connecting to the Specialized Inputs
The specialized inputs of Atena Easy fire alarm panel are designed for operation with an extinguishing control panel.
The example connection diagrams are presented on Figures 12 а) and b).
Figure 12 –Examples of connections to the specialized input IN XX
Sounder 1
Sounder 2
Sounder N
а) Connecting diagram of relay
contact to the input
b) Connecting diagram of open
collector to the input

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
13
2.3.4 Loop Controller
The Atena Easy fire alarm panel supports operation with the loop controller via communication protocol.
The Loop Controller realizes the connection between the I/O Module and devices connected to the communication
line. The Loop Expander has two basic functions:
Gathers data from the devices in the communication line and transfers it to the main microcontroller;
Receives commands from the main microcontroller and transfers them to the devices connected in the
communication line.
Up to 250 Comelit devices can be connected to Atena Easy loop controller. The general connection diagram of
devices to the loop controller is shown on Figure 13.
The maximum current consumption of the devices in the communication line is Imax = 500mA. If the consumption
exceeds this value an over-load protection would be turned on.
Figure 13 –Connecting of detectors to a loop controller
In the configuration of addressable fire alarm panel Atena Easy could be mounted a second loop controller as a
separate module –see Figure 14.
ATTENTION! Do not add or remove loop expanders to the fire panel configuration when
the main and backup power supplies are on!
- Connect the connectors: LOOP 2 of the main control panel and LOOP of the second loop controller.
- Fix the second loop expander to the metal box of the fire panel using the supplied bolts in the spare parts
kit.
LED 1/ LED 2 –LED indication for the loop controller status, analogical to that for the main control panel –see
the description on page 12.
Figure 14 –Adding of second loop controller
Detector 1
Detector 2
Detector N

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
14
2.4. Connecting to the Main Power Source
The mains power supply of Atena Easy fire alarm panel is realized with connection of the main power cable to the
230V terminal, mounted in the metal box under the powers source. The connection between the 230V terminal and the
main power source is done from the manufacturer. The connection of the main power supply cable to the 230V
terminal is shown on Figure 16.
Before the mains supply is switched on, check the correct connection of each loop, sounder or any other input
or output!
Figure 16. Connecting the main power supply cable to the 230V terminal
2.5. Connecting the Accumulator Battery
The accumulator battery leads are mounted on a terminal at the bottom of main control panel. Connect the battery
leads to the accumulator terminal as observe the polarity - see Figure 17.
The battery cannot power up the panel before the mains supply has been switched on!
The charging of the accumulator battery is done at maximum current I = 2A and charging voltage U
≤ 13.65V.
Main
Power
Source
Fuse 4А
Type: glass time-delay
Figure 17. Connecting
the accumulator battery
To control panel
To Datecs printer
To Kafka printer
To control panel
Black
Red
Accumulator
Battery
ATENA EASY
Main Board
Attention: The connection between the
accumulator battery and the main power
source has some special features.
It is strongly recommended to use only battery
with electrical characteristics and dimensions
pointed from the manufacturer.
Before connecting to the power source check
the polarity of the battery. Connect the battery
after the mains supply is turned on.
If the battery is new it will take a few hours
before its complete charging!
To measure the current temperature of the
battery, place the temperature sensor behind
or under the battery.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
15
2.6. Connecting a Heat Printer
The addressable fire alarm panel Atena Easy is equipped with RS232 interface connector, situated in the middle of the
main PCB, for connecting a heat printer. The heat printer allows the technician to print the log file for the alarm and
fault events, warnings and changes during programming. The capacity of log file is 10000 events, which are saved with
date and time of occurring –see also item 7.1.4.
The addressable fire alarm panel Atena Easy supports Canon 9 type external printers, models Kafka and Datecs. For
connecting the Atena Easy panel to the heat printer you have to prepare a special cable for the purpose –connect two
male DB9-DB9 (Datecs printer) or DB9-DIN5 (Kafka printer) type connectors as shown on Figure 18.
Before printing (access levels 2 and 3) make sure that the heat printer is connected to the ‘PRINTER’ interface
connector on the main PCB and the printer is powered on.
2.7. Connecting a Network Module
(supported for Soft. Revision 2.8 and higher)
The addressable fire alarm panel Atena Easy is designed with option for connection in a Ethernet network with other
Atena Easy or Atena addressable panels (up to 32). The network module is mounted under the main PCB and is
connected to ‘NET’ connector – Figure 19. The module should be fixed with screws to the metal bottom. The maximum
cable length between two redundant network modules is 1000m.
Attention: NEVER add or remove the network module to the fire panel configuration WHEN THE
MAIN AND BACKUP POWER SUPPLIES ARE ON!
Figure 18
Figure 19
DB9
DB9
DB9
DIN5
To control panel
To Kafka printer
To control panel
To Datecs printer
Atena Easy
Main Board
Module
Redundant
network

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
16
3. PROGRAMMING TYPES
3.1. Programming via AtenaProg Software
The specialized AtenaProg software is designed for programming of intruder and fire alarm panels produced by
Comelit. To program the fire alarm panel Atena Easy you should first to install the AtenaProg software on your
computer –the program can be downloaded free of charge on Comelit Website.
To program the AtenaProg panel you have to use cable type USB Micro B - USB A –Figure 20.
Figure 20. Programming via AtenaProg software
3.2. Programming via Panel’s Keyboard
The addressable fire alarm panel Atena Easy can be programmed directly using the keyboard on the front panel. The
programming and settings are accessed from levels 2 (Maintenance) and 3 (Installer). The buttons on the front panel
are organized in three main groups
Functional digit buttons –used for entry in submenus, changing parameter status, entering of new combination
for Maintenance and Installer access codes.
Navigation buttons –arrows for moving the cursor on the screen and switching over the editable fields,
confirmation of entered parameters, cancelation of entered parameters and step back in the menu
programming structure.
Specialized buttons for User operation –Silence buzzer, Silence sounders, Reset, Evacuation, General test of
the LEDs, buzzer and screen.
The detailed description of all buttons on the front panel is presented in item 2.2.1 –5, page. 9
The detailed description of Maintenance and Installer programming access levels is presented in item 5.
3.3. Firmware Update
ATTENTION!
The firmware update of the main microprocessor of fire alarm panel Atena Easy should be
performed by qualified personnel only and after held training program by the producer Comelit!
3.3.1 Firmware Update from Computer
To start a firmware update from a computer you should first to have a copy of an image update file (with *.bin
extension) saved on your computer. For firmware updates use the USB_UTG connector on the main PCB:
Connect the panel to the computer using USB cable: Normal A to Micro B type.
Enter access code for level 2 or 3 and choose menu 9) SOFT. REVISION.
Wait for the message from Windows Explorer for found new Removable Disk.
The panel will display automatically on the screen:
USB Host Detected
1. Copy image file to Removable Disk
2. Make Eject at Removable Disk
> Panel is configured

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
17
Use the Windows Explorer file manager to copy the new image update file (with *.bin extension) in Removable
Disk directory.
When the copying of the image file completes, remove the Removable Disk, as select Eject option from its
dialogue box (right click with the mouse over it).
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
3.3.2 Firmware Update from USB Drive
To start a firmware update from a USB drive you should first have to copy the new image update file (with *.bin
extension) in the main directory of the USB removable disk. The name of the file must be short –up to 8 symbols.
Connect the panel to the computer using USB cable: USB Micro А - USB A type.
Enter access code for level 2 or 3 and choose menu 9) SOFT. REVISION.
Connect the USB drive, with the new image file (with *.bin extension).
Notes:
1. The panel will scan the files copied only in the main directory and these files in the first subfolders in the tree
hierarchy of the USB drive.
2. It is obligatory the name of the file to be up to 8 symbols long.
Wait until the polling procedure is complete - USB drive will be displayed with its name and manufacturer. On
the last row of the screen will start blinking the notice Push 'Enter' to continue.
Press Enter button and wait for a message for the USB drive capacity. On the last row of the screen will be
active two buttons (2) To Panel and (3) From Panel.
Press (2) To Panel button. A list with the present image files (with *.bin extension) copied to USB drive is
displayed on the screen, as the software revision is displayed on the right side, for example:
0:/AtenaEasy/AtenaEasy2_0.BIN v 2.00
Scroll through the listed files using the buttons with up and down arrows –the currently selected file is blinking.
Select the file and press Enter button.
The panel starts uploading the file from the USB drive to the external Flash memory of the panel. The running
process is displayed with a progress bar.
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
3.3.3 Copying Image File from the Panel to USB Drive
Connect the panel to the computer using USB cable: USB Micro B - USB A type.
Enter access code for level 2 or 3 and choose menu 9) SOFT. REVISION.
Connect the USB drive.
Wait until the polling procedure is complete - USB drive will be displayed with its name and manufacturer. On
the last row of the screen will start blinking the notice Push 'Enter' to continue.
Press Enter button and wait for a message for the USB drive capacity. On the last row of the screen will be
active two buttons (2) To Panel and (3) From Panel.
Press (3) From Panel button –the panel will download a copy of its own image file to the USB drive and saves
the file in Atena Easy folder.
4. FULL HARDWARE RESET
The full hardware reset of Atena Easy addressable fire alarm panel allows the engineer to restore all factory settings
and access code combinations for level 2 (Maintenance) and 3 (Installer).
To perform full hardware reset, follow the steps:
1. Disconnect the mains and backup power supplies.
2. Set a jumper on ‘RESTORE DEFAULTS’ terminal on the PCB.
3. Connect mains and after that the backup power supply.
4. Wait the procedure for initialization to complete.
5. Remove the jumper from ‘RESTORE DEFAULTS’ terminal.
6. Proceed with save system configuration and other settings.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
18
5. PROGRAMMING OF ATENA EASY FIRE ALARM PANEL
5.1. General Information for Programming and Operation
Addressable fire alarm panel Atena Easy can be programmed directly through the navigation and functional digit
buttons on the front panel. The programming menus are organized in a text tree-structure and are viewed on the LCD-
display (4 rows x 40 symbols). The access to the programming menus is organized in three levels –see items 5.2.
When turned on, the panel always conducts a procedure of loading the parameters, which usually takes about 5-6 sec.
There is no access to the menus of the panel during that procedure.
Upon the initial startup, the panel does not hold any configurations. Initialization may take several minutes. The
initialization time needed depends on the number of periphery and loop devices –for Loop 1 and Loop 2. After the
panel has been turned on, it performs a procedure for detecting newly installed loop devices –see also APPENDIX C,
page 48.
During the procedure the symbol “ ” is blinking in the up right corner of the screen. This symbol will appear always
when running similar procedures like resetting of devices or recognized new devices connected to the loop.
Right after the initial startup of the mains power supply and initialization completed the panel turns to normal operation
mode. If there are any active alarm and fault messages they are displayed on the screen, as the indication follows the
priority:
Indication - Groups
Priority
ALARMS
The highest
FAULTS
High
DISABLED
Normal
TESTS
Normal
WARNINGS
Low
The name of the current active indication group is blinking together with the number of the first message. Press the
ENTER button to review some additional information for the respective message as data and time of occurring, device
address, zone number or other, according the trouble type.
The indication for the active ALARMS in the system is viewed with highest priority.
The addressable fire alarm panel Atena Easy supports different languages for the programming menus.
The factory default setting of the language is in English. You can change the language after the initial power-
up as enter in sequence:
Press CANCEL –enter code 3333 –select menu 6) GENERAL SETTINGS –menu 6.4) PANEL SETTINGS –
Button 1 –Button ENTER
Use the ENTER button to enter in programming menus and confirmation of entered values and
parameters; the functional digit buttons are used for entering of access codes and changing the
current status; the navigation buttons (up/ down and left/ right arrows) are used for scrolling
through the menus and for changing the editing field.
5.2. Codes and Access Levels
There are three access levels in Atena Easy panel: User, Maintenance and Installer. Every level comprises different
functions and operations. To enter Maintenance and Installer levels is necessary to enter valid access code:
Level
Description
Code
Combination
Access
1
User
-
Only Silence buzzer and Evacuation* buttons are active. It is not allowed to
enter Maintenance and Programming access levels.
* Just for that cases, when the fire alarm signal is received from a device
2
Maintenance
2222
Silence buzzer, Silence sounders, Reset and Evacuation buttons are active.
Maintenance access level entry, which allows partial programming and menu
settings.
3
Installer
3333
Silence buzzer, Silence sounders, Reset and Evacuation buttons are active.
Installer access level entry, which allows full programming and settings.
The introduced code combinations are visualized with “ “ symbol. The entry is automatic.

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
19
The access codes could be changed only from level Installer - menu 6) General Settings - submenu 6.1) Access
codes. There are different restrictions on the panel functions in the relative access levels, which are shown in the
following table:
Mode/ Menu
Description
Access Level
1
2
3
Operation modes
ALARMS
Viewing the Alarms Messages in the system.
FAULTS
Viewing the Faults Messages in the system.
DISABLED
Viewing the active disablements in the system.
TESTS
Viewing the running tests in the system.
WARNINGS
Viewing the Warnings Messages in the system.
Silence buzzer
Deactivating Internal Buzzer.
Silence Sounders
Deactivating the Sounders.
During active fire alarms and deactivated/ silenced
sounders the LED next the button is lighting up.
Reset
Resetting the panel without switching off the main and
backup power supplies.
Evacuation
Activating Evacuation alarm signal; the sounders will
activate immediately overriding all introduced delays.
*
Test
General test for operability of all LEDs and internal buzzer.
Programming menus
View history LOG
Viewing the LOG file for all events; printing of all or
separate events; clear the log file.
Zones
Zones status; setting a zone name; parameter
programming; zone test for operability.
Devices Setup
Setting a device name; parameter programming.
Addressing:
Menus for addressing devices.
-
Set address
Setting an address for single devices.
Change address
Changing device address.
Self-addressing
Automatic self-addressing mode.
Autoaddressing
Automatic mode for addressing devices by ID or isolator.
Panel outputs
Parameter programming for the built-in panel outputs:
SOUNDERS, EXITING, FIRE, FAULT, RELAY OUTPUTS.
General Settings:
General settings common for the panel.
-
Access codes
Changing the code combinations for levels Maintenance
and Installer; enable/ disable the automatic exit from the
installer programming menus.
Time/ Day
Setting the current time and date.
Day/ Night alarm mode
Setting Day/ Night alarm mode or operation on schedule.
Panel settings
Changing the menu language, setting the backlight
brightness; entering disablements.
Delay Т1
Setting the Delay Т1.
Sounders mode
Programming the operation of SOUNDER outputs.
Company logo
Enter company information for the main screen
Save configuration
Saving the set system configuration.
Restore defaults
Restoring the factory default settings.
Software revision
Reviewing the current software revision.
Network
Setting the redundant network parameters
Active isolators
Reviewing the activated isolators in the system.
Access level 1
Return to Access Level 1.
* Just for those cases, when the fire alarm signal is received from a device.
- The operation modes and the menus are not supported for that access level
- The operation modes and the menus can be reviewed or are allowed for partial programming for that access level

Atena Easy Addressable Fire Alarm Panel –Installation and Programming Manual
20
6. DESCRIPTION OF THE OPERATION MODES
In this section you can find detailed descriptions of all operation modes of Atena Easy addressable fire alarm panel.
The modes for reviewing of system events are accessible only from level 1 without entering access code. If no alarm,
fault or warning messages, active tests and disablements are present, then the panel is in normal operation mode and
only the current day and time is displayed. In case of alarm, fault or warning situation is occurred the panel will display
information and text messages for the events. A list of all types of event messages is presented with details in
APPENDIX A.
6.1. Review of Alarm Events
The messages for alarm events are displayed with the highest priority in the system. In case of alarm in the system the
panel will show a list with active alarms at the moment, and ALARMS mode is blinking together with the number of the
first alarm message. Over the button (1) is displayed the total number of the active alarms. The LED ‘General Fire’
lights on together with the number of the zone in alarm. The panel is signaling with continuous sound signal, which can
be stopped with pressing the ‘Silence buzzer’ button. The activated sounders could be stopped after entering access
level 2 or 3 and pressing the ‘Silence sounders’ button.
Example:
The User can review also some additional information for every of the alarm events. For this, select the number of the
alarm message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button.
On the screen is displayed information for the loop number and the address of the device sensed the alarm event. At
the bottom of the screen is displayed the day and time of occurring of the respective event. Note that the additional
information is different according the type of the alarm event. To exit the review alarm events mode, press CANCEL
button.
6.2. Review of Fault Events
The messages for fault events are displayed with high priority. If no alarm events are present, and there are active
faults in the system, the FAULTS mode is blinking together with the number of the first fault event. The LED ‘General
Fault’ lights on. The faults messages are cleared automatically after the fault condition is restored.
Example:
The User can review also some additional information for every of the faults events. For this, select the number of the
fault message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button.
In case, there are active alarms in the system, but you want to review the fault messages, press button (2) –FAULTS
mode. The present faults in the system are displayed with serial numbers. The reviewing is the same as described in
item 6.1. The total number of active faults is displayed at the bottom right corner of the screen. Use button (1) to go
back to ALARMS mode and reviewing the alarm messages.
To review the FAULTS at active alarms in the system:
To exit the review fault events mode, press CANCEL button.
This manual suits for next models
1
Table of contents
Other Comelit Security System manuals
Popular Security System manuals by other brands

SungJin Techwin Co
SungJin Techwin Co DiSS NetMaster NM-1004 user manual

Texecom
Texecom Premier Elite 8XP-W installation manual

First Alert
First Alert FA148CP Series Quick installation guide

Lorex
Lorex SG21FD3044-161 Software installation

Risco
Risco ProSYS Plus Quick user guide

Ross
Ross MC1-MK quick start guide

ADT
ADT iCenter 8142ADT user guide

Elk
Elk ELK-6030 Installtion and setup guide

Aritech
Aritech AS700G3 Installation sheet

AGCO
AGCO Cumberland Agri-Alert 128 Software update procedure

Safety Track
Safety Track UCIT PRO-4 installation manual

Linear
Linear Security DVS-2400 Installation & programming instructions