
441-622-052 REV 04/23/19 Type 550X Page 8
5. The connection option “A” is suitable for Class I, II, and III, Division 2, Groups A, B, C, D, E, F, and G hazardous (classified)
locations. Dust--tight conduit seal must be used when installed in Class II and Class III environments.
The connection options “D” and “T” are suitable for Class I, Division 2, Groups A, B, C, and D hazardous
(classified) locations.
Transducers to be installed in accordance with the:
(US) National Electrical Code (ANSI--NFPA 70) Division 2 hazardous (classified) location wiring techniques. (Canada) Canadian
Electrical Code
6. The Intrinsic Safety Entity concept allows the interconnection of two FM Approved Intrinsically safe devices with. The linear barriers
parameters must meet the following requirements:
Ui or Vmax > Uo or Voc or Vt > 7.2 volts
Ii or lmax > lo or lsc or lt
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
Pi > Po.
Entity Parameters for: MODELS T550-A*%
Ui (Vmax) = 30 V
li (lmax) = 125 mA
Pi = 0.70 watts
Ci = 0 uF
Li = 0 mH
7. No revision to this drawing is permitted without prior FM Approvals notification.
8. The Intrinsic Safety Entity concept allows the interconnection of two EU-Type certified devices with entity parameters, not
specifically examined in a combination when: Ui > Uo
Ii > lo
Ca > Ci + Ccable
La > Li + Lcable
Pi > Po
9. Because the enclosure is made of aluminum, if it is mounted in an area where the use of category 1G apparatus is required, it must
be installed such that even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
3.3 EU Declaration of Conformity
We,ControlAirLLC
8ColumbiaDrive
Amherst,NH03031
DeclarethattheType550XTransducerfamilytowhichthisdeclarationapplies,complywiththesestandards:
EN50082‐1:1998
EN55011:1999
EN61010‐1:1993includingAMD2:1995
FollowingtheprovisionsofEMCdirective89/336/EEC
EN60079‐0:2006
EN60079‐11:2007
FollowingtheprovisionsofATEXdirective2014/34/EU
Under normal circumstances, no maintenance should be required.
4.1 Instrument Air Filtration
4.1.1 Failures due to instrument supply air contamination are not covered by warranty.
4.1.2 Use of oil and/or water saturated instrument air can cause erratic operation.
4.1.3 Poor quality instrument air can result in unit failure. It is recommended that a filter regulator (such as
ControlAir Type 300) be placed upstream of each unit where oil and/or water laded instrument air is
suspected.
4.1.4 If clean, dry air is not used the orifice can become blocked. To clean, first turn off supply air, then
remove the screw located on the side of the unit above the “out” port. The orifice is a very small hole
on the side of the screw. Unplug the orifice using a wire that has a smaller diameter than 0.012”
(0.30mm). Replace screw tightly into unit.
4. MAINTENANCE AND REPAIRS
NOTE