manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cooper Wheelock
  6. •
  7. Security System
  8. •
  9. Cooper Wheelock NPS-R-031 User manual

Cooper Wheelock NPS-R-031 User manual

This manual suits for next models

1

Other Cooper Wheelock Security System manuals

Cooper Wheelock CLR-DC User manual

Cooper Wheelock

Cooper Wheelock CLR-DC User manual

Cooper Wheelock SERIES AS User manual

Cooper Wheelock

Cooper Wheelock SERIES AS User manual

Cooper Wheelock Series 43T AC Bells User manual

Cooper Wheelock

Cooper Wheelock Series 43T AC Bells User manual

Cooper Wheelock SAFEPATH4 SP40S User manual

Cooper Wheelock

Cooper Wheelock SAFEPATH4 SP40S User manual

Cooper Wheelock Series NPS User manual

Cooper Wheelock

Cooper Wheelock Series NPS User manual

Cooper Wheelock SQA-DC User manual

Cooper Wheelock

Cooper Wheelock SQA-DC User manual

Cooper Wheelock Series NPS User manual

Cooper Wheelock

Cooper Wheelock Series NPS User manual

Cooper Wheelock RSS-24MCWH User manual

Cooper Wheelock

Cooper Wheelock RSS-24MCWH User manual

Cooper Wheelock SM87 Series User manual

Cooper Wheelock

Cooper Wheelock SM87 Series User manual

Cooper Wheelock SAFEPATH SP-SVC User manual

Cooper Wheelock

Cooper Wheelock SAFEPATH SP-SVC User manual

Cooper Wheelock RSSPA-24MCC-NW User manual

Cooper Wheelock

Cooper Wheelock RSSPA-24MCC-NW User manual

Cooper Wheelock SYM-DC User manual

Cooper Wheelock

Cooper Wheelock SYM-DC User manual

Cooper Wheelock ROS-DC User manual

Cooper Wheelock

Cooper Wheelock ROS-DC User manual

Cooper Wheelock SLS-A-DC User manual

Cooper Wheelock

Cooper Wheelock SLS-A-DC User manual

Cooper Wheelock UTA-1 User manual

Cooper Wheelock

Cooper Wheelock UTA-1 User manual

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

ADEMCO VISTA-20P Series Installation and setup guide

ADEMCO

ADEMCO VISTA-20P Series Installation and setup guide

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

P84249 G
Sheet 1 of 3
273 Branchport Avenue
Long Branch, NJ 07740
(800) 631-2148
www.coopernotification.com Thank you for using our products.
INSTALLATION INSTRUCTIONS
PUSH STATION
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL: SERIES NPS
GENERAL:
Multipurpose Push Stations (NPS) for applications that need Normally Open or Normally Closed contacts. The NPS can be used for
manual activation of SAFEPATH and SAFEPATH4 Voice Evacuation Systems prerecorded messages. The NPS can also be used to
manually activate a message in the event of an emergency or for alerting.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
NOTE: Push Stations with the suffix code –039 with the wording “Fire” have not been tested to any UL Standard.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE
TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
WIRING INFORMATION:
Figure 1: Terminal Block
All terminals accept (2) two #12 to #18 American Wire Gauge (AWG).
250VDC - 1 AMP
600VAC - 3 AMPS
WARNING: DO NOT USE THE SERIES NPS PUSH STATIONS IN INSTALLATIONS WHERE TEMPERATURES
MAY FALL OUTSIDE OF THE UL LISTED TEMPERATURE [0˚C (32˚F) TO 49˚C (120˚F)] RANGE AS DAMAGE TO,
OR FAILURE MAY RESULT.
WARNING: FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS OR TO SUBSTITUTE ELECTRICAL
RIGID CONDUIT FITTINGS THAT DO NO COMPLY WITH CURRENT PRACTICES ADAPTED BY NEC, NFPA AND
ANSI CODES MAY RESULT IN LOSS OF PROTECTION FROM WATER OR DUST.
WARNING: IN ALL AREAS WHERE FREQUENT WASH DOWNS OCCUR, STAND OFF BLOCK MUST BE
INSTALLED.
Copyright 2015 Cooper Wheelock Inc., dba Cooper Notification. All rights reserved.
P84249 G
Sheet 2 of 3
FEATURES:
-Available in five colors: Red, Green, Yellow, White
or Blue
-Custom wording available
-Polycarbonate faceplate
-Stainless steel backplate
-UL 2017 listed switch assembly
-ADA Compliant
-Mounts to single-gang electrical backbox.
-Interchangeable or replaceable Normally Open (NO)
and Normally Closed (NC) single pole, single throw
gold plated contact blocks rated for 3 amps @ 600
VAC or 1 amp @ 250 VDC.
-Can be reset by depressing the "Push" button, and
turning clockwise a 1/4 turn.
-Measurements: 5" H x 3-1/4" W x 1-1/2" D.
MOUNTING INSTRUCTIONS:
STATIONLABEL
MOUNTINGSCREW
(SUPPLIED)
PUSH/TURN
RESETBUTTON
STATION HOUSING
GREEN, YELLOW, WHITE,
BLUEORRED
BACKPLATEASSEMBLY
WHEELOCKRECOMMENDSTHE USE OFTHIS
SPACER (NOTPROVIDED) FOR SWITCH CLEARANCE
ONSTANDARDSINGLE GANGBOXES
(2)6-32X 1"SCREWS
(SUPPLIED)
Figure 2: Overview of Assembly
.
Figure 3: Back view of Push Station
NOTE: To provide adequate clearance for installation, one of the following is recommended: Safety Tech. Inc. (STI) #102722
Spacer, or Raco #660 W/1/2" K.O. and Raco #653 Extension Ring. Also Raco #696 Masonry Box.
NOTE: Additional Normally Open, NPS-NO (0523) or Normally Closed, NPS-NC (0524) can be purchased separately.
P84249 G
Sheet 3 of 3
MOUNTING PROCEDURES:
Use this mounting procedure to position the field wires in the backbox so that they use minimum space and produce minimum stress
on the product. This is especially important for stiff, heavy gauge wires and wire with thick insulation or sheathing.
1. Strip 1/4" of wire insulation and insert in terminal block, then using a Phillips screwdriver turn screws clockwise until tightened.
2. Remove screw on bottom of Push Station unit with Allen Wrench included in hardware package.
3. Carefully push terminal block into backplate of Push Station until it snaps in securely.
4. Carefully press Push Station into backbox then screw Push Station into backbox using the (2) #6-32 screws provided in hardware
package.
5. Reattach Push Station to unit and secure with screw provided using Allen Wrench.
MOUNTING NOTES:
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and
conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used.
1. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.
2. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring
space for the signaling appliance.
3. Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result
in insufficient wiring space for the signaling appliance.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER
DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR
ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION
AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY
FOR SUCH USE.