Crestron 4 Series User manual

The ZUM-HUB4 enables centralized management for Zūm® commercial
lighting systems of up to 1,000 rooms with an Ethernet switch (sold
separately) across Zūm wired, Zūm wireless, and external spaces. The
device provides a web-based user interface for control. A built-in time
clock enables room lighting and occupancy and vacancy sensing
automation. The ZUM-HUB4 can also be integrated with other Crestron
lighting systems and control systems.
The ZUM-HUB4 is featured in three kits.
lZUML-HUB4-GW: 4-Series™ Control Processor for Zūm® Lighting
Control System with Wireless Gateway and Power Supply
Contains:
oZUM-HUB4 and PW-2420RU power pack
oZUMNET-GATEWAY: Zūm® Net Wireless Gateway for Zūm Light
Control System
oPW-2407WU: Wall Mount Power Pack, 24VDC, 0.75A, 2.1 mm,
Universal
For use with the ZUMNET-GATEWAY
lZUML-HUB4-PAK: Zūm® Lighting Control Processor Panel, Basic
Contains:
oZUM-HUB4 and PW-2420RU power pack
oCEN-SW-POE-5: 5-Port PoE Switch
oGLEX-FT-24-HC: Feed-Through Enclosure, 24 Circuits, Hinged
Cover
lZUML-HUB4-CN-PAK: Zūm® Lighting Control Processor Panel,
Expanded
Contains:
oZUM-HUB4 and PW-2420RU power pack
oDIN-AP4: 4-Series™ DIN Rail Control System
oDIN-EN-6X18: Enclosure for DIN Rail Devices, 6 DIN Rails, 18 M
Wide
oCEN-SW-POE-5 (x2): 5-Port PoE Switch
oDIN-HUB (x2): DIN Rail Cresnet Distribution Hub
oDIN-PWS60 (x2): DIN Rail 60 Watt Cresnet® Power Supply
For use with the DIN-HUB
In the Box
1 ZUM-HUB4, 4-Series™ Control Processor for Zūm®
Lighting Control System
Additional Items
1 Connector, 4-Pin (2003576)
1 Power Pack, 24VDC, 2.5A, 100-240VAC (2045873)
2 Bracket, Rack Ear, 1U (2032122)
4 Foot, 0.5 in. x 0.5 in. x 0.23 in., Rubber, Black (2002389)
1 Power Cord, 5 ft 10 in. (1.78 m) (2042043)
ZUM-HUB4
4-Series™ Control Processor for Zūm® Lighting Control System
1

2
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Installation
The ZUM-HUB4 can be mounted into a rack or placed onto a flat
surface.
Mounting Into a Rack
The hub occupies 1U of rack space.
To install the included rack ears:
1. Use a #1 or #2 Phillips screwdriver to remove the three screws from
each side of the front of the device as shown in the following
illustration.
2. Use the screwdriver and the screws removed in the previous step to
attach the included rack ears to the device.
3. Mount the device into the rack using four mounting screws
(notincluded).
Placing onto a Flat Surface
When placing the device onto a flat surface or stacking it with other
equipment, attach the included rubber feet near the corners on the
underside of the device.
Make Connections
The hub has a dedicated Control Subnet that is used for communication
between the control system and Crestron Ethernet devices. This subnet
allows for dedicated communication between the control system and
Crestron Ethernet devices without interferences from other network
traffic on the LAN.
Make the connections, and note the following:
lUse Crestron power supplies for Crestron equipment.
lThe included cable(s) cannot be extended.
lApply power after all connections have been made.
NOTES:
lEnsure the unit is properly grounded by connecting the chassis
ground lug to an earth ground (building steel).
lThe hub can be powered with the (included) 24VDC power pack.
lDo not connect the CONTROL SUBNET port to the LAN. The
CONTROL SUBNET port must be connected only to Crestron
Ethernet devices.
For details on using the Control Subnet, refer to the 4-Series™ Control
Systems Reference Guide (Doc. 8559).
3
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Connections
4
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Zūm Wired System Diagram NOTES:
lDaisy-chain up to 20 Zūm Net devices (up to 328ft (100m)
between Zūm Net devices) with purple CBL-CAT5E-ZUMNET-P
RJ-45 cables (sold separately).
lDo not exceed three network switches between a ZUM-HUB4
and a Zūm Net device.
lSystem sensors communicate digitally via Zūm Link. Non-system
sensors communicate via an analog connection on a Zūm Wired
load controller.
Firmware Upgrade
Before using a Zūm Wired device, ensure it is updated with the latest
firmware. Check for the latest firmware at
www.crestron.com/firmware. Load the firmware onto the device using
Crestron Toolbox™ software, the ZUM-HUB4 web interface, or the Zūm
app (refer to Update Firmware for a Zūm Space).
5
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Configure the ZUM-HUB4
The ZUM-HUB4 is configured using the web interface. Connect to the
device by entering the device hostname into a web browser. The
hostname is comprised of "ZUM-HUB4-" followed by the entire MAC
address (e.g., ZUM-HUB4-00107FCA1112). The New User Registration
screen is displayed during the first connection. Enter the user's
Username,Password,Firstname,Lastname, and Email Address, and
then click Submit.
Navigate to the Settings page to begin configuring the ZUM-HUB4.
For further configuration, refer to the ZUM-HUB4 Product Manual
(Doc.9094).
6
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Zūm Wired Setup
Once all of the devices are installed in the space and using the latest
firmware, use the Zūm app to modify default room behavior. Expedite
commissioning by copying a room configuration and sending it to a room
with identical devices. Save a room configuration template and share it
via email, or other methods available on the device. A template can be
deployed to any identical room via the Zūm app or the ZUM-HUB4.
NOTE: The ZUMLINK-KP Bluetooth® connection is required to
configure a Zūm wired space with the Zūm app.
Connect to the Zūm App
Download the Zūm app from the Google Play™ online store or the
Apple® App Store® online store.
To use the Zūm app:
1. Enable Bluetooth wireless connection on your device to communicate
with the Zūm space.
2. Launch the Zūm app and grant the permissions the app requests. The
Zūm app displays a list of available spaces.
3. If new firmware is detected, update the firmware. Refer to Update
Firmware for a Zūm Space.
4. Select the desired space.
5. When prompted, enter the PIN. The Zūm app main screen opens.
NOTES:
lFor Primary load controllers running firmware 3.6.18 and higher,
the default PIN is 246800. For firmware lower than 3.6.18, the
default PIN is 2468.
lTo change the PIN, navigate to the Room Settings. When
changing the PIN, the previous PIN is required.
lThe first failed log-in attempt locks the user out of the Zūm
space. With subsequent failed attempts, the lockout duration
increases up to 60 minutes.
lThe lockout duration resets when the correct PIN is entered, the
Primary load controller reboots, or when the PIN is changed from
the ZUM-HUB4 Web-Interface.
7
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Zūm App Main Screen
From the Nearby Rooms screen, tap the desired room to open the Main
screen. The following sections describe the actions available for each
area of the Main screen.
8
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

NOTE: The numbers below correspond with the numbers in the Main
screen diagram.
1. Room Settings: Edit the Room Name, PIN, Floor ID, Zone ID, and
Network information.
2. Configuration: Edit the room logic to view the current state of the
room.
lOccupancy Sensors: View details for the connected sensor(s)
or edit the sensor name.
lPhoto Sensors: View details for the connected sensor(s) or edit
the sensor name.
lLoad Controllers: Identify and view details for the connected
load controller(s).
oZUMLINK-JBOX-16A-LV and ZUMNET-JBOX-16A-LV load
controllers:
nView Current Scene, Daylighting status, and Output
Level.
nOverride: The state of the load when Override is recalled.
Click the toggle to turn the load on or off during
Override.
nAssign the occupancy mode (Occupancy menu), vacancy
mode (Vacancy menu), vicinity mode (Vicinity menu), and
daylight harvesting (Photo menu) to specific load
controllers.
nView Dimming Values
nEdit the Dimming Curve Configuration or Dimmer
Scenes Configuration.
oZUMLINK-JBOX-20A-PLUG load controller:
nOverride: The state of the load when Override is recalled.
Click the toggle to turn the load on or off during
Override.
nAssign the occupancy mode (Occupancy menu), vacancy
mode (Vacancy menu), vicinity mode (Vicinity menu), and
daylight harvesting (Photo menu) to specific load
controllers.
oZUMLINK-JBOX-20A-SW load controller:
nClosed: Click the toggle to turn the load on or off.
nOverride: The state of the load when Override is recalled.
Click the toggle to turn the load on or off during
Override.
nAssign the occupancy mode (Occupancy menu), vacancy
mode (Vacancy menu), vicinity mode (Vicinity menu), and
daylight harvesting (Photo menu) to specific load
controllers.
nScenes: Allow keypad access to the scene by selecting or
deselecting the checkbox. Determine the state of the
load when the scene is recalled by clicking the toggle on
or off.
9
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

oZUMLINK-EXP-16A-DIMU load controller:
nView Current Scene, Daylighting status, and Output
Level.
nOverride: The state of the load when Override is recalled.
Click the toggle to turn the load on or off during
Override.
nAssign the occupancy mode (Occupancy menu), vacancy
mode (Vacancy menu), vicinity mode (Vicinity menu), and
daylight harvesting (Photo menu) to specific load
controllers.
nView Dimming Values.
nEdit the Dimmer Scenes Configuration.
lScenes: View and edit room scenes: Scene 1 - Scene 16. When
editing the scene, tap the Identify icon to identify the load
controller. The load controller emits a sound and flashes the
Link LED. The connected loads also flash.
lKeypads: Identify and view details for the connected keypad(s).
Edit the keypad name and assign the button layout.
oAdjust the Double Tap Speed: Set the amount of time
between two button presses to qualify as a double tap.
oSpecify the Button Layout and click on a button to
configure button actions.
Button action options:
nNone
nOff: Assigned load controllers turn off.
nOn: Assigned loads turn on.
nRaise: Assigned load controllers raise.
nToggle: Switches load controllers between ON and
OFF states
nLower: Assigned load controllers lower.
nRecall Scene 1 - Scene 16: Assigned load controllers
recall the behavior set for the specified scene.
nExport to Hub: Name and send information to
ZUM-HUB4 for macro actions.
lLoad Shedding: Set the maximum levels for load shedding.
lLoad/Sensor Groups: Create groups within the room.
lDALI Controllers: Address drivers, create DALI groups, assign
drivers, and identify drivers.
lCurrent Scene: Displays the current room scene.
lOccupancy Status: Displays occupied or vacant. If any area of
the room is occupied, then the status is Occupied. When all
areas of the room are vacant, the status is Vacant.
3. Firmware: To update firmware, refer to Update Firmware with the
Zūm App.
4. Discovered Room Devices: Identify a device and edit the
commissioning settings
10
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

lTap the Identify icon to identify a device. A load controller
emits a sound and the Link LED flashes. The connected loads also
flash. A keypad flashes its LED.
lTap the device to edit or review the device details: Edit Name.
Review the Model, Serial Number, Status, and edit the device
settings.
5. Current Template Settings: Choose Open room template, Save room
template, or Share room template.
6. Configuration Data:
lSave room configuration: Save the room configuration data in the
space.
lShare room configuration: Share the room configuration data in
the space.
lSend configuration to room: Send room logic changes made in the
app to the room.
lAdvanced data management: Review the Map, Logic, and
Settings of the data currently loaded. Load, save or share new
Map, Logic, or Settings data.
NOTE: Changes made in the app are not sent to the room
until they are deployed using the Send configuration to room
button.
7. Revert changes: Restore all non-deployed changes made since
launching the app.
11
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System

Additional Information
Original Instructions
The U.S. English version of this document is the original instructions.
All other languages are a translation of the original instructions.
Regulatory Model: M201903003
This product may be purchased from select authorized Crestron dealers and
distributors. To find a dealer or distributor, please contact the Crestron sales
representative for your area. A list of sales representatives is available online at
www.crestron.com/How-To-Buy/Find-a-Representative or by calling 855-263-8754.
Crestron product development software is licensed to Crestron dealers and Crestron
Service Providers (CSPs) under a limited nonexclusive, nontransferable Software
Development Tools License Agreement. Crestron product operating system software
is licensed to Crestron dealers, CSPs, and end-users under a separate End-User
License Agreement. Both of these Agreements can be found on the Crestron website
at www.crestron.com/legal/software_license_agreement.
The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed online at
www.crestron.com/legal/patents.
Certain Crestron products contain open source software. For specific information,
please visit www.crestron.com/opensource.
Crestron, the Crestron logo, 4-Series, Cresnet, and Zūm are either trademarks or
registered trademarks of Crestron Electronics, Inc. in the United States and/or other
countries. Other trademarks, registered trademarks, and trade names may be used in
this document to refer to either the entities claiming the marks and names or their
products. Crestron disclaims any proprietary interest in the marks and names of
others. Crestron is not responsible for errors in typography or photography.
©2023 Crestron Electronics, Inc.
Doc ID 9004C
05/17/23
12
ZUM-HUB4 QuickStart
4-Series™ Control Processor for Zūm® Lighting Control System
Other manuals for 4 Series