Daikin DTA119A71 User manual

INTERFACE ADAPTER-AOR
DTA119A71
INSTALLATION MANUAL
IMPORTANT SAFETY INSTRUCTIONS
The following symbols and labels are used throughout this manual to indicate
immediate or potential safety hazards. It is the owner’s and installer’s
responsibility to read and comply with all safety information and instructions
accompanying these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product damage.
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING.
MULTIPLE POWER SOURCES MAY BE PRESENT.
FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST,
SERVICE OR REPAIR (HEREINAFTER, “SERVICE”) THE EQUIPMENT
SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY
OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR
SERVICE PROCEDURES. IF YOU SERVICE THIS UNIT,YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH
MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE
OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN
THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE
EQUIPMENT.
IMPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO
INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN
THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT
DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
01-FITQ AOR_DTA119A71_IM_EN.indd 1 2020/09/25 15:31:44

Index
IMPORTANT SAFETY INSTRUCTIONS.........................................1
SHIPPING INSPECTION ................................................................3
CODES & REGULATIONS .............................................................3
FEATURES .....................................................................................4
ACCESSORIES ..............................................................................4
SAFETY CONSIDERATIONS .........................................................5
APPLICATION.................................................................................7
INSTALLATION...............................................................................8
ELECTRIC WIRING WORK ............................................................9
WIRING DIAGRAM .......................................................................10
DEHUMIDIFICATION SETTING....................................................12
TROUBLESHOOTING ..................................................................17
2English
01-FITQ AOR_DTA119A71_IM_EN.indd 2 2021/04/19 13:50:10

SHIPPING INSPECTION
Shipping damage, and subsequent investigation is the responsibility of the
carrier. The distributor or manufacturer will not accept claims from dealers
for transportation damage or installation of incorrectly shipped units.
CODES & REGULATIONS
This product is designed and manufactured to comply with national codes.
Installation in accordance with such codes and/or prevailing local codes/
regulations is the responsibility of the installer. Please refer to the Codes
& Regulations in outdoor unit Installation and Operation manuals.
This device complies with Part 15 of the FCC’s Rules. Operation of this
device is subject to two conditions:
(1) This device may not cause harmful interference; and
(2) This device must accept any interference received, including
interference that may cause undesirable operation.
And this device meets the applicable Industry Canada technical specications.
CAN ICES-3(B)/NMB-3(B)
The FCC responsible party is Goodman Manufacturing Company, L.P.,
and may be contacted by calling (713)-861-2500, or at 19001 Kermier Rd.,
Waller, TX 77484. (www.GoodmanMFG.com)
Changes or modications not expressly approved by the party responsible
for compliance could void the user’s authority to operate the equipment.
NOTE:
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/ TV technician for help.
3English
01-FITQ AOR_DTA119A71_IM_EN.indd 3 2021/04/19 13:50:11

FEATURES
This interface adapter is part of a system that uses inverter technology to
more efficiently remove heat and achieve the target comfort conditions.
This adapter is designed to be compatible with any non-communicating
gas furnaces. The adapter may ONLY be paired with Daikin One+ Smart
Thermostat as part of the digital communicating system.
NOTE: The installation of the adaptor with unmatched system units will
not allow for proper operation.
ACCESSORIES
Name ①Installation
manual
②Screw
(M4 x 16 mm)
③Screw
(M4 x 10 mm)
Shape
Quantity 1 2 4
(Including 2 spares)
Name ④Clamp ⑤Wiring terminal
(Use for X1A) ⑥
Sealing material
Shape
Quantity 1 1 1
4English
01-FITQ AOR_DTA119A71_IM_EN.indd 4 2020/12/14 21:03:38

SAFETY CONSIDERATIONS
Read these Safety considerations for Installation carefully before installing
the adapter. After completing the installation, make sure that the unit
operates properly during the system start-up operation. Instruct the
customer on how to operate and maintain the unit. Inform customers that
they should store this Installation Manual for future reference.
Always use a licensed installer or contractor to install this product. Improper
installation can result in water or refrigerant leakage, electrical shock, re,
or explosion.
MEANINGS OF SYMBOLS
WARNING ........ Indicates imminently or potentially hazardous situation
which, if not avoided, will result in death or serious
injury.
CAUTION .........
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
NOTICE ............ Indicates situations that may result in equipment or
property-damage accidents only.
While these items will not cover every conceivable situation, they should
serve as a useful guide.
WARNING
• DO NOT GROUND UNITS TO WATER PIPES, SUCTION LINE,
TELEPHONE WIRES, OR LIGHTNING RODS AS INCOMPLETE
GROUNDING WILL RESULT A SEVERE SHOCK HAZARD RESULTING
IN SEVERE INJURY OR DEATH. ADDITIONALLY, GROUNDING TO
GAS PIPES WILL RESULT A GAS LEAK AND POTENTIAL EXPLOSION
RESULTING IN SEVERE INJURY OR DEATH.
• SAFELY DISPOSE ALL PACKING AND TRANSPORTATION MATERIALS
IN ACCORDANCE WITH FEDERAL/STATE/LOCAL LAWS OR
ORDINANCES. PACKING MATERIALS INCLUDING PLASTIC PACKING
MATERIALS USED FOR TRANSPORTATION WILL RESULT IN INJURIES
OR DEATH BY SUFFOCATION.
• ONLY QUALIFIED PERSONNEL MUST CARRY OUT THE INSTALLATION
WORK. INSTALLATION MUST BE DONE IN ACCORDANCE WITH THIS
INSTALLATION MANUAL. IMPROPER INSTALLATION COULD RESULT
IN WATER LEAKAGE, ELECTRIC SHOCK, OR FIRE.
5English
01-FITQ AOR_DTA119A71_IM_EN.indd 5 2020/10/05 18:43:35

• USE ONLY SPECIFIED ACCESSORIES AND PARTS FOR
INSTALLATION WORK. FAILURE TO USE SPECIFIED PARTS COULD
RESULT IN WATER LEAKAGE, ELECTRIC SHOCKS, FIRE, OR THE
UNIT FALLING.
• INSTALL THE ADAPTER ON A PLACE STRONG ENOUGH THAT IT CAN
WITHSTAND THE WEIGHT OF THE UNIT.
A PLACE OF INSUFFICIENT STRENGTH COULD RESULT IN THE UNIT
FALLING AND CAUSING INJURIES.
• MAKE SURE THAT A SEPARATE POWER SUPPLY CIRCUIT IS
PROVIDED FOR THIS UNIT AND THAT ALL ELECTRICAL WORK IS
CARRIED OUT BY QUALIFIED PERSONNEL ACCORDING TO LOCAL,
STATE AND NATIONAL REGULATIONS. AN INSUFFICIENT POWER
SUPPLY CAPACITY OR IMPROPER ELECTRICAL CONSTRUCTION
COULD RESULT IN ELECTRIC SHOCKS OR FIRE.
6English
01-FITQ AOR_DTA119A71_IM_EN.indd 6 2020/10/05 18:43:36

APPLICATION
This system is designed to work with
Daikin One+ Smart Thermostat only.
(Not available for CTK04 or other thermostats)
This system can be paired with conventional
gas furnaces (single-stage or two-stage).
Allowed indoor and outdoor unit combinations
Please refer to DAIKIN CITY or PartnerLink for the available indoor and
outdoor unit combinations.
NOTICE
All AHRI (Air Conditioning, Heating and Refrigeration Institute) system
ratings are accessible in the unitary matchup tool via DAIKIN CITY or in
the DAIKIN system congurator tool via PartnerLink.
Allowable Air ow CFM range
Rated performance is based on fan speed changing under low load
conditions. This lower airow will also provide best dehumidication and
comfort. The fan taps must be properly set to provide rated airows. Please
refer to Specication Sheets for correct airow rates. Any airow setting
beyond the range specied may cause condensation, dehumidication, or
compressor reliability issues.
Check the installation restrictions of each unit.
The latest Installation Manual can be obtained from the website“DAIKIN CITY
(Installation Manual/Unitary Split System)”or“PartnerLink (Info-FinderPlus/
Literature)”.
[DAIKIN CITY URL]
https://www.daikincity.com/Library/
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info-nder-plus
7English
01-FITQ AOR_DTA119A71_IM_EN.indd 7 2020/10/22 13:41:22

INSTALLATION
RA
SA
Screw
(accessory: M4×16 mm (②))
Mount the adapter with the screws (accessory: M4×16 mm
(②)) on a place
which has sufficient strength and stability.
(Return air duct, beams, pillars, walls, or other place which can support
this adapter appropriately)
DO NOT mount this adapter in a place has risk of vibration or water droplets.
Please refer to the wiring diagram part for adding a standard single-pole
double-throw (SPDT) relay when needed. This user-supplied SPDT relay
will be installed in the existing furnace.
CAUTION
NOT ON A-coil
NOT ON GAS FURNACE
NOT ON SA DUCT
OK for RA
DUCT
RA
SA
Do NOT mount DTA119A71 to any supply duct. Also, avoid mounting the
adapter directly to any air handler, furnace, hot water coil or evaporator
cabinet in the area. Otherwise, this may cause damages to those parts.
8English
01-FITQ AOR_DTA119A71_IM_EN.indd 8 2020/12/14 21:03:39

ELECTRIC WIRING WORK
1. Connect the wires to the devices according to the wiring diagram.
The connections are different due to different gas furnace (single-stage
or two-stage).
2. Connect the ground wire to the grounding screw.
Control/
Communication wires
Wiring through-hole
Pass the wires out
through the wiring
through-hole.
Attach wiring
terminal (⑤) to
PCB board.
When clamping the wires, be sure not to pull the wires out of
the wiring terminal.
After wiring, attach lid and x by screw (③).
Ground wire
Connect the ground wire to the appropriate place
(Unpainted surface of grounded furnace).
After wiring, please seal the gap with
the sealing material (⑥).
9English
01-FITQ AOR_DTA119A71_IM_EN.indd 9 2020/12/16 15:07:51

WIRING DIAGRAM
OFF
ON
COLOR CODES:
BL – BLUE BR – BROWN
RD –RED WH –WHITE
GY – GREY YL – YELLOW
BK – BLACK PU – PURPLE
GR – GREEN
DIP SWITCH CODES:
NOTES:
1. THE SIZE FOR WIRES USED IN X1A MUST BE WITHIN THE RANGE OF 12 TO 24 AWG,
WITH TEMPERATURE RATING OF AT LEAST 105 ℃.
2. UNIT MUST BE PERMANENTLY GROUNDED AND CONFIRM TO N.E.C AND LOCAL CODES.
3. CONNECT THE CORRECT TERMINALS IN FURNACE DUE TO DIFFERENT TYPES OF
FURNACE.
4. ADJUST DS2 DUE TO DIFFERENT SCENARIOS LISTED NEXT TO THE WIRING DIAGRAM.
5. PLEASE MAKE SURE THE TRANSFORMER IN GAS FURNACE HAS THE SUFFICIENT
POWER TO SUPPORT THIS ADAPTER (8 VA).
1 2 3 4 1 2 3 4
SINGLE-STAGE
GAS FURNACE
(DEFAULT)
SINGLE-STAGE
GAS FURNACE
(IF BLOWER SETTING
“G” HAS A HIGHER
SPEED TAP THAN “Y”)
1 2 3 4
TWO-STAGE
GAS FURNACE
1 2 3 4
NO FIELD
ADJUSTMENT
DS2
DS11
H2P(DIAGNOSTIC LED) INDICATIONS:
3 FLASHES: THERMOSTAT COMMUNICATION ERROR
4 FLASHES: EQUIPMENT COMMUNICATION ERROR DURING OPERATION
5 FLASHES: EQUIPMENT COMMUNICATION ERROR DURING START UP
6 FLASHES: ABNORMAL COMBINATION
COMPONENT CODES:
LOW VOLTAGE FIELD
HIGH VOLTAGE FIELD
CONNECTOR
ELECTRICAL GROUND
Fuse
LED
THERMOSTAT INDOOR A-COIL INTERFACE ADAPTER
H1P
H2P
HAP
32V 3A
Fuse
F1U
DIP SWITCH
DS11
DIP SWITCH
DS2
1 2 3 4
1 2 3 4
GAS FURNACE
(SINGLE-/TWO-STAGE) INVERTER OUTDOOR UNIT
AC
SUPPLY
POWER
L2
L1
24V AC
SINGLE-
STAGE
TWO-
STAGE
1 2 R C G W1 W2 YLO Y
1 2 R C1 2 R C
1 2 R C
C
G
R
C
G
R
W1
W2
Y
YLO
Y
W
BL
RD
GY
BK
BK GY RD BL
BL
GR
RD
BR
WH
YL
PU
X1A
TERMINAL LABELS:
1 – COMMUNICATION SIGNAL G – INDOOR FAN W2 – HI HEATING
2 – COMMUNICATION SIGNAL R – 24 V AC POWER YLO – LO COOLING
C – 24 V AC COMMON W1 – LO HEATING Y – HI COOLING
Please notice the wiring length limit in the system. The wiring length from the adapter to
outdoor unit should be less than 250 ft, from the adapter to gas furnace should be less than
100 ft, and from the adapter to Daikin One+ Smart Thermostat should be less than 125 ft.
Wire with thermostat, indoor a-coil, outdoor unit and gas furnace according to the
wiring diagram.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the
most up-to-date wiring.
The required wires are data lines 1 and 2 for communication, “R” (24 V AC power) and “C”
(24 V AC common) for power supply. For single-stage furnaces, connect “G”, “W1”, and
“YLO” on the terminal interface adapter. (See WIRING DIAGRAM for external relay wiring).
For two-stage furnaces, connect “W1”, “W2”, “YLO/Y1”, “Y/Y2” to the same terminal in the
interface adapter, and change switch on “DS2” according to the wiring diagram.
10 English
01-FITQ AOR_DTA119A71_IM_EN.indd 10 2021/02/13 14:20:10

INTERFACE ADAPTER
GAS FURNACE
(SINGLE-STAGE)
AC
SUPPLY
POWER
L2
L1
24V AC
1 2 R C G W1 W2 YLO Y
C
G
R
Y
W
BL
GR
RD
BR
WH
YL
PU
(Cool-Hi speed)**
(Cool-Lo speed)**
(Heat-Hi speed)**
Heat-Hi Cool-Hi
EXTERNAL
RELAY***
** Select any blower speed based on field requirement
Multi-speed Blower
PCB TERMINAL
*(Note)
* Connect the adapter “YLO” to the furnace “Y”
(Thermostat and A-coil wiring omitted)
24VAC
SPDT
***User-supplied
Please install relay according to UL electrical codes.
For this connection, set DIP switch DS2 to
“TWO-STAGE GAS FURNACE” setting
1 2 3 4
TWO-STAGE
GAS FURNACE
DS2
WIRING DIAGRAM FOR THE SINGLE-STAGE FURNACE APPLICATION OF ADDING A RELAY
INTERFACE ADAPTER
GAS FURNACE
(SINGLE-/TWO-STAGE)
AC
SUPPLY
POWER
L2
L1
24V AC
R C
C
R
X1A
WIRE NUT
(TO FLOAT SWITCH)
WIRING DIAGRAM FOR
FLOAT SWITCH
Please connect the normally closed float switch to “R” channel
for field installation.
11English
01-FITQ AOR_DTA119A71_IM_EN.indd 11 2020/12/14 21:03:40

DEHUMIDIFICATION SETTING
The dehumidication performance will be improved by changing the
setting in Daikin
One
+ Smart Thermostat to “A” or “B” or “C”. Accordingly,
the minimum compressor speed will be locked due to different setting.
For example, by selecting “C” the minimum compressor speed will be
xed at 100% dehumidication capability. This operating range limitation
will be unlocked when the humidity reaches the set value.
The default setting is “B”. Please select the proper setting due to your
dehumidication demand or local climate. The setting can be changed
from the dehumidication setting menu at any time when required. For
instance, if “B” is still not adequate, you can select “C” to achieve the
maximum dehumidication performance.
Minimum Maximum
Dehumidication = OFF
A
B
C
Compressor speed
12 English
01-FITQ AOR_DTA119A71_IM_EN.indd 12 2021/02/13 14:20:11

DEHUMIDIFICATION SET-UP ON Daikin One+ Smart Thermostat
For a system using the adapter, Daikin One+ Smart Thermostat allows
customers to have a dehumidication prole setting to achieve different
dehumidication performance due to different requirements.
Navigating to dealer edit will allow you to access the dehumidication set-up.
1. On the “HOME” screen, select the icon in the
top right corner.
2. Select “settings”.
3. Select “conguration”.
4. Enter dealer edit mode by selecting “dealer edit”.
5. Select “continue”.
6. The installer code is need, and it can be found by
referring to the icon in top right corner.
13English
01-FITQ AOR_DTA119A71_IM_EN.indd 13 2020/10/22 13:41:24

7. Find the unique installer code and enter the code,
click “done” to unlock thermostat.
8. Choose the language and click “continue”.
9. Select “unitary” and click “continue”.
10. Select “begin setup”.
11. Choose “equipment setup”.
Example: c0fe →
14 English
01-FITQ AOR_DTA119A71_IM_EN.indd 14 2020/12/14 21:03:41

12. Select “air conditioner”, which is the outdoor unit
in the system.
13. Select “cool settings”.
14. Select “dehumidication”.
15. Select one of the settings according to your
demand at this display.
“off” means no special dehumidication prole
setting. “A” has the less dehumidication
performance than the default setting “B”, while “C”
has the maximum performance.
16. For example, select “C”.
17. And then go back to “cool settings”, conrm the
selected prole is correct.
15English
01-FITQ AOR_DTA119A71_IM_EN.indd 15 2021/02/03 18:58:48

18. Go back to the main smart thermostat setup
menu and choose “complete setup”.
19. Last, click “continue” to nish all the setting. It will
go back to “HOME” screen.
7-SEGMENT DISPLAY
SCREEN 3(SETTING MODE 1)
Setting No. Contents Setting Installer/Service Notes
7 Dehumidication Select 0:STD 2:A 4:C
1:OFF 3:B
This setting can be set with Daikin One+ Smart Thermostat or 7-segment.
Please adjust the setting according to customer request.
16 English
01-FITQ AOR_DTA119A71_IM_EN.indd 16 2020/12/16 15:07:54

TROUBLESHOOTING
As shown in wiring diagram, different LED lights show different status or
errors. H1P indicates network traffic, H2P shows network status and HAP
brinks means CPU is working.
The following fault code will be displayed on the thermostat. Also, the
STATUS LED [H2P] on the circuit board blinks. Repair according to the
details of the error.
For the other fault codes, refer to the Installation and operation manuals
of the outdoor unit and indoor unit.
ClimateTalk
Fault Code
STATUS LED [H2P]
on interface adapter
Error message
on Daikin One+
Smart Thermostat
Probable Causes Corrective Actions
D2 66 Flashes Abnormal
combination
• Abnormal system
combination
(Connection with non-
applicable units)
• Check the availability of
the combination of indoor
unit and outdoor unit.
• Check the non-
communicating gas furnace
76 44 Flashes
Equipment
communication
error during
operation
• Communication wiring
with indoor unit has loose
connection.
• Communication wiring with
outdoor unit has loose
connection.
• Check communication
wiring with indoor unit
• Check communication
wiring with outdoor unit
77 33 Flashes
Thermostat
communication
error
• Communication error
between thermostat and
interface adapter.
• Check communication
wiring with thermostat
78 55 Flashes
Equipment
communication
error during
start up
• No communication with
outdoor unit. (Not detected
outdoor unit.)
• Check communication
wiring with outdoor unit
When the gas furnace shows any abnormal condition, refer to relevant
manual for the gas furnace.
Check the installation restrictions of each unit.
The latest Installation Manual can be obtained from the website“DAIKIN CITY
(Installation Manual/Unitary Split System)”or“PartnerLink (Info-FinderPlus/
Literature)”.
[DAIKIN CITY URL]
https://www.daikincity.com/Library/
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info-nder-plus
17English
01-FITQ AOR_DTA119A71_IM_EN.indd 17 2020/12/14 21:03:42

NOTES
18 English
01-FITQ AOR_DTA119A71_IM_EN.indd 18 2020/10/01 10:27:00

01-FITQ AOR_DTA119A71_IM_EN.indd 19 2020/09/28 13:17:41

4P628731-1C EM20A001C (2104) SP
CUSTOMER FEEDBACK
Daikin is very interested in all product comments.
Please ll out the feedback form on the following link:
https://daikincomfort.com/contact-us
You can also scan the QR code on the right to be directed
to the feedback page.
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO
CHANGE WITHOUT NOTICE
© 2020
04-FITQ AOR_DTA119A71_IM_back_cover.indd 1 2021/04/16 16:27:52
Table of contents
Other Daikin Air Conditioner Accessories manuals

Daikin
Daikin KPW5E112 User manual

Daikin
Daikin EKEXMCBV3 User manual

Daikin
Daikin EKMBDXB7V1 Guide

Daikin
Daikin RRDQ220V1 User manual

Daikin
Daikin RKD50GVMV User manual

Daikin
Daikin BRR9B1V1 User manual

Daikin
Daikin FDMQ09RVJU User manual

Daikin
Daikin BYCQ140E2W1 User manual

Daikin
Daikin DP 14 Operating instructions

Daikin
Daikin K-KDU303KVE User manual