ActronAir ERQ2-16AS User manual

Model Numbers
ERQ2-16AS
ERQ3-18AS
ERQ5-21AS
ERQ5-24AS
IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air conditioning unit.
That’s better. That’s Actron.
ESP Platinum QUE
Split Ducted Unit - 3 Phase
Installation and Commisioning Guide - Indoor

02 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
Table of Contents
01. Introduction....................................................................................................................................03
01.01. Information About This Guide 03
01.02. Product Inspections 03
01.03. Codes, Regulations and Standards 03
02. Safety Instructions.......................................................................................................................... 04
03. Components Overview....................................................................................................................05
04. Indoor Unit Dimensions / Clearances...............................................................................................06
04.01. Unit Dimensions and Weights 06
04.02. Minimum Service Access Areas and Airflow Clearances 08
05. Installation Instructions...................................................................................................................09
05.01. Lifting the Unit 09
05.02. Location 09
05.03. Condensate and Safety 09
05.04. Supply Air and Return Air Duct 09
05.05. Supply Air and Return Air Plenums (Optional) 09
05.06. Return Air Filter 10
05.07. Field Pipe Connection 10
05.08. Electrical Field Connection 10
06. Unit Lifting Procedures..................................................................................................................... 11
06.01. Crane Lifting Method 11
06.02. Fork Lift Method 12
07. Safety Drain Tray ..............................................................................................................................13
08. Zone Barrel Mounting Instructions .................................................................................................. 14
09. Indoor Unit Wiring Diagram..............................................................................................................15
10. Maximum Cable Lengths ................................................................................................................. 16
11. Maximum Cable Lengths - Zoning.....................................................................................................17
12. Maintenance Frequency Checklist ....................................................................................................18
13. Key Parts List ....................................................................................................................................19

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
03
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
01. Introduction
CONGRATULATIONS on your purchase of an ActronAir Platinum Series air conditioning unit. This unit has been designed and
engineered to provide optimum air conditioning and to achieve maximum energy efficiency.
Your air conditioning system has been manufactured from the highest quality materials. Numerous “in house” and “external”
test procedures were conducted to ensure satisfactory operation.
01.01. Information About This Guide
This guide provides installation instructions, specific to your split ducted indoor unit. Read this manual thoroughly and take
into consideration all specifications and instructions to ensure correct installation and safe operation of your air conditioning
system.
IMPORTANT
Keep this document for future reference. Ensure all technicians that work on the unit can refer to this manual at any time.
01.02. Product Inspections
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit, components
and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer Care Department
immediately on: 1300 522 722 to obtain a Goods Return Number.
Check the unit nameplate to verify the model, serial number and electrical rated specifications are correct.
01.03. Codes, Regulations and Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant council, state
/ federal codes, regulations and building code standards. All electrical wiring must be in accordance with current electrical
authority regulations and all wiring connections to be as per electrical diagram provided with the unit.

04 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
02.Safety Instructions
●Only licensed HVAC technicians* should install and service this air conditioning equipment. Improper service or
alteration by an unqualified technician could result in significant and major damage to the product or property
which may render your warranty null and void. Such unqualified service could also lead to severe physical injury or
death. Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
●Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on
this manual. Safe work practices and environment must be the paramount importance in the performance of all the
service procedures.
●Ensure that unit installation complies with relevant council regulations and building code standards.
●All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to
be as per electrical diagram provided.
●Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury.
●Always wear appropriate PPE, remove any dangling jewellery and protect long hair by wearing a cap.
●Make sure that safety guards and panel covers are always firmly secured and not damaged.
●This appliance is not intended for use by young children or infirm persons unless they have been adequately
supervised by a responsible person to ensure that they can use the appliance safely. Young children should be
supervised to ensure that they do not play with the appliance.
●Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance
with AS/NZS 3000:2018 (also known as Australian Wiring Rules).
●Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
*Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and
Training dependent on local State/Territory regulations.
IMPORTANT NOTES TO INSTALLER
• This indoor unit is designed to match only with a specific ActronAir outdoor unit as specified in the Technical Selection
Catalogue.
• This unit is designed for use with R410A refrigerant only.
• The unit is supplied with factory charged dry air. Beware of the pressurised air charge when purging. Remove the caps from
the connection points and purge the system only when the field pipe connections are ready to be completed.
DANGER
Hazardous Voltage - Risk of Electrocution.
TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/TAG-
OUT (LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.
WARNING
EC Motors and Inverter Drives are fitted with high power capacitors and can have dangerous residual voltages at motor terminals
after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning
service work.
VISUAL INSPECTION AND WORK ASSESSMENT
Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important to be
familiar with the unit parts and components before proceeding with any service task.

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
05
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
03. Components Overview
INDOOR UNIT COMPONENTS OVERVIEW
INDOOR
UNIT
ID COIL ASSEMBLY
ZONE MODULE
COVER CONTROL
PANEL
EC ID Fan
INDOOR
CONTROL PANEL
INDOOR PC BOARD
*FILTER
BOARD
SAFETY TRAY
CONNECTION
CONDENSATE DRAIN
CONNECTION
* Applicable to ERQ5-21AS and ERQ5-24AS only.

06 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
04.Indoor Unit Dimensions / Clearances
04.01. Unit Dimensions and Weights
ERQ2-16AS / ERQ3-18AS
1100
80
715
20 20
INDOOR COIL
412
O/A
615 O/A
1250
40
300
72
40
340
22
50
140
247.5 247.5
575
SUPPLY
AIR RETURN
AIR
1290 O/A
40
535
70
50
EC INDOOR FAN
SUPPLY AIR
GAS PIPE
Ø 19.05mm (3/4")
SWAGED
LIQUID PIPE
Ø 9.52mm (3/8")
SWAGED
SAFETY DRAIN TRAY
Ø 20mm ID
CONDENSATE DRAIN
Ø 20mm OD
OVERALL NOMINAL DIMENSION (H x W x D)
= 412 x 1290 x 615
SUPPLY DUCT (H x W) = 300 x 715
RETURN DUCT = 340 x 1100
DRAIN CONNECTION = 20mm OD
TOP VIEW
FRONT VIEW SIDE VIEW
NOTE
• All dimensions are in mm unless specified.
• Do not scale drawing.
Unit Model Number Unit Weight (kg)
ERQ2-16AS 54
ERQ3-18AS 54

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
07
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
ERQ5-21AS / ERQ5-24AS
OVERALL NOMINAL DIMENSION (H x W x D)
= 485 x 1470 x 695
SUPPLY DUCT (H x W) = 380 x 715
RETURN DUCT = 410 x 1190
DRAIN CONNECTION = 25mm ID
FRONT VIEW SIDE VIEW
119080 120
715
337.5 337.5
INDOOR COIL
1470 O/A
695 O/A
60540 50
380
70
35
410
25
50
SUPPLY
AIR RETURN
AIR
645
20 20
1430
85
485
O/A
130
SUPPLY AIR
EC INDOOR FAN
GAS PIPE
Ø 25.4mm (1")
SWAGED
LIQUID PIPE
Ø 12.7mm (1/2")
SWAGED
SAFETY DRAIN TRAY
Ø 25mm ID
CONDENSATE DRAIN
Ø 25mm ID
TOP VIEW
NOTE
• All dimensions are in mm unless specified.
• Do not scale drawing.
Unit Model Number Unit Weight (kg)
ERQ5-21AS 76
ERQ5-24AS 80

08 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
04.02. Minimum Service Access Areas and Airflow Clearances
DUCT
WORK
DUCT WORK
A*
SERVICE
CLEARANCE
B*
SERVICE
CLEARANCE
(ELECTRICAL)
* See Table Below for
clearance dimension
119080 120
715
337.5 337.5
INDOOR COIL
1470 O/A
695 O/A
60540 50
380
70
35
410
25
50
SUPPLY
AIR RETURN
AIR
645
20 20
1430
85
485
O/A
130
SUPPLY AIR
EC INDOOR FAN
GAS PIPE
Ø 25.4mm (1")
SWAGED
LIQUID PIPE
Ø 12.7mm (1/2")
SWAGED
SAFETY DRAIN TRAY
Ø 25mm ID
CONDENSATE DRAIN
Ø 25mm ID
Model A B Height
Clearance
ERQ2-16AS / ERQ3-18AS 800 800 340
ERQ5-21AS / ERQ5-24AS 890 890 410
NOTES
• Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for
mounting hole details.
• Service Access Areas and Spaces for Airflow Clearances given above are suggested minimums based on the condition that the
spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the
unit and the outside perimeter is available.
• Minimum service access areas and spaces for airflow clearances are the responsibility of the installer, ActronAir will not be
held liable for any extra charges incurred due to lack of access and space for airflow.

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
09
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
05. Installation Instructions
The installation instructions provided below are intended as a guide only and do not supersede the relevant council, state and
federal codes, regulations and building code standards. Compliance and consultation with the authorities having jurisdiction
with the installation of this equipment is the responsibility of the installer. ActronAir will not be held liable for any damages or
costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit Installation and Commissioning
Guide for further information and details.
05.01. Lifting the Unit
The installation instructions provided, in Section 06, adhere to WH&S regulations for safe and secure lifting practices in order
to prevent physical injury.
Suggested lifting procedures are outlined in Section 06 as a reference guide to safely lift and transport the unit, however, this
does not over rule the industry WH&S practices.
05.02. Location
This unit is intended for indoor installation only. It is highly recommended that this indoor unit and accessories, particularly
zone barrels, be mounted in the roof cavity.
Mount the unit in a stable and rigid support wherein the weight is properly distributed, such as roof joist and rafters. Take into
consideration the minimum service access clearances provided in the unit drawings.
Locate the indoor unit away from the areas where noise is a critical factor. Use rubber mounting pad (not supplied) in order to
minimize the transfer of noise and vibration into building structures.
A hanging bracket assembly and rubber grommet (optional on other units) are also provided to secure the indoor unit into
the roof rafters. This configuration is most suitable for installations that require the unit to be rigidly secured up from the roof
joist.
05.03. Condensate and Safety
An integrated safety drain tray is provided as a standard inclusion to your indoor unit in order to reduce the potential of
condensate damage to the roof. A drain kit (supplied with some units) is required for the condensate drain to be externally
trapped from the indoor unit. Suggested condensate and safety tray drainage instructions are provided in Section 07 of this
document for your reference.
05.04. Supply Air and Return Air Duct
The indoor unit is supplied with a duct flange as standard in order to facilitate the system’s duct connection into the unit.
Supply and return air duct works must be adequately sized to meet the system’s air flow and static pressure requirements.
Refer to the unit drawing for supply air and return air duct dimensions, specific to your requirement.
IMPORTANT NOTES TO INSTALLER
Fit a flexible duct connection in between the unit and the duct system, where noise and vibration is a critical consideration.
05.05. Supply Air and Return Air Plenums (Optional)
Supply Air plenums and Duct Plates (twin-spigot) are available in order to facilitate your duct system connection to the indoor
unit. The supply air plenums come in 1-way, 2-way and 3-way options.

10 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
05.06. Return Air Filter
Air filters must be provided in the return air side of the unit to maintain the efficiency and prolong the operation of the unit.
These are also paramount to satisfy the requirement for a clean and hygienic room condition. Air filters must be placed in an
easily accessible location for service and maintenance.
IMPORTANT NOTES TO INSTALLER
• Air filters are not supplied with the unit as individual air filtration requirements vary.
• Ensure that filters are cleaned / replaced regularly.
05.0 7. Field Pipe Connection
Specifications and installation requirements for field pipe connections are contained in the Installation and Commissioning
Guide of the outdoor unit that matches your indoor unit. Please refer to this guide and thoroughly understand the procedures
for safe and correct indoor and outdoor connection. ActronAir highly recommend all field pipes to be insulated.
05.08. Electrical Field Connection
The power supply and control communication data to the indoor unit are supplied via the outdoor unit. Please refer to the
wiring diagram supplied with the outdoor unit for specifications.
All electrical work must be performed by a licensed electrician and must conform with the wiring diagram and all relevant
electrical authorities.

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
11
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
06.Unit Lifting Procedures
WARNING
WH&S regulations must be observed and will take precedence during lifting process.
DANGER
Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent potential
damage to property, severe personal injury or death. Please check unit weight and weight distribution points on unit drawing
dimensions section.
06.01. Crane Lifting Method
NOTE
• Crane lifting method is recommended for high rise lifting.
• Refer to catalogue for unit weight before selecting shackles and slings.
• Lifting procedure and unit model shown are suggestions and for illustration purposes only.
• It is highly recommended that installer observe current industry safe and sound rigging and lifting procedure.
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor•
10-100% Variable Refrigeration Capacity•
Multiple Speed Outdoor Fans•
Louvre Outdoor Coil Guard•
Pre-charged with R410A Refrigerant•
AM7-D8 Wall Controller Supplied as Standard•
20 m of Data Cable Included•
EXV (Electronic Expansion Valve)•
Integral Fan Coil Safety Tray with Drain Kit•
Indoor Coil Overheat Protection•
Indoor Coil Anti-Freeze Protection•
Smart Defrost Function•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day•
24- Hour ON/OFF Timer•
Auto, Heat & Cool Modes•
Auto/Continuous Indoor Fan Operation•
3 Speed Indoor Fan Setting•
Hot Start Feature•
Home/Building Automation ON/OFF Capability•
CONTROL OPTIONS
Remote Temperature Sensors•
Zone Kit for Control up to 8 Zones•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way•
Configuration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots• or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL * NETT **
COOLING CAPACITY (kW) *** 18.12 17.40
SENSIBLE CAPACITY (kW) *** 14.81 14.09
HEATING CAPACITY (kW) ^ 17.60 18.30
COOLING INPUT POWER (kW) ^^ 6.07
HEATING INPUT POWER (kW) ^^ 5.44
EER 2.99 2.87
COP 3.24 3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^ 740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH 52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH 69.0 / 71.0
POWER SUPPLY - OUTDOOR 240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR 240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ** 22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^ 32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS 40.0
APPROXIMATE STARTING AMPS <45.0
WEIGHT (kg) -- INDOOR / OUTDOOR 75.0 / 180.0
OUTDOOR UNIT MODEL SRD175C
INDOOR UNIT MODEL SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airflow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifications sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Fig. 1
Connect the loop ends of
slings onto shackle
DETAIL A
Slip nylon slings
through the pallet
INDOOR UNIT
PALLET
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor•
10-100% Variable Refrigeration Capacity•
Multiple Speed Outdoor Fans•
Louvre Outdoor Coil Guard•
Pre-charged with R410A Refrigerant•
AM7-D8 Wall Controller Supplied as Standard•
20 m of Data Cable Included•
EXV (Electronic Expansion Valve)•
Integral Fan Coil Safety Tray with Drain Kit•
Indoor Coil Overheat Protection•
Indoor Coil Anti-Freeze Protection•
Smart Defrost Function•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day•
24- Hour ON/OFF Timer•
Auto, Heat & Cool Modes•
Auto/Continuous Indoor Fan Operation•
3 Speed Indoor Fan Setting•
Hot Start Feature•
Home/Building Automation ON/OFF Capability•
CONTROL OPTIONS
Remote Temperature Sensors•
Zone Kit for Control up to 8 Zones•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way•
Configuration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots• or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL * NETT **
COOLING CAPACITY (kW) *** 18.12 17.40
SENSIBLE CAPACITY (kW) *** 14.81 14.09
HEATING CAPACITY (kW) ^ 17.60 18.30
COOLING INPUT POWER (kW) ^^ 6.07
HEATING INPUT POWER (kW) ^^ 5.44
EER 2.99 2.87
COP 3.24 3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^ 740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH 52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH 69.0 / 71.0
POWER SUPPLY - OUTDOOR 240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR 240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ** 22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^ 32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS 40.0
APPROXIMATE STARTING AMPS <45.0
WEIGHT (kg) -- INDOOR / OUTDOOR 75.0 / 180.0
OUTDOOR UNIT MODEL SRD175C
INDOOR UNIT MODEL SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airflow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifications sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
A
Provide rubber pads
to prevent damage to
the unit
EQUIPMENT REQUIRED FOR CRANE LIFTING: 1 x shackle ; 2 x nylon slings; 4 x rubber pads
Procedure:
1. Slip nylon slings through the pallet as shown in Fig. 1.
2. Use a Bow or Dee shackle to connect the slings.
3. Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles . This
will prevent the unit from being damaged during lifting.
4. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location.

12 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
06.02. Fork Lift Method
DO NOT LIFT UNIT from this end in order to
prevent damage to electrical panel and pipes.
CAUTION
Pallet fork lifting hole dimensions
All dimensions in mm.
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor•
10-100% Variable Refrigeration Capacity•
Multiple Speed Outdoor Fans•
Louvre Outdoor Coil Guard•
Pre-charged with R410A Refrigerant•
AM7-D8 Wall Controller Supplied as Standard•
20 m of Data Cable Included•
EXV (Electronic Expansion Valve)•
Integral Fan Coil Safety Tray with Drain Kit•
Indoor Coil Overheat Protection•
Indoor Coil Anti-Freeze Protection•
Smart Defrost Function•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day•
24- Hour ON/OFF Timer•
Auto, Heat & Cool Modes•
Auto/Continuous Indoor Fan Operation•
3 Speed Indoor Fan Setting•
Hot Start Feature•
Home/Building Automation ON/OFF Capability•
CONTROL OPTIONS
Remote Temperature Sensors•
Zone Kit for Control up to 8 Zones•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way•
Configuration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots• or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL * NETT **
COOLING CAPACITY (kW) *** 18.12 17.40
SENSIBLE CAPACITY (kW) *** 14.81 14.09
HEATING CAPACITY (kW) ^ 17.60 18.30
COOLING INPUT POWER (kW) ^^ 6.07
HEATING INPUT POWER (kW) ^^ 5.44
EER 2.99 2.87
COP 3.24 3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^ 740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH 52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH 69.0 / 71.0
POWER SUPPLY - OUTDOOR 240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR 240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ** 22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^ 32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS 40.0
APPROXIMATE STARTING AMPS <45.0
WEIGHT (kg) -- INDOOR / OUTDOOR 75.0 / 180.0
OUTDOOR UNIT MODEL SRD175C
INDOOR UNIT MODEL SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airflow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifications sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
624
675
100
100
100
675
38
38
Fig. 2
ELECTRICAL PANEL END
Insert forklift
tines here
Insert forklift
tines here
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor•
10-100% Variable Refrigeration Capacity•
Multiple Speed Outdoor Fans•
Louvre Outdoor Coil Guard•
Pre-charged with R410A Refrigerant•
AM7-D8 Wall Controller Supplied as Standard•
20 m of Data Cable Included•
EXV (Electronic Expansion Valve)•
Integral Fan Coil Safety Tray with Drain Kit•
Indoor Coil Overheat Protection•
Indoor Coil Anti-Freeze Protection•
Smart Defrost Function•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day•
24- Hour ON/OFF Timer•
Auto, Heat & Cool Modes•
Auto/Continuous Indoor Fan Operation•
3 Speed Indoor Fan Setting•
Hot Start Feature•
Home/Building Automation ON/OFF Capability•
CONTROL OPTIONS
Remote Temperature Sensors•
Zone Kit for Control up to 8 Zones•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way•
Configuration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots• or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL * NETT **
COOLING CAPACITY (kW) *** 18.12 17.40
SENSIBLE CAPACITY (kW) *** 14.81 14.09
HEATING CAPACITY (kW) ^ 17.60 18.30
COOLING INPUT POWER (kW) ^^ 6.07
HEATING INPUT POWER (kW) ^^ 5.44
EER 2.99 2.87
COP 3.24 3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^ 740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH 52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH 69.0 / 71.0
POWER SUPPLY - OUTDOOR 240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR 240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ** 22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^ 32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS 40.0
APPROXIMATE STARTING AMPS <45.0
WEIGHT (kg) -- INDOOR / OUTDOOR 75.0 / 180.0
OUTDOOR UNIT MODEL SRD175C
INDOOR UNIT MODEL SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airflow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifications sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Procedure:
1. To move the unit around with a forklift, insert the fork tines through the pallet, as shown in Fig. 2.
2. Do not lift the unit through the electrical panel end of the unit (See illustration for location of electrical panel end).
CAUTION
Length of fork lift tines must pass the unit middle section, in order to safely carry the unit.

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
13
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
07. Safety Drain Tray
NOTE
• Refer to indoor unit dimension page for specification of drain connectors .
• Test condensate drain installation to ensure that the water flows freely and does not leak. Also check that the drain tray does
not overflow.
INDOOR COIL
RETURN AIR
INDOOR COIL
CONDENSATE DRAIN MUST BE
RUN SEPERATLY FROM THE
SAFETY TRAY DRAIN
SAFETY TRAY DRAIN
CONNECTION
CONDENSATE DRAIN
CONNECTION
SUPPLY AIR
INTERNAL CONDENSATE TRAY
THE TOP OF THE P-TRAP
MUST BE 50MM BELOW THE
TOP OF THE CONDENSATE
DRAIN CONNECTION
THE TOP OF THE P-TRAP
MUST BE 50MM BELOW THE
TOP OF THE CONDENSATE
DRAIN CONNECTION
INSTALL A T-PIECE AS AN
AIR VENT FOR LONG DRAIN RUNS.
CLEAR
PLASTIC
INSPECTION
TUBE
P.V.C
ELBOW
CLAMP
BANDS
SEAL WITH
SILICONE
SEALANT
PREFERRED METHOD
OF CONNECTING P-TRAP
P.V.C
ELBOW
25MM 15MM
P-TRAP
ENSURE DRAIN PIPES
SLOPE DOWN FROM THE
FAN COIL AT A MINIMUM
OF 10MM PER METRE
CONDENSATE AND SAFETY TRAY
DRAINAGE
DFDRAIN - 100505
05 - 05 - 2010
REVISION DATE DRAWING NUMBER
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Suggested Minimum Slope to Ensure Correct Drainage
Suggested P- Trap Connection with Limited Height Clearance
Suggested P- Trap Connection with Long Drain Running

14 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
08.Zone Barrel Mounting Instructions
TOP VIEW
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
Duct
Duct Zone Barrel
Damper Motor on Top
of the Zone Barrel
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
SIDE VIEW
DUCT
DUCT
ZONE BARREL
DAMPER MOTOR ON
TOP OF THE ZONE
BARREL
PREFERRED LOCATION
FRONT VIEW
UPPER HALF OF ZONE
BARREL’S CENTRE LINE
ZONE
BARREL
DAMPER BLADE
DAMPER MOTOR
RECOMMENDED LOCATION

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
15
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
09. Indoor Unit Wiring Diagram
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
FIELD WIRING BY
INSTALLER
REFER TO QUE CONTROL SYSTEM
INSTALLATION & COMMISSIONING
MANUAL FOR WIRING INSTRUCTIONS
IF-1
1 EC
ECM
CONTROL
MODULE
INDOOR FAN (IF)
INTERNAL AUTO RESET
OVERLOAD PROTECTION
FERRITE
EMC-1
E
N
A
N
A
PCB JUMPER PIN
POSITION TABLES
Jumper Pin
Position A/C Model
D
PCB Model: QUEIB3-1
C
B
A
E
ERQ3-18AS
ERQ5-21AS #
ERQ5-24AS #
N/A
ERQ2-16AS
EARTH
NEUT
ACT
EC CONTROL
FERRITE
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30 SHIELDED
TWISTED PAIR DATA CABLE WITH SCREEN
WIRE CONNECTED TO TERMINAL "G" ON
OUTDOOR & INDOOR UNIT
POWER
& DATA
(YELLOW
CAT5E
CABLE)
POWER
ONLY
(YELLOW
CAT5E
CABLE)
MASTER
SECONDARY
- OPTIONAL
WiFi WiFi
RF RF
MODULATION
ZONING
QUEIB
DATA
ZONE
8
ZONE
7
ZONE
6
ZONE
5
ZONE
4
ZONE
3
ZONE
2
ZONE
1
TO ZONE 2 - 8
240V
MAINS
ZONE
MOTOR
ZONE
CONTROL 1
REMOTE
SENSOR 1
LOG
RJ45 SOCKETS FOR ACTRON AIR
CAT5E SPEC CABLES ONLY
REFER TO QUE CONTROL SYSTEM
INSTALLATION & COMMISSIONING
MANUAL FOR ALL AVAILABLE
CONFIGURATIONS
FIELD WIRING
RF
RF
OPTIONAL WIRED
CONNECTION
- POWER ONLY
TO OUTDOOR UNIT
8Z-VAQ DATA CABLE
(GREEN CAT5E CABLE)
SEE JUMPER PIN POSITION
TABLES FOR CORRECT SETTING
INDOOR
COIL IN
SENSOR
D ATA
MAINTAIN TWISTED
PAIR UNTIL TERMINAL
ON QUEIB
SHIELD
WIRE
OUTDOOR
AGB
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
FIELD WIRING BY
INSTALLER
REFER TO QUE CONTROL SYSTEM
INSTALLATION & COMMISSIONING
MANUAL FOR WIRING INSTRUCTIONS
IF-1
1 EC
ECM
CONTROL
MODULE
INDOOR FAN (IF)
INTERNAL AUTO RESET
OVERLOAD PROTECTION
FERRITE
EMC-1
E
N
A
N
A
PCB JUMPER PIN
POSITION TABLES
Jumper Pin
Position A/C Model
D
PCB Model: QUEIB3-1
C
B
A
E
ERQ3-18AS
ERQ5-21AS #
ERQ5-24AS #
N/A
ERQ2-16AS
EARTH
NEUT
ACT
EC CONTROL
FERRITE
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30 SHIELDED
TWISTED PAIR DATA CABLE WITH SCREEN
WIRE CONNECTED TO TERMINAL "G" ON
OUTDOOR & INDOOR UNIT
POWER
& DATA
(YELLOW
CAT5E
CABLE)
POWER
ONLY
(YELLOW
CAT5E
CABLE)
MASTER
SECONDARY
- OPTIONAL
WiFi WiFi
RF RF
MODULATION
ZONING
QUEIB
DATA
ZONE
8
ZONE
7
ZONE
6
ZONE
5
ZONE
4
ZONE
3
ZONE
2
ZONE
1
TO ZONE 2 - 8
240V
MAINS
ZONE
MOTOR
ZONE
CONTROL 1
REMOTE
SENSOR 1
LOG
RJ45 SOCKETS FOR ACTRON AIR
CAT5E SPEC CABLES ONLY
REFER TO QUE CONTROL SYSTEM
INSTALLATION & COMMISSIONING
MANUAL FOR ALL AVAILABLE
CONFIGURATIONS
FIELD WIRING
RF
RF
OPTIONAL WIRED
CONNECTION
- POWER ONLY
TO OUTDOOR UNIT
8Z-VAQ DATA CABLE
(GREEN CAT5E CABLE)
SEE JUMPER PIN POSITION
TABLES FOR CORRECT SETTING
INDOOR
COIL IN
SENSOR
D ATA
MAINTAIN TWISTED
PAIR UNTIL TERMINAL
ON QUEIB
SHIELD
WIRE
OUTDOOR
AGB
R R
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
Rev. Rev.
Description Description
Date Date
By By
PCR PCR
ORIGINAL ORIGINAL
A A
QUE INDOOR BOARD
WITH 2 TOUCH CONTROLLERS
QUE INDOOR BOARD
WITH 2 TOUCH CONTROLLERS
Revision Revision
Description: Description:
A A
WD2022 WD2022
A5 A5
Size: Size:
Base
Model No:
Base
Model No:
Variation: Variation:
VARIOUS VARIOUS
Variation Code: Variation Code:
Drawing No: Drawing No:
Drawn: Drawn:
Date: Date:
02-11-2018 02-11-2018
RL RL
Approved: Approved:
MJH MJH
Date: Date:
15-01-2019 15-01-2019

16 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
10. Maximum Cable Lengths
OPTIONAL
DUAL MASTER CONTROLLER
(Mimic Logic)
Secondary
Controller
4
4A
Cat5E spec cable with RJ45
connector and cable boots -
Yellow
FIELD WIRING BY INSTALLER
2 CORE 7/0.30 (0.5mm2) Twisted Pair Shielded Data Cable
OUTDOOR UNIT
TO OUTDOOR PCB
MODEL
R-410A
“CAUTION”
PLEASE THEREIS
NOGAS/PRESSUREINTHE
FANCOILUNITBEFORE
REMOVINGCOPPERENDCAPS.
ENSURE
3670-043
Sensor
4
CAUTION
LIVEELECTRICAL WIRING
AUTHORISEDTECHNICIANSONLY
INTERNAL CONTROL ISOLATORFITTED
MODEL
MEPS
CERTIFIED
A
U
S
T
R
A
L
I
A
N
M
A
D
E
A
U
S
T
R
A
L
I
A
N
O
W
N
E
D
R-410A
1
MODEL
R-410A
“CAUTION”
PLEASE THEREIS
NOGAS/PRESSUREINTHE
FANCOILUNIT BEFORE
REMOVINGCOPPERENDCAPS.
ENSURE
3670-043
Sensor
4
CAUTION
LIVEELECTRICAL WIRING
AUTHORISEDTECHNICIANSONLY
INTERNAL CONTROL ISOLATORFITTED
MODEL
MEPS
CERTIFIED
A
U
S
T
R
A
L
I
A
N
M
A
D
E
A
U
S
T
R
A
L
I
A
N
O
W
N
E
D
R-410A
INDOOR UNIT
2
8 ZONE
MODULE
3
TO INDOOR PCB
Master
Controller
Item Description Maximum Cable Length *
1 to 2 Outdoor PCB to Indoor PCB 60 m
2 to 3 Indoor PCB to QUE Module (factory fitted) 0.175 m
2 to 4 Indoor PCB to Master Wall Controller 30 m
2 to 4A Indoor PCB to Secondary Wall Controller 30 m
* Long runs beside mains cables to TV antenna cables should be avoided where possible. To minimise noise interference,
Data and Power cable clearance should be maintained as much as possible.
NOTE
Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring connection
details

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
17
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
11. Maximum Cable Lengths - Zoning
INTEGRATED ZONE BARRELS
(1-Zone Up To 8-Zone Options / Max. of 10 Zone Motors per System )
MODEL
R-410A
“CAUTION”
PLEASE THEREIS
NOGAS/PRESSUREINTHE
FANCOILUNITBEFORE
REMOVINGCOPPERENDCAPS.
ENSURE
3670-043
Sensor
4
CAUTION
LIVEELECTRICAL WIRING
AUTHORISEDTECHNICIANSONLY
INTERNAL CONTROL ISOLATORFITTED
MODEL
MEPS
CERTIFIED
A
U
S
T
R
A
L
I
A
N
M
A
D
E
A
U
S
T
R
A
L
I
A
N
O
W
N
E
D
R-410A
8 ZONE
MODULE
1.5V AAA
1.5V AAA
1.5V AAA
1.5V AAA
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
1.5V AAA
1.5V AAA
ZONE
OPTION 1
TEMPERATURE
AVERAGING ZONE
1
* All Zone Device Power Cable : Cat5E Spec Cables with RJ45 Connectors and Cable Boots - Green Colour
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
ZONE
OPTION 2
1.5V AAA
1.5V AAA
1.5V AAA
1.5V AAA
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
TYPE10" (250 mm)
PART NUMBER
ZB-10-250
INTEGRATED ZONE BARREL PART NUMBERS
12" (300 mm)
ZB-12-300
Please check prior to purchase.
ActronAir is constantly seeking ways to improve the design of it's products,therefore specifications are subject to change without notice.
ZB-080129
INTEGRATED ZONE BARRELS
12" (300 mm)
10" (250 mm)16" (400 mm)
14" (350 mm)
14" (350 mm)16" (400 mm)
ZB-14-350ZB-16-400
ITEM
PART NUMBER
24 VOLT 4 ZONE KIT
4Z-24V
INCLUSIONS
5 YEAR RESIDENTIAL / 2 YEAR COMMERCIAL
PARTS ONLY WARRANTY
ROBUST METAL BARREL CONSTRUCTION
10 mm FIRE RATED POLYETHELYNE
INSULATION
7 m CABLE SUPPLIED
(JOINERS AND EXTRA CABLE AVAILABLE)
EASY SNAP-IN WIRING CONNECTION
FAST REACTION TIME
SAFE LOW VOLTAGE (24 VAC)
HIGH TORQUE MOTOR (3 Nm)
DAMPER POSITION INDICATOR
BLADE SEAL INSULATION
FEATURES:
24 VOLT, 3 Nm MOTOR
DRIVE OPEN / DRIVE CLOSE
INSULATED METAL
ZONE BARREL
7 METER SNAP-IN CABLE
24 VOLT ZONE KIT
NOTE:
THE TOTAL LENGTH OF ALL GREY CABLES CONNECTED
TO THE ZONE MOTORS MUST NOT EXCEED 100 METERS
INCLUSIONS: 4Z-24V (4 ZONE KIT)
NOTE:
WHEN USING INTEGRATED ZONE BARRELS YOU
WILL REQUIRE THE APPLICABLE ZONE KIT.
(INCLUSIONS & INSTALLATION INSTRUCTIONS
AS PER DETAILED LIST)
OPTIONAL EXTRAS & SPARE PARTS
INTEGRATED ZONE BARRELS OPERATE
WITH M-SERIES CONTROLS ONLY
24 VOLT 8 ZONE KIT
8Z-24V
AMZ-24V ZONE CARD
20VA, 240 TO 24 VOLT TRANSFORMER
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
LENGTH OF ALL BARRELS MEASURE 290 mm.
DIMENSIONS
ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY
BOXED FOR SAFE TRANSPORT.
INCLUSIONS: 8Z-24V (8 ZONE KIT)
8Z-24V ZONE MODULE
INSTALLATION INSTRUCTIONS
MOUNTING SCREWS
ITEM
PART NUMBER
7 METER CABLE
4070-004
ZONE MOTOR ONLY
TRANSFORMER ONLY
ZM-24V
2045-046
20 METER CABLE
4070-007
2-WAY RJ45 JOINER
2045-121
3-WAY RJ45 JOINER
4070-008
1.5V AAA
1.5V AAA
1.5V AAA
1.5V AAA
1.5V AAA
1.5V AAA
ZONE
OPTION 3
2
3
4567
89
10
11
12
Zone Power Cable
Cat5E Spec Cables with RJ45 Connectors - Grey Colour
***
TEMPERATURE
AVERAGING ZONE
Item Description Maximum Cable Length
1 to 2 and 1 to 3 8-zone module to 3-way cable joiner (P.N. 4070-012) 0.175m
1 to 8 8-zone module to zone controller 100m
4 to 8, 5 to 10
and 7 to 12 zone barrel motor to zone device 20m
3 to 9 and 2 to 11 3-way cable joiner to zone device 20m
TOTAL CABLE LENGTH PER INDIVIDUAL ZONE (from 8-zone module) MUST NOT
EXCEED 100 MTRS.
TOTAL LENGTH OF ALL ZONING CABLES (from 8-zone module) MUST NOT EXCEED
250 MTRS.
1.5V AAA
1.5V AAA
OR
1.5V AAA
1.5V AAA
OR
1.5V AAA
1.5V AAA
OR
**

18 Installation & Commissioning Guide - ESP Platinum QUE Split Ducted Units
Doc. No.0525-061 Ver. 1 190131
ESP Platinum QUE - Three Phase
Installation and Commissioning Guide
12. Maintenance Frequency Checklist
Regular servicing of equipment by a qualified technician is recommended every 12 months for residential applications and
every quarter for commercial applications. Regular servicing of your unit helps in maintaining its optimum performance and
reliability. The following checklist and service periods are provided as a guide only, as some sites may require more
frequent servicing.
ELECTRICAL
Parts
Service Period Detail of
Service Check Service Methods
1
Mth
3
Mth
6
Mth
1
Yr
2
Yrs
3
Yrs
4
Yrs
5
Yrs
Isolators/Printed
Circuit Boards Visual Inspection Tighten Terminals as necessary on
isolators and printed circuit boards
Electrical
Connections
Check all electrical
terminals, mains,
communications, etc
Re-tighten if loose.
INDOOR SECTION
Parts
Service Period Detail of
Service Check Service Methods
1
Mth
3
Mth
6
Mth
1
Yr
2
Yrs
3
Yrs
4
Yrs
5
Yrs
Casing / Panels
and Frames
Visual check for
damage, rust and dust
accumulation.
For highly corrosive environment,
wash panels quarterly with water
and neutral detergent solution.
Wax panels. Repair / re-paint
where required.
Insulation Visual check for
insulation conditions. Repair / replace insulation material.
Fan
Visual check for run
out of balance and dust
attached
Clean off dust as necessary to
negate possibility of fan running
out of balance
Motor
Visual check on wiring.
Insulation resistance
check to be carried out
annually
Measure insulation resistance
to earth with insulation tester.
Insulation resistance should be
more than 1M.
Heat
Exchanger
Check for clogging by
dust. Check for leaks /
damage.
Clean air inlet side as necessary.
Straighten any bent fins using fins
comb.
Drain Pan/
Condensation
line
Check for obstructions
and free flow of water
Clean to eliminate obstructions/
sludge and check condition of pan.
Pour water to ensure flow
Filter * Check for clogging
by dust. Clean Filter
Temperature
Readings Measure air on
and air off
Place temperature probe in return
and supply air of unit.
Damper Motors
(If fitted)
Visual inspection of
motors open/closing.
Ensure no obstructions
Drive motors opened and closed.
Ensure correct operation
*Service period for filter cleaning may vary depending on operating time and surrounding environment.

Installation and Commissioning Guide ESP Platinum QUE - Three Phase
19
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
13. Key Parts List
ESP PLATINUM MODELS
ERQ2-16AS ERQ3-18AS ERQ5-21AS ERQ5-24AS
Item Description Part
Number Quantity Quantity Quantity Quantity
1
EC ID Fan 2520-330 1 1 --- ---
EC ID Fan 2520-334 --- --- 1 ---
EC ID Fan 2520-313 --- --- --- 1
2
Indoor Coil Assembly 1040-254 1 1 --- ---
Indoor Coil Assembly 1040-274 --- --- 1 ---
Indoor Coil Assembly 1040-273 --- --- --- 1
3
Coil Piston 4540-090 1 --- --- ---
Coil Piston 4540-128 --- 1 1 1
4 ID PC Board 2020-167 1 1 1 1
5 Zone Module 8Z-VAQ 1 1 1 1
6 Filter Board 4080-013 --- --- 1 1
7 Yellow Cat5e Cable 10m 4070-028 1 per controller 1 per controller 1 per controller 1 per controller

©Copyright 2018 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited.
Document: 0525-061 Ver. 1 Issue Date: 01/2019
Refrigerant Trading Authorisation
No.: AU06394
This manual suits for next models
3
Table of contents
Other ActronAir Air Conditioner Accessories manuals

ActronAir
ActronAir BMS MODBUS 485 User manual

ActronAir
ActronAir LC7-2W User manual

ActronAir
ActronAir Easyconnect OSK105 Assembly instructions

ActronAir
ActronAir CRQ2-14AS User manual

ActronAir
ActronAir Classic 2 EVA100S User manual

ActronAir
ActronAir PKV160T User manual

ActronAir
ActronAir MRE-035AS User manual

ActronAir
ActronAir CP05 User manual

ActronAir
ActronAir LR7-1W User manual

ActronAir
ActronAir Que Touch Series User manual