Daikin RRDQ220V1 User manual

【Please read this manual before operation】
REFRIGERANT
RECYCLE EQUIPMENT
RRDQ220V1
OPERATION MANUAL
【Original operation manual】
English

1
Refrigerant Recycle Equipment
Thank you for selecting Refrigerant Recycle Equipment RRDQ220V1.
● Please give this operation manual to anyone who operates this unit.
● For safe and ecient operation any operator should read this manual thoroughly before operation.
● Keep this manual at a safe place that is easily accessible by operators.
● Do not use this unit for purposes other than originally intended.
● Check the following as soon the unit is delivered:
・ Is the specication same as the ordered product?
・ Has there been any damage or deformation during delivery?
・ Are any accessories missing?
If you have any questions, please contact the store where you have purchased this unit or our sales
department.
(The contents of this manual may be changed without prior notice.)
WARNING
CAUTION
WARNINGFORSAFETY ........................... 2
COMPONENTSOFTHEUNIT
...................... ...... 5
Name of Each Part ...................................... 5
Specications ............................................... 6
Standard Accessories .................................. 6
Optional Accessories ................................... 6
HOWTOUSE ................................................ 7
Preparation Before Operation .................... 7
Recycle Operation ....................................... 8
Description of Auto Stop Timer .................. 13
Oil Discharge Procedure (Oil Separator)
..... 15
Oil Discharge Procedure (Electrostatic Filter System)
....... 15
Warm Up Operation ..................................... 16
MAINTENANCE&INSPECTION ........... 17
Maintenance ................................................. 17
Replace Molecular Sieve Replacement Kit
........ 17
In Case of Recycle Other Refrigerant ....... 18
INSPECTIONBEFOREWORK
.................. 18
LOADING/UNLOADINGOFTHEUNIT
................... 20
EUDECLARATIONOFCOMFORMITY
................... 20
BEFOREREQUESTINGREPAIRORSERVICE
......... 21
PIPINGDIAGRAM ......................................... 23
FLOWDIAGRAM(RECYCLE)...................... 24
FLOWDIAGRAM (PURGE).......................... 25
Situation that may cause death or serious injury to the operator or anyone in the
immediate area.
Situation that may cause minor to medium injury to the operator or anyone in the
immediate area or may cause damage to the unit.
Deadly
Poison
Caution
for Gas Explosion Fire No Fire Electric
Shock
Burn Rotating
Wear
Protective
Gear
Do Not
Disassemble
Grounding
Power
Source
Voltage
Handling of
Wire
Working
Condition Others Operation
Manual
The warning signs used in this manual or on the product are divided in the following two categories.
FORSAFEOPERATION
CATEGORIESOFWARNINGSIGNS
INDEX

2
RRDQ220V1
● General warnings in operating this unit are mentioned in this section.
● While specic details are mentioned in each particular clause.
◆Whenperformingrecycleoperation,choosealocationthathasgood
ventilation.Inenclosedareas,mechanicalventilationshouldprovideat
leastfourairchangesperhourortheunitshouldbeusedatleast0.5m
abovetheoor.
Leakage of gas without sufficient ventilation may cause suffocation due to lack of
oxygen.
◆Donotrecycleflammablegas(hydrocarbonor hydrocarbonmaterial).
Ifanything otherthan fluorocarbon[Ammonia,hydrocarbon(propane,
isobutene,),etc.]getsintotheunit,itmaycauseanexplosion.
◆BurningrefrigerantcreatesadeadlypoisonousCarbonOxy-Chloride
andinhalingthisgasisverydangerous.
There should be absolutely no ammable material near the working area and the unit
must be operated under good ventilation.
◆Absolutelynosmokingoranyopenameduringtheworkinprocess.
Cigarettes may create Carbon Oxy-Chloride and cause a re.
◆Usesafetyglasses andleatherhand glovesduring operationorwhen
disconnectinghoses.
Refrigerant gas may cause frostbite or damage your eye sight.
◆Donotclosethevalvesoftheunitandthehoseswhentheyarefullof
liquidrefrigerant.
◆Donotoperateorstoretheunitattemperatureabove35℃ .
When the recycle operation is done, operate the purge procedure to prevent the liquid
refrigerant from expanding which may cause an explosion.
◆Useascaletomonitortheamountofrefrigerantinthecylinder.
Stop lling at 80% or less as the cylinder may explode in the event of full lling.
◆UseONLY authorizedrellable refrigerantcylinders.The unitrequires
theuseofrecycle cylinderswithaminimumworking pressureof27.6
bar(2.76MPa/400psi).
Do not exceed the working pressure of the recycle cylinder.
◆Donotoperatetheunitwithwethandsorintherain.
Handling the electric plug and power switch with wet hands or in the rain, may cause
electric shock.
◆Makesuretohavetheunitgrounded(earthed).
If the unit is not properly grounded, it may cause electric shock.
◆Checktheelectricpowerplugregularlytomakesureofnodamage.
Alwayshavethepluginsertedrmly.
When the plug has dirt or oil or the connection is incomplete, it may cause electric shock
or re.
WARNINGFORSAFETY
WARNING
WARNING FOR SAFETY

3
Refrigerant Recycle Equipment
◆Donothavetheelectriccordconnectedtootherelectricaldevicesor
withothercords.
It may cause re.
◆Donotpullontheelectricpowercordtoremovefromtheoutlet.
It may cause re or injury.
◆Thepowersource shouldbeAC220-240V10Aoruseageneratorwith
thecapacityof3KVAormore.
If the capacity of the generator is not large enough, it may lead to overheating, smoking
or re. See the specication label or this manual for the detailed specications.
◆Donotsetuptheunitinalocationwhere gasoline,thinner, or
ammablegasexists.
The recycle unit sparks at the start-up time and may ignite gasoline and thinner.
If leaked gasoline or ammable gas accumulates at near the unit, it may cause explosion
and re.
◆Alwaysturnoff theswitchandpulloutthe powercordduring
inspectionandmaintenance.
The unit may suddenly start and cause accident.
◆Donotdisassemble.Theunitshouldonlyberepairedbyanauthorized
repairperson.
◆Donotoperatetheunitwiththecoverremoved.
It may cause injury or damage.
◆Varioussafety devicesarebuiltintothis unit.Alwayscarryoutpre-
startinspectionaccordingtopage 18"INSPECTIONBEFOREWORK"
beforeusing.
If any abnormality is found in the unit, please stop using it immediately and contact your
dealer or our sales representative.
WARNING
CAUTION
◆Transportcarefully.
The unit may get damaged but this may also cause injury.
◆Whenmovingtheunit,pushitwiththehandle.Donotpulltheunit.
◆InstallFilteratSuctionPort.
Otherwise the compressor may be damaged.
◆Anyextensioncord shouldbeathree-corecabtyrecablewith atleast
2.0mm2diameterif20morlessor3.5mmdiameterif20to30mlong.
An unsuitable extension cord (too thin or too long) may lead to failure or fire, or
electrical components may be damaged.
If the cord used is a two-core cord without a ground wire, it may cause an electric
shock.
◆Donotrecyclerefrigerantwhichcontainssealant.
Sealant may clog the valves or the check valves.
WARNING FOR SAFETY

4
RRDQ220V1
CAUTION
◆Keepaspaceof1mormorearoundtheunit.
Do not let other workers come within 1 m of the unit.
◆Donotletvisitorstouchtheunit.
◆Donotusetheunitforpurposesotherthantheoriginallyintended.
This unit is designed to recycle the specied refrigerants.
◆Donotoperatetheunitwithoverload.
Operating under overload may cause an accident or damage to the unit.
◆Donotusetheunitonanunevenoor.
The unit or the cylinder may fall over and lead to an accident.
◆Theoperatingplatformandtheworkareashouldbekept neat,clean
andwell-littoavoidaccidents.
◆Donotoperatetheunitwhenfatiguedorundertheinuenceofalcohol
ormedications.
◆Whentherecycleunit isnot inuse,storeinadryspaceandout of
reachbychildren.
◆Donotuseaccessoriesotherthanthosereferencedinthismanualor
showninourcatalogue.Useofotheraccessoriesmaycauseproblems.
◆Iftherecycleunitisdroppedorstruck,inspectimmediatelyfordamage.
Recycle under damaged, cracked and dented condition may cause injury.
◆Checkdailyfordeformedorcorrodedparts.
◆Ifanabnormalcondition(strangesmell,vibration,strange noise)is
noticed,stopoperationimmediatelyandrefertopage21inthemanual
"BEFOREREQUESTINGREPAIRORSERVICE".
◆Requestrepairorserviceinsteadofdisassemblingtheunit.Contactthe
storewheretheunitwaspurchased.
◆Useourcylindersthatareexpresslymadeforrecycling.
◆Usecylindersthatmatchthetypeofrefrigerantbeingrecycled.
◆Disposal(ForEUcountriesonly)
Componentsoftheunitarerecyclablematerialandshouldbeputtorecycling.Forthis
purposeregisteredandcertiedrecyclingcompaniesareavailable.Foranenvironmental
friendlydisposal of thenon-recyclableparts (e.g. electronicwaste)contact your local
wastedisposalauthority.
Donot disposeelectrictools withdomesticwaste. In accordancewiththe European
Directive2012/19/EC the disposalofelectrical and electronicequipmentand its
implementationas national law,electrictools that arenolonger serviceable mustbe
collectedseparatelyandutilizedforenvironmentallycompatiblerecycling.
◆BatteriesareusedinAutoStopTimer.
Disposethembytheregulations.
◆Whendisposingtheunit:
Handleaccordingtotheregulationsorthemethoddenedbyeachmunicipality.
(MolecularSieve,Filter,variousplasticparts,etc.)
WARNING FOR SAFETY

5
Refrigerant Recycle Equipment
Operation time
Oil Discharge Port
for Oil Separator
Power Cord
Force Start Switch
Specification Label
Dry Filter
(V2) Switching Valve
(V3) Discharge Valve
(V1) Suction Valve
Suction Pressure
Gauge
Discharge Pressure
Gauge
Warning Lamp for
high pressure
Tank Full Lamp
Start Switch
Power Switch
Breaker
Auto/Manual
Shut-off Mode
Setting Auto Stop Timer
Oil Discharge Port
for Electrostatic Filter System
Suction
Port
Filter
(TF011)
Discharge
Port
Sight Glass
(ES603)
Labels are required by law for safety and the warnings are placed on the recycle unit.
If the label comes o the unit or became dirty and unreadable, request us for new label.
Replace the label at the same position on the unit.
COMPONENTSOFTHEUNIT
NameofEachPart
COMPONENTS OF THE
UNIT

6
RRDQ220V1
* Specications are subject to change without prior notice.
* Recycle rates vary under dierent conditions.
* When recycle R134a, follow page 11 in the operation manual.
StandardAccessories
Description Refrigerant Recycle Equipment
Code No. / Type AR023E / RRDQ220V1
Recycle refrigerant
R410A、R32、 R134a
Recycle method Liquid, Electrostatic separation recycle method(possible to vapor recycle)
Power supply 220 - 240V/ Single-phase(50 / 60Hz) > 8 Amps recommended
Compressor 750W(1HP) Oil free
Dimension / Weight 562 x 538 x 976mm (L x W x H) / 60kg
Electric current of operation
8.0/6.0A (50/60Hz)
Operating temperature
5 – 35℃
Degrees of protection IP20
Applicable cylinder Refrigerant Recycle Cylinder (minimum working pressure of 400 psi )
Recycle rate R410A R32 R134a
Liquid (g/min) 220 100 100
Vapor (g/min) 90 90 90
Recycled refrigerant R410A R32 R134a
Performance standard AHRI 740
Moisture (ppm) < 20 < 20 < 20
Total residue on evaporation (% ) < 0.01 < 0.01 < 0.01
* Results of the recycle varies depending on the contamination of the refrigerant to be recycled.
Description Code No.
1/4" Charging Hose with Ball Valve (Red) 152cm AR344
1/4" Charging Hose with Ball Valve (Blue) 152cm AR345
Filter TF011
Dry Filter Cartridge with Molecular Sieve AR179E
Sight Glass 1/4" ES603
Flare Joint 1/4" Female x 1/4" Female BF0020
Operation Manual RRDQ220V1 IM0496
Specications
OptionalAccessories
Description Code No. Explanation of the Item
Liquid Charge Adapter 1/4" Y41123 Used for recycle of R134a
COMPONENTS OF THE
UNIT

7
Refrigerant Recycle Equipment
The new unit is lled with nitrogen gas to prevent damage during transit.
① Connect the unit to proper power supply.
② Connect Filter to Suction Port.
(Refer to page 8 ③ )
③ Connect Sight Glass to Discharge Port.
④ Open Suction Valve and Discharge Valve.
1)Dischargenitrogengasfromtheunit
3)PreparationofCylinder
Evacuate a cylinder by using a vacuum pump (optional accessories).
① Connect the suction port of the vacuum pump
to the vapor port of the cylinder with a hose.
② Switch on the vacuum pump.
③ Close the liquid port of the cylinder and open
the vapor port.
④ Close the vapor port of the cylinder when the
vacuum reaches - 0.095MPa( - 13.8psi) ~
- 0.1MPa(- 14.5psi).
⑤ Switch o the vacuum pump.
⑥ Disconnect the hose between the vacuum pump and the cylinder.
① In case ambient temperature is under 10℃ , the unit needs warming up before operation. Refer to
the page 16, Warm Up Operation. Do not operate at temperature under 5℃ and over 35℃ .
② Filter provided as standard accessory must be installed on Suction Port when operating the unit.
③ Do not recycle following refrigerant with the unit :
・The purity of recycled refrigerant is low and, it may cause damage to the unit.
・Refrigerant charged in a system which the compressor has been burned out.
・Refrigerant which may be mixed with other type of refrigerant.
・Refrigerant which contains sealant.
4)Precautions
Liquid Port Vapor Port
Suction
Port
Cylinder Vacuum Pump
OPEN
3
Remove
cap
Suction Port /
Discharge Port
2
(V1) Suction /
(V3) Discharge
Valve
HOWTOUSE
PreparationBeforeOperation
◆ Brand-newcylindershavenitrogeninside.
Evacuationshouldbedoneafterdischargingnitrogenbyopeningthevaporvalve.
◆ Donotevacuatecylinderswhichcontainrefrigerant.
Therefrigerantwillbedischargedtotheairandthevacuumpumpoilwillblowout.
CAUTION
Install the unit according to the following.
① Flat space indoors.
② Lock Casters properly.
③ Keep 1 m or more around the unit for safe operation.
2)Installationoftheunit
HOW TO USE

8
RRDQ220V1
① Connect the hoses as above.
② Check elapsed time of timer
③ Connect Filter to Suction Port of the unit.(Code No.TF011)
④ Install Molecular Sieve provided as a standard accessory.(Refer to page 17)
RecycleOperation
1)Connectionofhoseandcords
Operationtime
Suction Discharge
CLOSE
Liquid
valve
CLOSE
CLOSE
Low
pressure side
High
pressure side
CLOSE
Vapor
valve
Cylinder Manifold RRDQ220V1
Cylinder + Scale
Vapor valveLiquid valve
Liquid port
CLOSE
CLOSE CLOSE
kg
M ED
RESOLUTION
Filter
CLOSE
◆ Besuretouseascaletopreventoverllingofcylinder.
◆Overllingmaycausecylinderrupture.
◆ Thisinstallationshouldbedonequicklyafteropenthepackagetoavoidspoilingthequality
ofMolecularSieve.
CAUTION
CAUTION
◆ Pleasecheckifelapsedtimeofthetimerhasreached20hours.
◆In R32・R134arecycle,press Reset KeyofAuto StopTimerat rst automaticstopto
initializethe timerandreplaceMolecular Sieve ReplacementKitand Filter atsecond
automaticstop(40hours).
◆ Please replace Molecular Replacement Kit and Filter and press Reset Key of Auto Stop
Timer to initialize the timer.
CAUTION
◆ Makesuretheinstallingdirection.
◆ HoldSuctionPortrmly with awrenchto prevent
damageofinsidepartswhenconnectingFilter.
◆ After20hours(R410A)or40hours(R32・R134a)ofoperation,orwhenclogging,replace
Filter.
CAUTION
A scale must be used to prevent
overfilling of cylinder.
⑤ Connect Liquid Charge Adapter(Code No. Y41123) as an optional accessory for R134a.
HOW TO USE

9
Refrigerant Recycle Equipment
① Open high and low pressure side valve of manifold.
② Open the ball valve of the hose.
③ Connect vacuum pump to side port of manifold.
④ Disconnect the hose which is connected to the liquid port of the cylinder.
⑤ Connect hose removed in ④ to low pressure side of manifold.
⑥ Open the ball valve of the hose.
⑦ Turn Suction Valve (V1) to [OPEN] position.
Turn Switching Valve (V2) to [Recycle] position.
Turn Discharge Valve (V3) to [Open] position.
⑧ Turn on the power switch of the vacuum pump and evacuate the suction side of the unit.
* If refrigerant remains in the unit, do not evacuate.
⇒ Continue until low pressure gauge becomes vacuum.
⑨ Turn Suction Valve (V1) to [PURGE] position.
Turn Switching Valve (V2) to [PURGE] position.
⇒ Continue until low pressure gauge becomes vacuum.
⑩ Close the discharge hose ball valve.
⑪ Turn o the vacuum pump power switch.
⑫ Connect discharge hose to liquid side port of collection cylinder.
2)Evacuationoftherecycleunitandthehoses
Operationtime
Suction Discharge
Cylinder
OPEN
Vapor valve
CLOSE
PURGE
7
OPEN
Suction Valve
PURGE
Switching Valve
OPEN
Discharge Valve
2 2 2
kg
MED
RESOLUTION
CLOSE
Liquid valve
OPEN
CLOSE
Vapor valve
Manifold
1
OPEN
1
OPEN
Ball valve
2
CLOSE
Suction
port
Ball valve
High
pressure side
CLOSE
Vacuum pump
Connect
3
Hose
Connect
5
OPEN
Ball valve
6
Ball valve
CLOSE
10
Cylinder + Scale
RRDQ220V1
Liquid valve
CLOSE
V
DISCONNECT
CONNECT
4
12
Hose
HOW TO USE

10
RRDQ220V1
① Set each valve as above.
② Set Auto Shut-o/Manual Mode Setting to [Auto Shut-o] position.
* WhenusingtheAuto Shut-offmode,SuctionPressuremust behigherthan
atmosphericpressureforoperation.
③ Set the Power Switch to [ON] position.
Push Start Switch once.
④ Open the suction hose ball valve from the manifold slowly so as not to raise Suction Pressure
suddenly.
⑤ The unit automatically stops when Suction Pressure becomes -0.03MPa (psi).
⑥ Close the suction hose ball valve.
⑦ Set Power Switch to [OFF] position.
⑧ Close high pressure side of the manifold and liquid valve of the cylinder to be recycled.
3)Recycleprocedure
Operationtime
Suction Discharge
OPEN
Liquid valve
OPEN
CLOSE
Vapor valve
Cylinder Manifold
OPEN
Ball valve
OPEN
Suction Valve
RECYCLE
Switching Valve
OPEN
Discharge Valve
OPEN
CLOSE
8
CLOSE
8
CLOSE
Low
pressure side
High
pressure side
OFF
Power
O N
Start
OFF
Power
O N
Auto
Shut-off
Manual
Auto Shut-off
2
ON
3
OFF
7
kg
MED
RESOLUTION
Cylinder + Scale
RRDQ220V1
CLOSE
Vapor valve
Liquid valve
CLOSE
CLOSE
Ball valve
SLOWLY
OPEN
4
CLOSE
6
OPEN
Ball valveBall valve
Auto Shut-off
2
◆ Warmuptheunitwhenambienttemperatureisunder10℃ .
Refertopage16"WarmUpOperation"
◆ Ascalemustbeusedtopreventoverllingofcylinder.
CAUTION
◆ Whentheoperationtimeoftheunithaspassed20hourswithAutoStopTimer,theunit
stopsautomaticallytomaintaintherecycleperformance.
◆ ReplaceMolecular SieveReplacementKitand Filteraccordingtothe following
procedure.
① Press Reset Key of Auto Stop Timer once to cancel the automatic stop.
② Close the valve of the manifold and remove the refrigerant in the unit by operating.
[Recycle → Purge operation].
③ Replace Molecular Sieve Replacement Kit and Filter.
④ Restart recycle operation after pressing Reset Key of Auto Stop Timer.
Caution (for Timer)
HOW TO USE

11
Refrigerant Recycle Equipment
■ Prepare the following accessories in advance. (Optional accessories)
■ Warm up
OperationprocedureofR134arecycle
Operationtime
Suction Discharge
OPEN
CLOSE
Low
pressure side
High
pressure side OPEN
Suction Valve
RECYCLE
Switching Valve
CLOSE
Discharge Valve
OPEN
5
OPEN
Liquid valve
CLOSE
Vapor valve
Cylinder Manifold
OPEN
Ball valve
OFF
Power
O N
Start
ON
3
kg
MED
RESOLUTION
Cylinder + Scale
RRDQ220V1
OPEN
8
CLOSE
Vapor valve
Liquid valve
CLOSE
SLOWLY
OPEN
6
CLOSE
Ball valve
At 0.2MPa (29psi)
Maintain
4
START
Liquid Charge Adapter 1/4”
Filter
Auto Shut-off
2
Auto
Shut-off
Manual
● In case of recycling R134a, the eciency of the heat exchanger in Oil Separator is not adequate
even if the ambient temperature is 10℃ or higher.
Liquid R134a accumulates in Oil Separator and the full tank sensor unit.
● Connect Liquid Charge Adapter 1/4" (A) and Filter (B) between the suction hose and the manifold
center port.
● Warm up the unit every time regardless of temperature. (Refer to page 16 "Warm Up Operation".)
● If the pressure of the recycled R134a is low (if the temperature is low), warm the R134a in the
cylinder with a heater to increase the pressure.
(A) Code No. Y41123 Liquid Charge Adapter 1/4 " 1 piece
(B) Code No. TF011 Filter 1 piece
■ Operation method
① Connect hoses as above after carrying out procedure on Page 9 " 2) Evacuation of the recycle
unit and the hoses".
② Set Auto Shut-o/Manual Mode Setting to [Auto Shut -o] position.
③ Set Power Switch to [ON] and press Start Switch once.
④ Adjust Suction Pressure between 0.1MPa (14.5psi) ~ 0.2MPa (29psi) by opening the suction hose
ball valve from the manifold and keep operating until discharge pressure becomes 1.0MPa (145psi).
HOW TO USE

12
RRDQ220V1
⑤ After ④ , turn Suction Valve (V1) to [OPEN] position.
⑥ Open the suction hose ball valve from the manifold slowly for approximately 20 seconds.
⑦ Follow usual recycle procedure.
■ Note (
CAUTION
)
(1) R134a has a high boiling point and is harder to gasify than R410A.
Avoid working in a low temperature environment as much as possible.
(2) Even if the normal recycling procedure is performed after a warm-up operation, if the oil tank
full sensor stops the procedure, reduce Suction Pressure to less than 0.2MPa (29psi) to prevent
R134a from accumulating.
(3) The recycle speed of R134a is slower than R410A.
Adjust the timing to replace Molecular Sieve Replacement Kit considering the condition of
recycled R134a.
Press Reset Key of Auto Stop Timer at rst automatic stop to initialize the timer to replace
Molecular Sieve Replacement Kit, and Filter at the second automatic stop (40 hours).
(4) If the surface of Filter connected to the manifold becomes frozen during recycling and it
stops recycling, replace or clean Filter according to the following procedure and then restart
recycling:
1 - Set Auto Shut-o/Manual Mode Switch to [Auto Shut-o] and close the high pressure side
valve of the manifold.
2 - Close the suction hose ball valve from the manifold.
3 - Wait until the unit stops automatically.
4 - When the unit stops, carefully remove Filter. (Be careful of squirting liquid R134a.)
5 - Clean or replace Filter and Liquid Charge Adapter 1/4".
6 - Connect Filter and Liquid Charge Adapter 1/4" to the center port of the manifold.
7 - Connect the suction hose to Liquid Charge Adapter 1/4" and open the high pressure side valve
of the manifold and the suction hose ball valve from the manifold.
8 - Press Start Switch once to resume recycling.
HOW TO USE

13
Refrigerant Recycle Equipment
● Use the following procedure when refrigerant which becomes high pressure due to temperature
rise. Refer to page 10 "Recycle Procedure".
● Even if the cylinder is not full, if the inside pressure of the cylinder is high, replace it with an
evacuated spare cylinder.
■ Replacement of spare cylinder
RecycleProcedureWhenthePressureofRefrigerantisHigh
◆ Non-condensablesubstance(air)mayexistinthecylinderwhenthetemperatureofthe
cylinderrisesabnormallyduringrecycle.
Removetheairorreplacethecylinder.
CAUTION
③Reset Indicator
②Control Output
Indicator
⑧Mode Key
(Changes modes
and setting
items)
⑨Reset Key
(Resets present
value and
output)
⑤Time Unit
Indicators(h)
④Present Value
Display
⑥Set Value
Display
⑦
Set Value 1, 2
Indicator
Operation Key
⑩
Up Keys 1 to 4
⑪
Down Key 1 to 4
①Key Protect
Indicator
Use
Unused
Operation possible
● The timer measures [ON] time of
Power Switch and it is set to stop
automatically after 20 hours have
elapsed.
● The setting value is locked by Key
Protect, do not change it.
● The function of ● mark in right gure
is not used.
● ○ mark parts are used as a display
function.
● □ mark part is a function that can be
operated.
● When press Reset Key, measurement is
canceled and the display time returns to
[0 h].
※ For R410A, Molecular Sieve and Filter have to be replaced after every 20 hours operation.
※ For R32・R134a, Molecular Sieve and Filter have to be replaced every 40 hours operation.
At rst automatic stop after 20 hours operation, press Reset Key to restart the unit.
※ For R134a, adjust the timing to replace Molecular Sieve considering the condition of recycled
R134a.
DescriptionofAutoStopTimer
HOW TO USE

14
RRDQ220V1
① Setting up as the above drawing.
② Turn Switching Valve (V2) to [PURGE] position.
* Do not turn the valve during operation or Discharge Pressure Gauge may be damaged.
③ Set Auto Shut-o/Manual Mode Setting to [Auto Shut-o] position.
* When using the Auto Shut-o mode, the unit does not starts when Suction Pressure is lower than
atmospheric pressure.
④ Set Power Switch to [ON] position.
Push Start Switch once.
⑤ Turn Suction Valve (V1) slowly to [PURGE] position adjusting Suction Pressure to less than
0.2MPa.
⑥ Close the liquid port of the cylinder when the unit stops automatically.
⑦ Turn Discharge Valve (V3) to [CLOSE] position and close the discharge hose ball valve.
⑧ Set Power Switch to [OFF] position.
⑨ Disconnect the hoses.
* Vapor refrigerant remains in the recycle unit and the hose of the discharge side.
Connect the hose of the discharge side to an evacuated cylinder to recover all refrigerant in the
recycle unit and the hose.
4)RefrigerantDischarge(Purge)Procedure
Operationtime
Suction Discharge
rs.
of
t.
ed
kg
MED
RESOLUTION
Cylinder + Scale
OPEN
Liquid valve
CLOSE
Vapor valve
Cylinder Manifold
CLOSE
Ball valve
OPEN
Ball valve
Suction Valve
PURGE
Switching Valve
OPEN
Discharge Valve
2
CLOSE
CLOSE
Low
pressure side
High
pressure side
CLOSE
CLOSE
7
0.2MPa
PURGE
5
CLOSE
7
CLOSE
6
OFF
Power
O N
Start
OFF
Power
O N
ON
4
OFF
8
RRDQ220V1
CLOSE
Vapor valveLiquid valve
CLOSE CLOSE
Auto Shut-off
2
Auto
Shut-off
Manual
◆ Usesafetyglassesandleatherhandgloveswhenoperatingordisconnectinghoses.
Ifrefrigerantgastouchesyourskinorgetsintoyoureyes,itmaycausefrostbiteordamageyoureye
sight.
CAUTION
◆ AdjustSuctionPressurelessthan0.2MPainpurging.
Otherwise,itmaycausedamageonthecompressor.
CAUTION
A scale must be used to prevent
overfilling of cylinder.
HOW TO USE

15
Refrigerant Recycle Equipment
Discharge the oil when Tank Full Lamp is on ( ①~⑧)or after daily operation(⑤~⑧).
① Close the suction hose ball valve from the
manifold.
② In Auto Shut-o mode, start the unit by pushing
Force Start Switch.
* The switch will release unless you keep it
depressed.
③ The unit stops automatically
when Suction
Pressure reaches - 0.03MPa(- 4.4psi)
.
④ Set Power Switch to [OFF] position.
⑤
Adjust Suction Pressure between 0.1MPa
(14.5psi) ~ 0.2 MPa(29psi) by opening the
suction hose ball valve from the manifold.
⑥ Remove the cap of Oil Discharge Port on the
back of the unit.
⑦ Open the valve slowly and discharge the oil
into another container.
* The oil tank capacity is 2L.
⑧ Close the valve and cap of Oil Discharge Port
after discharging the oil.
Check every 100 hours of operation for any oil or contamination in the Electrostatic Filter System.
OilDischargeProcedure(OilSeparator)
OilDischargeProcedure(ElectrostaticFilterSystem)
Oil Discharge Port
for Oil Separator
Force Start Switch
Oil Discharge Port for
Electrostatic Filter System
① Adjust Suction Pressure between 0.1MPa
(14.5psi) ~ 0.2MPa (29psi) by opening the
suction hose ball valve from the manifold.
② Remove cap of Oil Discharge Port.
③ Open the valve slowly and discharge the oil
into another container.
④ Close the valve and cap of Oil Discharge Port
after discharging the oil.
HOW TO USE

16
RRDQ220V1
When the ambient temperature is under 10℃ , this unit needs a warm up operation to operate
eciently.
WarmUpOperation
Operationtime
Suction Discharge
Cylinder Manifold
OPEN
Liquid valve
CLOSE
Vapor valve
OPEN
Ball valve
OPEN
CLOSE
Low
pressure side
OPEN
High
pressure side
OPEN
Suction Valve
RECYCLE
Switching Valve
CLOSE
Discharge Valve
OPEN
5
OFF
Power
O N
Start
ON
3
kg
ME D
RESOLUTION
Cylinder + Scale
RRDQ220V1
CLOSE
Vapor valveLiquid valve
CLOSE
CLOSE
Ball valve
SLOWLY
OPEN
6
At 0.2MPa (29psi)
Maintain
4
Auto Shut-off
2
Auto
Shut-off
Manual
① Connect hoses as above after carry out Page 9 " 2) Evacuation of the recycle unit and the hoses"
② Set the Auto Shut-o/Manual Mode Setting to [Auto-Shut OFF] position.
③ Set Power Switch to [ON] position.
④ Adjust suction pressure around 0.2MPa(29psi)by opening the ball valve of the suction hose
from the manifold and keep operating until Discharge Pressure becomes 1.5 MPa(217.5psi).
⑤ After ④ , turn Discharge Valve (V3) to [OPEN] position.
⑥ Open the suction hose ball valve from the manifold slowly for approximately 20 seconds.
⑦ Follow usual recycle procedure.
A scale must be used to prevent
overfilling of cylinder.
HOW TO USE

17
Refrigerant Recycle Equipment
① Keep gauges and front panel clean by wiping with a clean cloth.
② Keep the air blow hole and condenser clean so as to cool down the condenser eciently.
MAINTENANCE&INSPECTION
Maintenance
● Inspect and clean regularly as instructed below and perform correction or replacement timely.
① Remove all refrigerant from the unit until
0MPa(psi).
② Open the lid of Dry Filter and remove Dry
Filter Cartridge and two O-rings in Dry
Filter Housing(G-85,P-24) and one O-ring in
Lid(P-80).
③ Open the lid of Dry Filter Cartridge and
remove Spring, Mesh Plate, and Filter.
④ Take out Molecular Sieve and two Filters in
the bottom.
Dry Filter Cartridge is installed at the back side of the unit.
● Replacement period
・ ・・R410A : Every 20 hours (every automatic stop by Auto Stop Timer)
・ ・ ・ R32・R134a : Every 40 hours (every other automatic stop by Auto Stop Timer)
● Replace Filter TF011 together with Molecular Sieve at the same time.
⑤ Prepare Molecular Sieve Replacement Kit
(AR338) and replace three Filters and
Molecular Sieve. Two O-rings will be replaced
later on.
⑥ Set Mesh Plate and Spring in Dry Filter
Cartridge and close the lid.
⑦ Properly set two new O-rings from AR338 on
Dry Filter Housing and put the refilled Dry
Filter Cartridge into the unit and close the lid
securely with the holding spring.
< Internal structure of Dry Filter Cartridge >
ReplaceMolecularSieveReplacementKit
Dry Filter
Cartridge
Two O-rings
in Dry Filter
Housing
One
O-ring
in Lid
Lid
CLOSE
OPEN
Mesh Plate
Mesh Plate
Filter
Filter
Molecular Sieve
Filter
Lid
Spring
Mesh Plate
◆ ReplacingMolecularSieve should bedonequicklyafter open thepackageto avoid
spoilingitsquality.
CAUTION
MAINTENANCE &
INSPECTION
⑧ Check for leakage, referring to page 19,
Conrmation of Leak.

18
RRDQ220V1
① Replace Molecular Sieve Replacement Kit
referring to page 17 after discharging oil
referring to page 15.
② Connect a vacuum pump to Oil Discharge Port
of Oil Separator.
③ Turn on the vacuum pump and open the valve
of Oil Discharge Port for Oil Separator.
④ After one hour evacuation, close the valve of
Oil Discharge Port for Oil Separator and turn
o the vacuum pump.
InCaseofRecycleOtherRefrigerant
Oil Discharge Port
for Oil Separator
Suction
port
Vacuum pump
Ball valve
OPEN
① Check damage on the plug and cord.
② Check for scratches or cracks on the outer surface of each hose.
③ Conrm that all gaskets on the hoses are worn or exhausted.
④ Conrm the unit starts normally when Power Switch is turned on.
⑤ Conrm the unit stops when Power Switch is turned o.
InspectioninGeneral
● Periodically inspect and clean the unit according to following.
Please correct or replace if necessary.
INSPECTIONBEFOREWORK
① Remove cap of Suction Port and Discharge Port.
② Turn Suction Valve (V1) to [OPEN] position.
Turn Switching Valve (V2) to [RECYCLE] position.
Turn Discharge Valve (V3) to [OPEN] position.
③ Set Power Switch to [ON] position.
Push Start Switch.
④ Conrm suction from Suction.
⑤ Conrm discharge from Discharge Port.
InspectionofRecyclefunction
Suction
4
Suction Port
Discharge
5
Discharge Port
MAINTENANCE &
INSPECTION
INSPECTION BEFORE
WORK

19
Refrigerant Recycle Equipment
① Remove cap of Suction Port and Discharge Port.
② Turn Suction Valve (V1) to [PURGE] position.
Turn Switching Valve (V2) to [PURGE] position.
Turn Discharge Valve (V3) to [OPEN] position.
③ Set Power Switch to [ON] position.
Push Start Switch.
④ Conrm Suction Pressure is under 0MPa.
⑤ Conrm no air ow from Discharge Port.
InspectionofPurgefunction
Under 0MPa
4
Suction Pressure
No air flow
5
Discharge Port
① Remove cap of Suction Port and Discharge Port.
② Turn Suction Valve (V1) to [OPEN] position.
Turn Switching Valve (V2) to [RECYCLE] position.
Turn Discharge Valve (V3) to [CLOSE] position.
③ Set Power Switch to [ON] position.
Push Start Switch.
④ After a while, High Pressure Shut-off function
makes the unit stop automatically and Warning
Lamp is turned on.
InspectionofHighPressureSwitchFunction
Lighting
4
Warning Lamp
Refrigerant Recycle Equipment
RR-220
RR-220
Refrigerant Recycle Equipment
Refrigerant Recycle Equipment
① Remove cap of Suction Port and Discharge Port.
② Turn Suction Valve (V1) to [OPEN] position.
Turn Switching Valve (V2) to [RECYCLE] position.
Turn Discharge Valve (V3) to [CLOSE] position.
③ Set Power Switch to [ON] position.
Push Start Switch.
④ After a while, High Pressure Shut-off function
makes the unit stop automatically and Warning
Lamp is turned on.
⑤ Leave this condition for 1 to 2 minutes and
conrm that there is no signicant pressure drop.
(Slight pressure decrease due to pressure balance
is normal.)
InspectionofLeak
Lighting
4
Warning Lamp
No pressure drop
5
Pressure gauge
INSPECTION BEFORE
WORK
Table of contents
Other Daikin Air Conditioner Accessories manuals

Daikin
Daikin RKD50GVMV User manual

Daikin
Daikin BYCQ140E2W1 User manual

Daikin
Daikin BYBCQ40HW1 User manual

Daikin
Daikin DZK Series User manual

Daikin
Daikin DTA119A71 User manual

Daikin
Daikin KPW5E112 User manual

Daikin
Daikin DP 14 Operating instructions

Daikin
Daikin K-KDU303KVE User manual

Daikin
Daikin EKMBDXB7V1 Guide

Daikin
Daikin BRR9B1V1 User manual
Popular Air Conditioner Accessories manuals by other brands

mundoclima
mundoclima OSK102 user manual

Mitsubishi Electric
Mitsubishi Electric PFR-12-18 How to Use / How to Install

Tecnosystemi
Tecnosystemi smart clima SCD600001 user manual

Toshiba
Toshiba RBC-UM11PGE installation manual

Lennox
Lennox 13U57 installation instructions

Mitsubishi Electric
Mitsubishi Electric PAC-RB01BC quick start guide