3
2. Specications
Ceiling suspended type
Model FXHQ12MVJU FXHQ24MVJU
Powersupply 1 phase, 60 Hz, 208/230 V 1 phase, 60 Hz, 208/230 V
H1, H3Coolingcapacity Btu/h 12,000 24,000
H2, H3 Heating capacity Btu/h 13,500 27,000
Casing/Color White(10Y9/0.5) White(10Y9/0.5)
Dimensions:(H × W ×D) in. 7-11/16 × 37-13/16 × 26-3/4 7-11/16 × 55-1/8 × 26-3/4
Coil(crossn
coil)
Rows × Stages × FPI 2 × 12 × 15 3 × 12 × 15
Face area ft² 1.96 3.15
Fan
Model 3D12K1AA1 3D12K2AA1
Type Siroccofan Siroccofan
Motoroutput W 62 130
Airowrate(H/L) cfm 410/340 710/600
Drive Direct drive Direct drive
Temperaturecontrol Microprocessorthermostatforcoolingand
heating
Microprocessorthermostatforcoolingand
heating
Soundabsorbingthermalinsulationmaterial Glasswool Glasswool
Airlter Resinnet(withmoldresistant) Resinnet(withmoldresistant)
H4Soundpressurelevel(reference
data)(H/L) dBA 42/38 44/42
Weight lbs 55 80
Piping
connections
Liquidpipes in. f1/4(areconnection) f3/8(areconnection)
Gas pipes in. f1/2(areconnection) f5/8(areconnection)
Drain pipe in. VP20(externaldia.1,internaldia.3/4) VP20(externaldia.1,internaldia.3/4)
Safety devices Fuse,Thermalprotectorforfanmotor Fuse,Thermalprotectorforfanmotor
Refrigerantcontrol Electronicexpansionvalve Electronicexpansionvalve
Connectableoutdoorunit R410AVRV series R410AVRV series
Standardaccessories
Operationmanual,Installationmanual,Drain
hose,Paperpatternforinstallation,Clampmetal,
Insulationfortting,Clamps,Washers
Operationmanual,Installationmanual,Drain
hose,Paperpatternforinstallation,Clampmetal,
Insulationfortting,Clamps,Washers
Note:
H1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB,67°FWB
Outdoortemperature:95°FDB
Equivalentrefrigerantpipinglength:25ft(horizontal)
H2. Nominalheatingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:70°FDB.
Outdoortemperature:47°FDB,43°FWB
Equivalentrefrigerantpipinglength:25ft(horizontal)
H3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.
H4. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofambientconditions.