4PEN584178-1.book Page 1 Wednesday, July 10, 2019 9:21 AM

Installation manual
1
EKRP1C13
Electric heater PCB kit
4P584178-1
Contents page
Content of kit EKRP1C13 ....................................................................................................................2
Name of parts ......................................................................................................................................2
Function possibilities............................................................................................................................3
Installation in unit .................................................................................................................................3
Electrical connections ..........................................................................................................................4
EKRP1C13 Electric heater PCB kit Installation manual
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES
COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER
DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY
DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT
AND HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR
DAIKIN DEALER FOR ADVICE AND INFORMATION.
All field wiring and components must be installed by a licensed electrician and must
comply with relevant local and national regulations.
The field wiring must be carried out in accordance with the wiring diagrams and the
instructions given below.
Take care not to bend the printed circuit board when inserting or removing the connectors.
4PEN584178-1.book Page 1 Wednesday, July 10, 2019 9:21 AM

EKRP1C13
Electric heater PCB kit
4P584178-1
Installation manual
2
Content of kit EKRP1C13
Name of parts
PCB
CN2
X1 X2 X3 X4
YC
Y1
Y4
Y3
Y2
CN1
F1U F2U
Electrical Heater PCB Kit
INSTALLATION MANUAL
1 Connector to indoor PCB
2 Pilot lamp connection
3 Hour meter connection
4 Electric heater connection
5 Electric heater control relay power supply
6 Fuses 5 A - 250 V
7 Humidifier connection
CN2
X1 X2 X3 X4
YC
Y1
Y2
Y3
Y4
CN1
F1U F2U
1
2
5
4
7
63
4PEN584178-1.book Page 2 Wednesday, July 10, 2019 9:21 AM

Installation manual
3
EKRP1C13
Electric heater PCB kit
4P584178-1
Function possibilities
■ Compressor operation indication
■ Indoor fan operation indication
■ Electrical heater connection
■ Humidifier connection
Installation in unit
Refer to the installation manual of the indoor unit or refer to the option handbook if the option can be
installed inside the unit.
In all other cases use an installation box to mount the EKRP.
Do not drill any holes in the casing of the unit to install the option.
Only use the accessories provided by Daikin to install the option.
4PEN584178-1.book Page 3 Wednesday, July 10, 2019 9:21 AM

EKRP1C13
Electric heater PCB kit
4P584178-1
Installation manual
4
Electrical connections
■ Power supply connection
■ Communication line
Do not bundle low and high voltage wires together. Bundle all wires with the included
clamps in order to avoid contact with indoor PCB's or sharp edges.
CN2
X1 X2 X3 X4 CN1
F1U F2U
PCB
NL321
X35A
X21A
X27A
X11A
X10A
X1 X2 X3 X4 CN1
F1U F2U
CN2
X33A for all Sky Air units
4PEN584178-1.book Page 4 Wednesday, July 10, 2019 9:21 AM

Installation manual
5
EKRP1C13
Electric heater PCB kit
4P584178-1
■ Connection of hour meter
■ Connection of operation lamp
1PCB
2 Power supply for hour meter (3 A - 250 V AC/0.3 A - 110 V DC)
3 Hour meter
4 Compressor
HM
X
1
X
2
3
4
1
2
1PCB
2 Power supply for operation lamp (3 A - 250 V AC/0.3 A - 110 V DC)
3 Operation lamp
4Fan
X
3
X
4
3
4
2
1
4PEN584178-1.book Page 5 Wednesday, July 10, 2019 9:21 AM

EKRP1C13
Electric heater PCB kit
4P584178-1
Installation manual
6
■ Electrical connection of electric heater
1 Main PCB
2 Optional PCB
3 Main terminal (1-3) (230 V - 50 Hz)
Field supply:
4 Thermal fuse (Max. 110°C): to protect the installation
from accident (e.g. fire) when a malfunction occurs.
5 Thermal protector: to protect the electric heater for
overheating.
6 Relay (Max. 550 VA)
7 Heater
t° t° t° t° t° t°
LN L1L1 L2L2 L3
~2~ 3~
t° t° t°
L1 L2 L3
3N~
N
CN2
X
1
X
2
X
3
X
4
YC
Y
1
Y
2
Y
3
Y
4
CN1
3
4
1
2
7
6
5
4PEN584178-1.book Page 6 Wednesday, July 10, 2019 9:21 AM

Installation manual
7
EKRP1C13
Electric heater PCB kit
4P584178-1
Important installation caution
The heater should be installed according to local regulations and must comply with
EN60335-2-40.
A thermal fuse should be installed on the heater so that there is no danger of damage to
the heater and no safety risk when the fan is stopped or when the PCB is malfunctioning.
The electric heater must be installed on a safe location in the discharge duct, so that there
is no danger for damage to the unit.
Maximum temperature in the discharge duct may not exceed 90°C. Select the proper
safety device or thermal protector accordingly.
Temperature on the unit casing may not exceed 70°C.
Maximum heater capacity to be installed:
20~35 class 2 kW 71~90 class 5 kW 200 class 12 kW
35~63 class 3 kW 100 class 7 kW 250 class 16 kW
125 class 9 kW
4PEN584178-1.book Page 7 Wednesday, July 10, 2019 9:21 AM

EKRP1C13
Electric heater PCB kit
4P584178-1
Installation manual
8
■ Electrical connection of humidifier (control by 1 humidifier adjustment switch)
indoor 1
CN2
SS1
X
1
X
2
X
3
X
4
YC
Y
2
Y
4
Y
3
Y
1
CN1
indoor 2
CN2
SS1
X
1
X
2
X
3
X
4
YC
Y
2
Y
4
Y
3
Y
1
CN1
indoor 3
CN2
SS1
X
1
X
2
X
3
X
4
YC
Y
2
Y
3
Y
4
Y
1
CN1 HU
HU HU
A
YC
Y
2
Y
3
Y
4
Y
1
B
HU
RY
1
2
7
4
6
4
6
5
33
4
1
2
7
3
4
1
2
7
1Main PCB
2 Optional PCB
3 Main terminal (1-3) (230 V - 50 Hz)
Field supply:
4 Humidifier HU (YC-Y2) min. 20 mA-125 V AC, max. 1 A-250 V AC
5 Relay RY (YC-Y4) max. 400 mA-250 V AC (only required in case B)
case A: (YC-Y3) min. 200 V AC, max. 2 mA
case B: Humidifier adjustment switch current >2 mA
Current of RY must be lower than current of the humidifier adjustment switch.
6 Humidifier adjustment switch
7 SS1 - ON/OFF switch: Set the switch to ON for enabling humidifier control.
4PEN584178-1.book Page 8 Wednesday, July 10, 2019 9:21 AM

Installation manual
9
EKRP1C13
Electric heater PCB kit
4P584178-1
■ Remote control settings
Installation
■ Do not bundle low and high voltage wires together.
■
Bundle any excess wires with the attached tie wraps to keep loose wirings off the indoor unit PCB.
Mode No. Setting First code No. Second code No.
15(25)
Operate the humidifier during heating
mode if suction air temperature is more
than 20°C (also in thermostat off
condition).
102
Operate humidifier and drainpump. 3 01
PCB support
PCB support
Adaptor
Adaptor
4PEN584178-1.book Page 9 Wednesday, July 10, 2019 9:21 AM

4PEN584178-1.book Page 1 Wednesday, July 10, 2019 9:21 AM

4P584178-1
4PEN584178-1.book Page 1 Wednesday, July 10, 2019 9:21 AM
Table of contents
Other Daikin Electric Heater manuals
Popular Electric Heater manuals by other brands

DeLonghi
DeLonghi 634 operating instructions

Harvia
Harvia HPC1104XE Instructions for installation and use

Vornado
Vornado Automatic Vortex Heat AVH2 owner's guide

Argo
Argo MINIMAL operating instructions

Airchaud Diffusion
Airchaud Diffusion Haverland HL WI5S/C Instruction and installation manual

Trotec
Trotec IR 1500 SC operating manual