manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Control Unit
  8. •
  9. Danfoss KP 1 User manual

Danfoss KP 1 User manual

This manual suits for next models

4

Other Danfoss Control Unit manuals

Danfoss VHX-DUO Installation instructions manual

Danfoss

Danfoss VHX-DUO Installation instructions manual

Danfoss AMER 230 V User manual

Danfoss

Danfoss AMER 230 V User manual

Danfoss MSV-F2 DN Series User manual

Danfoss

Danfoss MSV-F2 DN Series User manual

Danfoss EKC 102D User manual

Danfoss

Danfoss EKC 102D User manual

Danfoss PVG 100 User manual

Danfoss

Danfoss PVG 100 User manual

Danfoss ICM 20 User manual

Danfoss

Danfoss ICM 20 User manual

Danfoss PM 5-65 User manual

Danfoss

Danfoss PM 5-65 User manual

Danfoss MSV-C User manual

Danfoss

Danfoss MSV-C User manual

Danfoss AB-QM Series User manual

Danfoss

Danfoss AB-QM Series User manual

Danfoss ASV-PV User manual

Danfoss

Danfoss ASV-PV User manual

Danfoss AB-QM DN 125 User manual

Danfoss

Danfoss AB-QM DN 125 User manual

Danfoss PVG 32 Manual

Danfoss

Danfoss PVG 32 Manual

Danfoss PVG 120 Manual

Danfoss

Danfoss PVG 120 Manual

Danfoss MSV-F Plus DN 15 User manual

Danfoss

Danfoss MSV-F Plus DN 15 User manual

Danfoss MBC 5000 User manual

Danfoss

Danfoss MBC 5000 User manual

Danfoss AB-QM series User manual

Danfoss

Danfoss AB-QM series User manual

Danfoss AK-CC 550A Instruction Manual

Danfoss

Danfoss AK-CC 550A Instruction Manual

Danfoss PVG 100 Building instructions

Danfoss

Danfoss PVG 100 Building instructions

Danfoss AVTB User manual

Danfoss

Danfoss AVTB User manual

Danfoss VLT 380-500 V Guide

Danfoss

Danfoss VLT 380-500 V Guide

Danfoss DSV 1 User manual

Danfoss

Danfoss DSV 1 User manual

Danfoss AK-SM 800A User manual

Danfoss

Danfoss AK-SM 800A User manual

Danfoss EVR 2 User manual

Danfoss

Danfoss EVR 2 User manual

Danfoss SCA-X User manual

Danfoss

Danfoss SCA-X User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

MOTECK CB4M-S user guide

MOTECK

MOTECK CB4M-S user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Installation Guide
Pressure Control
Types KP 1, KP 2, KP 5, KP 7W, KP 7B
© Danfoss A/S (AC-MCI / jmn), 2012-11 DKRCC.PI.C00.E1.22 / 520H6070 1
060R9746
060R9746
Refrigerants
Auto reset:
KP 1, KP 2, KP 5, KP 7W
Manual reset:
KP 1, KP 5, KP 7B
HCFC and non-ammable HFC
Mounting
CAUTION:
Do not mount the control in a position where dirt,
sediment or oil will aect the operation of the control.
CAUTION:
Do not install these controls on ammonia systems.
Mounting requirements Ambient temperatures
t1 min. KP 1, KP 2, KP 5: -40 °F (-40 °C)
t1 min. KP 7: -13 °F (-25 °C)
t1max.: 149 °F (65 °C)
Test pressure (Ptest)
Enclosure
max. 1/8in.
(3 mm)
B: Enclosure: ~NEMA 1A: 10 – 32 UNC Threads
CAUTION:
The mounting panel must be plane to avoid damage of control.
Connections
Ptestmax.:
KP 1, KP 2: 285 psig (20 bar pe)
KP 5, KP 7: 510 psig (35 bar pe)
KP 2: 174 psig (12 bar pe)
Bellows Bellows
2 DKRCC.PI.C00.E1.22 / 520H6070 © Danfoss A/S (AC-MCI / jmn), 2012-11
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock
or damage to equipment. Do never touch live parts with your ngers or with any tool.
Wiring
All wiring should conform
to the National Electrical Code
and local regulations.
Terminal block
CAUTION:
Use terminal screws furnished
in the contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.
Contact load ratings
Load Option A
CUT-OUT on pressure drop
Wire terminals 1-4:
CUT-IN = High Set Point (HSP)
see “Setting”
CUT-OUT = Low Set Point (LSP)
see “Setting”
Load Option B
CUT-OUT on pressure rise
Wire terminals 1-2:
CUT-IN = Low Set Point (LSP)
see “Setting”
CUT-OUT = High Set Point (HSP)
see “Setting”
Example:
CUT-IN = 30 psig
CUT-OUT = 10 psig
This means :
CUT-IN = HSP = 30 psig
CUT-OUT = LSP = 10 psig
Example:
CUT-IN = 250 psig
CUT-OUT = 350 psig
This means :
CUT-IN = LSP = 250 psig
CUT-OUT = HSP = 350 psig
Bellows movement
on pressure rise
The free terminal can be
used for signal purpose.
120 V a.c. 16 FLA, 96 LRA
240 V a.c. 8 FLA, 48 LRA
240 V d.c. 12 W pilot duty
Terms 1-4 close on pressure rise
Terms 1-4 open on pressure drop
Terms 1-2 close on pressure drop
Terms 1-2 open on pressure rise
Bellows movement
on pressure drop
Note:
Note:
KP 1, man. reset is possible only
after a pressure rise
of 10 psi (0.7 bar). KP 5 and KP 7B,
man. reset is possible
only after a pressure drop
of respectively 43 psi (3.0 bar)
and 58 psi (4.0 bar)
Note:
KP 1, KP 5 and KP 7B with man. reset:
Push manual reset knob during
manual tripping.
TRIP (main lever)
use FINGERS ONLY!
(Do NOT use screwdriver)
To resume control operation
after safety cutout,
push reset knob as indicated.
Adjustment spindle(s) location
Type Dierential
KP 1 10 psi (0.7 bar)
KP 5 43 psi (3 bar)
KP 7B 58 psi (4 bar)
Auto reset KP 1, KP 2, KP 5, KP 7W
Manual reset KP 1, KP 5, KP 7B
A: Range
B: Dierential
A: Range
B: Dierential
Manual trip function
(Electrical contacts / wiring test)
Manual reset
1
2
1
2
© Danfoss A/S (AC-MCI / jmn), 2012-11 DKRCC.PI.C00.E1.22 / 520H6070 3
Manual reset KP 1, KP 5, KP 7B
Setting
(see also “Wiring”)
KP 1 (auto reset), KP 2, KP 5, KP 7W, KP 7B
1. Adjust range spindle to desired HIGH SET POINT (HSP)
2. Adjust dierential spindle to desired DIFFERENTIAL (DIFF.)
1. Adjust range spindle to desired LOW SET POINT (LSP)
2. DIFFERENTIAL is xed Value printed on scale plate
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example: Example:
LOW SET POINT plus DIFFERENTIAL equals HIGH SET POINT
KP 1 (manual reset ONLY)
HSP – DIFF. = LSP
30 psig – 20 psi = 10 psig
(2.1 bar) (1.4 bar) (0.7 bar)
LSP + DIFF. = HSP
12 psig + 10 psi = 22 psig
(0.8 bar) (0.7 bar) (1.5 bar)
If terminals 1-4 are used: CUT-IN = HSP
CUT-OUT = LSP
If terminals 1-2 are used: CUT-IN = LSP
CUT-OUT = HSP
Note:
KP 5 (manual reset) and KP 7B have xed di.
Value printed on scale plate.
Adjustment
Note:
Remove lockplate before adjustment.
Replace lockplate after adjustment (if desired).
See instruction printed on top of control
KP 1: 3 psi (0.2 bar)/rev.
KP 2: 1.5 psi (0.1 bar)/rev.
KP 5: 4 psi (0.3 bar)/rev.
KP 7W: 7 psi (0.5 bar)/rev.
Range
Increase
360°
Decrease
360°
Increase
360°
Decrease
360°
6 mm
(15/64 in.)
Dierential
KP 1: 10 psi (0.7 bar)/rev.
KP 2: 7 psi (0.5 bar)/rev.
KP 5, 7W, 7B: 33 psi (2.3 bar)/rev.