EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Measuring Instrument
  8. •
  9. Danfoss VLT User manual

Danfoss VLT User manual

Other manuals for VLT

7

Other Danfoss Measuring Instrument manuals

Danfoss SonoMeter 30 User manual

Danfoss

Danfoss SonoMeter 30 User manual

Danfoss AKS 4100 User manual

Danfoss

Danfoss AKS 4100 User manual

Danfoss SonoMeter 30 User manual

Danfoss

Danfoss SonoMeter 30 User manual

Danfoss WS 403 Manual

Danfoss

Danfoss WS 403 Manual

Danfoss Infocal 9 Operation manual

Danfoss

Danfoss Infocal 9 Operation manual

Danfoss SonoSensor 30 Operation manual

Danfoss

Danfoss SonoSensor 30 Operation manual

Danfoss SonoSafe Operation manual

Danfoss

Danfoss SonoSafe Operation manual

Danfoss MAGFLO MAG 1100 User manual

Danfoss

Danfoss MAGFLO MAG 1100 User manual

Danfoss Vickers Target-Pro 2 User manual

Danfoss

Danfoss Vickers Target-Pro 2 User manual

Danfoss ADAP-KOOL AK-LM 340 User manual

Danfoss

Danfoss ADAP-KOOL AK-LM 340 User manual

Danfoss PFM 5001 User manual

Danfoss

Danfoss PFM 5001 User manual

Danfoss SonoSelect 10 Operation manual

Danfoss

Danfoss SonoSelect 10 Operation manual

Danfoss AKS 4100 User manual

Danfoss

Danfoss AKS 4100 User manual

Danfoss SonoMeter 30 Operation manual

Danfoss

Danfoss SonoMeter 30 Operation manual

Danfoss SonoSelect User manual

Danfoss

Danfoss SonoSelect User manual

Danfoss PR-SC4K Direct User manual

Danfoss

Danfoss PR-SC4K Direct User manual

Danfoss PFM 100 User manual

Danfoss

Danfoss PFM 100 User manual

Danfoss Micromon User manual

Danfoss

Danfoss Micromon User manual

Danfoss PR-OCTO User manual

Danfoss

Danfoss PR-OCTO User manual

Danfoss 40 User manual

Danfoss

Danfoss 40 User manual

Danfoss SonoCollect 110 User manual

Danfoss

Danfoss SonoCollect 110 User manual

Danfoss AK-LM 350 Guide

Danfoss

Danfoss AK-LM 350 Guide

Danfoss SONO 3500 CT User manual

Danfoss

Danfoss SONO 3500 CT User manual

Danfoss PFM 1000 User manual

Danfoss

Danfoss PFM 1000 User manual

Popular Measuring Instrument manuals by other brands

Suaoki D40 user manual

Suaoki

Suaoki D40 user manual

Elster BK-G1.6 operating instructions

Elster

Elster BK-G1.6 operating instructions

Endress+Hauser Deltabar FMD71 technical information

Endress+Hauser

Endress+Hauser Deltabar FMD71 technical information

Duratool D03128 manual

Duratool

Duratool D03128 manual

Vega VEGAPULS 65 Quick setup guide

Vega

Vega VEGAPULS 65 Quick setup guide

Tonghui TH2618B Operation manual

Tonghui

Tonghui TH2618B Operation manual

Tenmars TM-801 user manual

Tenmars

Tenmars TM-801 user manual

MSR 145 user manual

MSR

MSR 145 user manual

TPS WP-82 manual

TPS

TPS WP-82 manual

PCB Piezotronics 003C30 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 003C30 Installation and operating manual

Tenma 72-10465 manual

Tenma

Tenma 72-10465 manual

Endress+Hauser Proline Promag 50 Brief operating instructions

Endress+Hauser

Endress+Hauser Proline Promag 50 Brief operating instructions

Siemens SITRANS F Coriolis FCT030 Function manual

Siemens

Siemens SITRANS F Coriolis FCT030 Function manual

KLINGER CMF V Series instruction manual

KLINGER

KLINGER CMF V Series instruction manual

Keysight M8290A Getting started guide

Keysight

Keysight M8290A Getting started guide

Acterna MS1400 Operation manual

Acterna

Acterna MS1400 Operation manual

R&S ZPH manual

R&S

R&S ZPH manual

Datacolor ColorReader DC10-2 user guide

Datacolor

Datacolor ColorReader DC10-2 user guide

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

The perfect solution for
•Intelligent control
•HVAC system protection
•Remote status reporting
The VLT® HVAC Drive provides a new No-Flow detection feature
for pump systems. This feature is useful for detecting conditions
where a pump is producing no flow – a condition that can cause
pump damage if not detected and corrected.
No flow based on motor
power and frequency
No-Flow Detection is based on the
measurement of power at specific
motor speeds. The drive monitors
actual power and motor frequency
and compares it to the calculated
no-flow power at specific speeds.
If the power measured at a specific
frequency is greater than the no-flow
power calculated by the drive, the
pump is producing flow. If the power
measured is less than the no-flow
power calculated by the drive, a
warning or alarm is generated to
notify the operator of the condition.
To determine the no-flow power level
throughout the speed range, the
drive generates a power vs. frequency
curve that represents the no-flow
condition. This curve is generated by
the drive from two data points. These
power/frequency points can be
entered into the drive automatically
or manually.
Manual or Auto Set Up are available
The Auto Set Up automatically steps
the user through the commissioning
process, storing the data measured.
When the automatic set-up is selected
the output frequencies used are 50%
and 85% of maximum. Manual set-up
can be used when a different pair of
frequencies is desired.
Programming is quick and easy
The drive software makes program-
ming the No-Flow feature quick and
easy by choosing Pump Functions
and then No-Flow Function under the
Quick Menu.
Features Benefits
Eliminates an external differential
pressure switch or flow meter Reduce installation and maintenance cost
Eliminates wiring for external sensors Reduce installation and maintenance cost
A warning or alarm can alert operator
of the problem Provides proper operation of equipment and
increases occupant comfort
Programming is quick and easy with
pre-programmed software Saves time and increases reliablity
VLT® No Flow Feature
Danfoss Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80, www.danfoss.com/drives • E-mail: info@danfoss.com
MF004A02 VLT® is a trademark of Danfoss A/S Produced by KKM 2007.10
Programming for No-Flow detection
is simplified with a number of para-
meters that are pre-programmed into
the drive. Prior to programming this
feature, commission the drive by
using the parameters in the Quick
Menu Q2 Quick Set-Up. Then perform
the following steps for programming
No-Flow detection:
Par.# Description
Settings
Comments
Factory
setting Recommended
setting
22-20 Low Power Auto Set-up Disable Enable Close the outlet valve for the pump before starting Auto Set-up. Select Enable
and follow the instruction on the LCP. After Auto Set-up is complete, open the
pump outlet valve.
The following parameters are accessed through the Main Menu and will be stored after pressing the [OK] key to save the results after the auto-tuning
22-33 Low Speed
[Hz] When Low Power Auto Set-up is used, 50% of the drive’s maximum frequency
will be stored here. This can be manually edited, if desired.
22-34 Low Speed Power [kW] When Low Power Auto Set-up is used, the output power measured under
no-flow conditions at 50% speed will be stored here. This can be manually
edited, if desired.
22-37 High Speed
[Hz] When Low Power Auto Set-up is used, 85% of the drive’s maximum frequency
will be stored here. This can be manually edited, if desired.
22-3 High Speed Power [kW] When Low Power Auto Set-up is used, the output power measured under
no-flow conditions at 85% speed will be stored here. This can be manually
edited, if desired.
These parameters are used after Auto Set-up and the No-Flow feature is operating
22 - 30 No-Flow Power When the drive is running, this parameter will show the power level that will
be interpreted as producing no flow at the current motor speed.
22 - 31 Power Correction
Factor 100% 110% This parameter is used to raise or lower the no-flow power curve to the
percentage entered here. Values above 100% help ensure the drive reliably
detects no-flow.
The following parameters determine the action that the drive will take if a no flow condition is detected
22-21 Low Power
Detection Disable Enable To activate no-flow based on power
22-23 No-Flow Function Off Sleep Mode/
Warning/Alarm Select action
22-24 No-Flow Delay 10 sec. Set the time delay before the drive will perform the No-Flow Function.
Generally set longer than the decel ramp time.
The following parameters give and indication to a BMS if a no flow condition is detected
5-40 Function Relay [190] No-Flow Program one of the relays to selection [190], No-Flow. The selected relay will
be activated when No-Flow occurs.
Digital Output [190] No-Flow A digital output can be used to indicate a no flow condition. Use the
parameter that sets the function of the desired digital output.
The following are used if No-Flow is reported via serial communications
Protocol Warning Word
BACnet BV:77 No Flow
LonWorks nvoWarningword Bit 37
Modbus RTU TU Register 16930 Bit 6 = 1
Programming No-Flow detection