Danfoss 103E7 Assembly Instructions

103E7
Installation & User Instructions
including Factory Replacement Units (FRU)
7-day electronic
timeswitch for controlling
hot water and heating
http://waterheatertimer.org/Woods-timers-and-manuals.html#TE22
More timers and manuals:

2
INDEX
Index
Installation
Product specification 3
Installation 4-6
Wiring 6-9
Replacement 10-11
User
Your timeswitch 12
Resetting the unit 12
24hr or AM/PM display 13
Setting the Time and Day 13
Factory preset programmes 14
Changing the preset programmes 15
Setting the programme - 7 day 16-17
Setting the programme - 5/2 day 18-19
Running your programme 20
Temporary user overrides 21
Changing clocks forward/back 22
Battery backup 23
Contact details 24

3
Please Note:
This product should only be installed by a qualified
electrician or competent heating installer, and
should be in accordance with the current edition of
the IEEE wiring regulations.
Specification
Power supply 230Vac ± 15%, 50 Hz
Switching action 1 x SPST, Type 1B
Switch rating 264Vac, 50/60Hz, 3(1)A
Setting/Running Accuracy ±1 min./month
Power Reserve Minimum 24 hours
Enclosure Rating IP30
Max. Ambient Temperature 45°C
Dimensions, mm (W, H, D) 102 x 136 x 47
Design standard EN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test 75°C
Product specification
Specification
Installation Instructions

4
Installation
NB. For FRU units - go straight to point 6 below.
1. Loosen the fixing screw in the base of the unit to release
the Wiring Cover.
2. Holding the unit face downwards, press firmly in the
centre of the wallplate and slide it apart and lift it from
the module.
3. Fix the wallplate and terminal block to the wall, or
plaster box, as required. Ensure that the screw heads
do not protrude beyond the vertical centre rib of the
wallplate, or this will prevent the module correctly
locating onto the wallplate.
4. Surface cables can only enter from below the unit. Cut
an appropriate cable aperture in the wiring cover. If the
wallplate is mounted on a plaster box, cables can enter
from the rear below the terminal block.
Installation
Screw fixing holes
(screwheads MUST
NOT protrude
above centre rib) Vertical centre rib
Wallplate & Terminals

5
5. Electrical connections are simplified by using a Wiring
Centre. However, if this is not used, the wallplate
terminal identification is as shown.
If the system being controlled is 230 Vac, then
terminals 3 and L must be linked with insulated cable
capable of carrying full load current. Whilst the unit
does not require an earth connection, a terminal is
provided on the wallplate for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect
the unit as shown.
7. Find out from the user whether the unit is required to
operate in 7-day mode (factory preset) or weekday/
weekend mode (5/2 day). To convert to 5/2 day
mode remove the small two-way connector from the
pins towards the left of the recess on the rear of the
module, then press the button marked R/S under the
flap to RESET the unit.
8. Ensure all dust and debris are cleared from the area.
Plug the module into the wallplate by locating it onto
the wallplate and, when flush with it, sliding it down,
ensure the hook at the top of the wallplate engages
with the slot at the back of the module.
9. Before setting the programme, check the unit and
circuit. Press the SELECT button until the bar in the
display lines up with the word ON. Adjust the remote
thermostats to check the system operates correctly.
Installation
Load Mains Supply
(via 3 amp fuse)
ON SPARE COM NL
123 5 6

6
103, 103E5
Wiring
Wiring
10. Then press the SELECT button until the bar lines up
with the word OFF and check the system does not
operate.
11. When the circuit check has been completed, replace
the wiring cover and tighten the fixing screw. Cut
any cable aperture in the wiring cover which may be
necessary to accommodate surface mounted cables.
12. Finally set time of day and programmes required,
noting that the unit is supplied with a pre-set
programme, as stated on Page 14.

7
12356
L
NMAINS
SUPPLY
FUSED
3 AMP
L N
COM CALL
ROOM
'STAT
N
LINK
PUMP
TERMINALS
103E5
TERMINALS
L N L N
COM CALL
N
ROOM
'STAT L
N
BOILER
TERMINALS PUMP
TERMINALS
LINK
103E5
TERMINALS
MAINS
SUPPLY
FUSED
3 AMP
123 56
Wiring
Typical Gravity DHW with pumped heating
Typical control of Pump for Central Heating on a
Solid Fuel System
103E7
TERMINALS
103E7
TERMINALS

8
12356
103E5
TERMINALS
L
N
LOAD
MAINS
SUPPLY
FUSED
3 AMP
LOW
VOLTAGE
SUPPLY
COM CALL
LOW
VOLTAGE
ROOM
'STAT
COM CALL
N
ROOM
'STAT
L N BOILER
TERMINALS L N PUMP
TERMINALS
L
N
103E5
TERMINALS
MAINS
SUPPLY
FUSED
3 AMP
123 56
LINK
Wiring
Typical Heating Only system, Boiler and Pump
control
Typical control of Low Voltage System requiring
voltage free contacts
103E7
TERMINALS
103E7
TERMINALS

9
103E5
TERMINALS
123 56
MID-POSITION VALVE L N
L
NMAINS
SUPPLY
FUSED
3 AMP
BOILER &
PUMP
TERMINALS
RED OR
ORANGE
WHITE
OR
BROWN BLUE GREY
ROOM
'STAT CYL.
'STAT
SAT CALL
COM
N
LINK
123 56
COM CALL
N
ROOM
'STAT
INPUT OUTPUT NL
L
N
103E7
TERMINALS
MAINS
SUPPLY
FUSED
3 AMP
COMBI BOILER
TERMINALS
Wiring
Typical control of Heating when provided by
Combination type Boiler (see note below)
Typical Heating & Hot Water control system usuing 3
port mid-position valve
103E7
TERMINALS
103E7
TERMINALS
Note: Connection must only be made if input/output of boiler are
230V signals

10
DANFOSS
RANDALL
103E7
LOAD MAINS SUPPLY
(via 3 amp fuse)
An additional terminal block is
required where these discon-
nected leads (or pairs of leads)
should be terminated
ON SPARE COM
1 2 3 5 (N) 6 (L) A B C D
RANDALL 103, 103E,
103E7 123 56
RANDALL 3020 4 2 - 1,7 6 3 5
RANDALL TSR2 5 4 1 3 2 6 7
GRASSLIN 45, 45A, 45E 4 - 3 2 1
HORSTMANN 424
EMERALD & PEARL
AUTO RANGE
423 NL,15
HORSTMANN 423
PEARL, EMERALD &
TOPAZ
413 NL256
SANGAMO S254 Form 2,
S408 Form 5,
S251 Form 2
LOAD - - N L
SANGAMO S610 F2,
S611 F2, S612 F2, S408
F4, S408 F6, S253 F2,
S255 F2
LOAD - SWITCH
LIVE NMOTOR
LIVE
Replacement

11
SANGAMO S409 Form 8 2 1 6 3,N 5,L
SANGAMO/RANDALL
SET 1 425 NL
SMITHS IND. MKI, MKII P3 P1 P2 N L
SMITHS IND.
CENTROLLER 30 4,5 3 - 1 2 6
SMITHS IND.
CENTROLLER 40 4,5 3 - 1 2
SWITCHMASTER 300 1 2 4 N L 3
TOWERCHRON TC 7 3 4 2 1 8 9 10 11
VENNER VENNERETTE
MKIIA LOAD - LINE N L
VENNER VENNERETTE
MKIVA 1-4 23
VENNER VENNERON
VENNERON P 4-1 32
Replacement

12
User Instructions
Your timeswitch
Your 103E7 timeswitch allows you to switch your heating
and hot water on and off at times that suit you.
The 103E7 can provide 3 ON periods and 3 OFF periods each
day and can offer either 7-day control (a different programme
for each day of the week) or 5/2 day control (one set of
programmes for weekdays and a different set for weekends).
Before you start
Open the flap on the front of
the unit.
Press and release the R/S
button using a small, non-
metallic object (e.g. matchstick,
biro tip)
This will reset the unit, reinstate
the preset programmes and set
the time to 12:00pm on Monday.
Your timeswitch & Resetting the unit
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R/S

13
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
24hr or AM/PM display & Setting the Time & Day
Choice of 24hr or AM/PM display
Press and hold DAY and NEXT
ON/OFF buttons for 1.5 seconds
to toggle between 24hr clock and
AM/PM display, as required.
Setting the correct Time & Day
SETTING THE TIME
Press PROGRAMME once
The words SET TIME will appear
at the top of the display and the
time will flash on and off
Use + and – buttons to set the
correct time
When time is correct press
PROGRAMME again.
SETTING THE DAY
Press DAY repeatedly until the
correct day of the week is displayed.
MO is Monday, TU is Tuesday etc.
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/

14
Factory preset programmes
Factory Presets
The unit is supplied with the following preset programme
which will be active after the unit has been reset.
Mon-Fri Sat-Sun
1st ON 6.30am 7.30am
1st OFF 8.30am 10.00am
2nd ON 12.00pm 12.00pm
2nd OFF 12.00pm 12.00pm
3rd ON 5.00pm 5.00pm
3rd OFF 10.30pm 10.30pm
NB. 2nd ON and 2nd OFF are set to the same time.
These 2 times are ignored by the programme therefore
the heating will just come on once in the morning and
once in the evening. If you want the heating to come on in
the middle of the day set the 2nd ON and 2nd OFF to the
times you require.
Accepting the preset times
If you are happy to use the settings above, you don’t
need to do anything else.
To accept the presets press the
PROGRAMME button until the colon
in the display begins to flash.
Your unit is now in RUN mode.

15
Changing the preset programmes
Your installer will have set your unit to operate in one of the
following modes:
● 7 day - different settings for each day of the week
(page 16-17) - default setting
● 5/2 day - one set of programmes for weekdays and
another for weekends (page 18-19)
Please follow the correct instructions to programme
your unit.
Please Note
The unit must be programmed in sequence and ON/
OFF times cannot be set out of sequence.
If you want to leave a preset time as it is, simply press
NEXT ON/OFF to move on to the next setting
Your clock will allow you to programme 3 ON/OFF
settings per day. If you do not wish to use one of the
ON/OFF settings, simply programme the ON time to
be the same as the OFF time and the setting will not
operate.
If at any time you get confused and need to reset your
timings to the standard preset programme, press the
R/S button to return to the preset programmes.
!
!
Changing the preset programmes

16
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
Programming the unit - 7-day mode
1. Press PROGRAMME until
SET ON TIME appears at
the top of the display and
MO appears at the bottom
of the display.
Use the + and - buttons to
set the time you want your
heating to first come on in
the morning (Event 1).
2. Press NEXT ON/OFF to
move to Event 2.
Either press COPY to use
the same settings as the
day before or continue to
programme the central
heating ON and OFF
times, using the + and
-buttons to set the time
you want and pressing the
NEXT ON/OFF button to
move to the next setting.
3. Press DAY button once
only. TU will appear at the
bottom of the display.
Programming the heating & hot water
in 7-day mode
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/

17
Continue programming the
rest of the week by pressing:
a) NEXT ON/OFF button to
move to the next setting,
b) + and - buttons to amend
the time
c) DAY to advance to the next
day.
Alternatively press COPY to
keep the same settings as the
day before
4. Press the PROGRAMME
button to return the unit to
RUN mode
5. Proceed to page 20.
Return to RUN mode
COPY previous event times
To move to next DAY
To amend TIME
To advance to next time
setting
Programming the unit - 7-day mode
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/

18
1. Press PROG until SET
ON TIME appears at the
top of the display and
MOTUWETHFR appears at
the bottom of the display.
Use the + and - buttons to
set the time you would like
your heating/hot water to
first come on in the morning
(Event 1).
2. Press NEXT ON/OFF once
only.
Use the + and - buttons to
set the time you want your
heating/hot water to go off
(Event 2).
To move to the next setting,
i.e. when you would like your
heating/hot water to come
on again (Event 3) press the
NEXT ON/OFF button again.
Programming the heating & hot water
in 5/2 day mode
Programming the unit - 5/2 day mode
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/

19
3. Continue programming the
heating/hot water ON and
OFF times for weekday
Events 4, 5 & 6 as in Step 2.
4. Press the DAY button once
and SASU will appear at the
bottom of the display.
Either press COPY to
keep the same settings for
Saturday and Sunday as
you have programmed for
Monday to Friday.
Alternatively, programme
new ON/OFF times by
pressing the NEXT ON/OFF
button to move to the next
setting and using the + and
-buttons to set the time you
want.
5. Press the PROG button to
return the unit to RUN mode
6. Proceed to page 20.
Programming the unit - 5/2 day mode
Return to RUN mode
COPY previous event times
To amend TIME
To advance to next time
setting
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/
PROGRAMME
NEXT/ON/OFF
+
-
DAY
COPY R
/

20
Running your programme
The 103E7 controls your hot water and heating together,
turning them on and off at the same times.
To run the central heating and hot water programme
press the SELECT button.
As you press SELECT a bar on the display will move
between ON, OFF, ALLDAY and AUTO
ON = the hot water/heating will remain on
constantly
OFF = the hot water/heating will not come on
AUTO = the hot water/heating will come on
and go off according to the programmed times
ALLDAY = the unit will come on at the first
programmed ON and will remain on until the
last programmed OFF
Select the option you require, depending on your
circumstances, time of year, etc.
RUN mode
Other manuals for 103E7
4
Table of contents
Other Danfoss Remote Control manuals

Danfoss
Danfoss WS103 User manual

Danfoss
Danfoss MP08A User manual

Danfoss
Danfoss Ikompact User manual

Danfoss
Danfoss CF-RC User manual

Danfoss
Danfoss CF-RC User manual

Danfoss
Danfoss Ikompact User manual

Danfoss
Danfoss SET3M User manual

Danfoss
Danfoss MPCAN User manual

Danfoss
Danfoss CF-RC User manual

Danfoss
Danfoss FP975 Assembly Instructions

Danfoss
Danfoss 102E7 User manual

Danfoss
Danfoss R13 F User manual

Danfoss
Danfoss IKORE User manual

Danfoss
Danfoss 175G9004 User manual

Danfoss
Danfoss T70 1 HALL User manual

Danfoss
Danfoss R06 User manual

Danfoss
Danfoss TM70 User manual

Danfoss
Danfoss IK2 User manual

Danfoss
Danfoss IKP1000 User manual

Danfoss
Danfoss IKORE B User manual