Deif AGC 150 User manual

AGC 150
Generator marine stand-alone
Operator's manual
4189341314C

1. Introduction
1.1 Symbols for hazard statements......................................................................................................................................................................................... 3
1.2 About the operator's manual...............................................................................................................................................................................................3
1.3 Warnings and safety.................................................................................................................................................................................................................4
1.4 Legal information....................................................................................................................................................................................................................... 4
2. About the AGC 150 Stand-alone marine
2.1 Stand-alone (island mode)...................................................................................................................................................................................................5
2.1.1 Display, buttons and LEDs............................................................................................................................................................................................. 5
2.2 Emergency genset....................................................................................................................................................................................................................6
2.2.1 Display, buttons and LEDs............................................................................................................................................................................................7
2.3 Display settings..........................................................................................................................................................................................................................8
2.4 Mimic function............................................................................................................................................................................................................................ 8
2.5 Running modes...........................................................................................................................................................................................................................9
3. Menus
3.1 Menu structure..........................................................................................................................................................................................................................10
3.2 Parameters menu....................................................................................................................................................................................................................10
3.2.1 Menu numbers...................................................................................................................................................................................................................11
3.2.2 The jump to parameter function.............................................................................................................................................................................11
3.3 View menu...................................................................................................................................................................................................................................12
3.3.1 Display views..................................................................................................................................................................................................................... 12
3.3.2 Display text........................................................................................................................................................................................................................13
3.4 Status texts.................................................................................................................................................................................................................................14
3.5 Service view...............................................................................................................................................................................................................................15
3.6 Engine shortcuts..................................................................................................................................................................................................................... 16
3.6.1 PID configuration............................................................................................................................................................................................................. 16
3.6.2 ECU Diagnose and Force Regeneration.............................................................................................................................................................16
3.7 Exhaust after-treatment (Tier 4/Stage V)................................................................................................................................................................17
4. Alarm handling and log list
4.1 Alarm handling...........................................................................................................................................................................................................................21
4.2 Logs menu...................................................................................................................................................................................................................................22
Operator's manual 4189341314C EN Page 2 of 22

1. Introduction
1.1 Symbols for hazard statements
DANGER!
This shows dangerous situations.
If the guidelines are not followed, these situations will result in death, serious personal injury, and equipment
damage or destruction.
WARNING
This shows potentially dangerous situations.
If the guidelines are not followed, these situations could result in death, serious personal injury, and equipment
damage or destruction.
CAUTION
This shows low level risk situation.
If the guidelines are not followed, these situations could result in minor or moderate injury.
NOTICE
This shows an important notice
Make sure to read this information.
1.2 About the operator's manual
This document gives the necessary information to operate the controller.
CAUTION
Installation errors
Read this document before working with the controller. Failure to do this may result in human injury or damage
to the equipment.
Intended users of the operator's manual
The operator's manual is for the operator that uses the controller regularly.
The manual describes the LEDs, buttons and screens on the controller, alarm handling, and the logs menu.
Operator's manual 4189341314C EN Page 3 of 22

1.3 Warnings and safety
Factory settings
The controller is delivered pre-programmed from the factory with a set of default settings. These settings are based on
typical values and may not be correct for your system. You must therefore check all parameters before using the controller.
Data security
To minimise the risk of data security breaches:
• As far as possible, avoid exposing controllers and controller networks to public networks and the Internet.
• Use additional security layers like a VPN for remote access, and install firewall mechanisms.
• Restrict access to authorised persons.
1.4 Legal information
Third party equipment
DEIF takes no responsibility for the installation or operation of any third party equipment, including the genset. Contact the
genset company if you have any doubt about how to install or operate the genset.
Warranty
NOTICE
Warranty
The controller is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF
does not take responsibility for the accuracy of translations, and translations might not be updated at the same time as the
English document. If there is a discrepancy, the English version prevails.
Copyright
© Copyright DEIF A/S. All rights reserved.
Software version
This document is based on the AGC 150 software version 1.16.0.
Operator's manual 4189341314C EN Page 4 of 22

2. About the AGC 150 Stand-alone marine
2.1 Stand-alone (island mode)
Stand-alone (island mode)
G
Stand-alone (island mode operation) is typically used in
power plants that are isolated from other power generation
systems.
NOTE For the AGC 150 Stand-alone controller, you can
disable breaker control.
2.1.1 Display, buttons and LEDs
No. Name Function
1 Power Green: The controller power is ON.
The controller power is OFF.
2 Display screen
Resolution: 240 x 128 px.
Viewing area: 88.50 x 51.40 mm.
Six lines, each with 25 characters.
3 Navigation Move the selector up, down, left and right on the screen.
4 OK Go to the Menu system.
Confirm the selection on the screen.
5 Back Go to the previous page.
Operator's manual 4189341314C EN Page 5 of 22

No. Name Function
6 Remote mode Remote equipment (digital inputs, Modbus commands, commands) controls the AGC
150.
7 Silence horn Turns off an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Mode selection, Test, Lamp test
9 Local mode The operator can use the display unit push buttons to start, stop, connect or disconnect the
genset.
10 Main busbar This AGC does not use this. It is only lit during a lamp test.
11 Close breaker Push to close the breaker.
12 Open breaker Push to open the breaker.
13 Breaker symbols
Green: Breaker is closed.
Red: Breaker failure.
The breaker is open.
14 Generator
Green: Generator voltage and frequency are OK. The controller can close the breaker.
Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still
running. The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
15 Engine
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running, or there is no running feedback.
16 Stop Stops the genset if Local or Semi-auto is selected.
17 Start Starts the genset if Local or Semi-auto is selected.
18 Load symbol Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
2.2 Emergency genset
Emergency genset
G
If there is a significant loss of power or a total blackout in
the main power generation system, the controller
automatically changes the supply to the emergency
generator. This makes sure that there is power during a
failure and prevents damage to electrical equipment.
NOTE Alternatively, the breaker to the busbar can be
externally controlled.
Operator's manual 4189341314C EN Page 6 of 22

2.2.1 Display, buttons and LEDs
No. Name Function
1 Power Green: The controller power is ON.
The controller power is OFF.
2 Display screen
Resolution: 240 x 128 px.
Viewing area: 88.50 x 51.40 mm.
Six lines, each with 25 characters.
3 Navigation Move the selector up, down, left and right on the screen.
4 OK Go to the Menu system.
Confirm the selection on the screen.
5 Back Go to the previous page.
6 Auto mode
If there is a blackout, the controller automatically starts and connects the genset. No operator
actions are needed. The controller also automatically opens and closes the tie breaker (open
transitions, since there is no synchronisation).
7 Silence horn Turns off an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Mode selection, Test, Lamp test
9 Semi-auto mode Remote equipment (digital inputs, Modbus commands, commands) controls the AGC 150.
The operator can also use the display unit push buttons.
10 Main busbar This AGC does not use this. It is only lit during a lamp test.
11 Close breaker Push to close the breaker.
12 Open breaker Push to open the breaker.
13 Breaker symbols
Green: Breaker is closed.
Red: Breaker failure.
The breaker is open.
14 Generator
Green: Generator voltage and frequency are OK. The controller can close the breaker.
Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still
running. The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
Operator's manual 4189341314C EN Page 7 of 22

No. Name Function
15 Engine
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running, or there is no running feedback.
16 Stop Stops the genset if Local or Semi-auto is selected.
17 Start Starts the genset if Local or Semi-auto is selected.
18 Load symbol Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
2.3 Display settings
To adjust for ambient lighting, configure the display settings.
Parameters > Basic settings > Controller settings > Display > Display control
Parameter Text Range Default
9151 Backlight dimmer 0 to 15 * 12
9152 Green LEDs dimmer 1 to 15 * 15
9153 Red LEDs dimmer 1 to 15 * 15
9154 Contrast level to 0
9155 Sleep mode timer 1 to 1800 s 60 s
9156 Enable mode timer) OFF
ON ON
9157 Alarm Jump OFF
ON ON
9158 Engineering units Bar/Celsius
PSI/Fahrenheit Bar/Celsius
NOTE * Low numbers are minimum brightness and high numbers are maximum brightness.
2.4 Mimic function
With the mimic function you can select how the control buttons and LEDs are shown on the controller's display.
Parameters > Basic settings > Controller settings > Display > LED mimic
Parameter no. Item Range
6082 LED mimic
Standard with genset
Standard
Guided with genset
Guided
Operator's manual 4189341314C EN Page 8 of 22

Standard
The control buttons and LEDs are shown.
If you stop the genset, the engine/generator symbols are not
shown.
Standard with genset
The control buttons and LEDs are shown.
If you the stop the genset, the engine/generator symbols are
shown in red.
Guided
Active control buttons and LEDs are shown inactive are not shown.
Example: The controller is in semi-auto mode, and the genset is not
operating. Only the start button and the open breaker symbol is
shown, as these are the only possible actions.
Guided with genset
Active control buttons, LEDs and the engine/generator symbols are
shown, inactive are not shown.
Example: The controller is in semi-auto mode, and the genset is not
operating. The only possible actions are to start the genset, and to
open the breaker, so only these symbols and the red engine/
generator symbols are shown.
All Mimic settings
Red breaker symbol:
• Breaker position failure
• Breaker close failure
2.5 Running modes
To configure the running modes, push the Shortcut button and use the display buttons to select Running Modes.
You can select Locale mode or Remote mode, when zero or one breaker is configured. If two or more breakers are
configured, you can select Auto mode or Semi-auto mode.
More information
See Display, buttons and LEDs for a description of the different running modes.
To configure the test mode go to Settings > Test. To select the test mode push the Shortcut button and select Start
Test.
Operator's manual 4189341314C EN Page 9 of 22

3. Menus
3.1 Menu structure
The controller has two menu systems, which can be used without password entry:
•The View menu system: Shows the operating status and values. The system has 20 configurable windows, that can be
entered with the arrow buttons.
•The Parameters menu system: The operator can see the controller's parameters. A password is necessary to change
the parameter settings.
3.2 Parameters menu
You can configure the controller in the parameters menu and you can also find information, which is not available in the
view menu. From the view menu, push the button to find the parameters menu. Use the and buttons to find
the different settings parameter and select with the button.
Parameters menu example
This is an example of how to change the nominal voltage settings.
Operator's manual 4189341314C EN Page 10 of 22

3.2.1 Menu numbers
Each parameter has a menu number. You can find the number in the upper right corner on the display screen.
You can also find the menu number with the utility software:
1. Select Parameters from the toolbar on the left.
2. Set the view mode to list. The view mode can be found in the left corner of the screen.
3. The menu numbers are in the Channel column.
3.2.2 The jump to parameter function
If you know the menu number for a parameter, you can use the jump to parameter function to go directly to the parameter.
On the controller
1. From the view menu, push the Shortcut button to see the jump to parameter function:
2. Use the and buttons to go to Jump to parameter and push the button.
3. Use the and buttons to change the numbers, and push the button to save. Use the and buttons to
move to the next number.
Operator's manual 4189341314C EN Page 11 of 22

3.3 View menu
The view menu is shown when the controller is turned on, and you can see the operating status and values. The event and
alarms list will also be shown if an alarm is on.
1. Operating status
2. Values and information
3. Page number
The view menu has 20 different display views. Use the and buttons to select a view.
Push
3.3.1 Display views
The controller has 20 different display views and 17 of the views are pre-configured. You can configure the views with the
utility software.
Line View 1 View 2 View 3 View 4 View 5
1 G 0.00PF 0kW Speed detection Run absolute 0hrs G 0 0 0V Energy total 0kWh
2 G 0.00kVA 0kvar Water temp. detection Serv 1 0d 0h G 0 0 0A Date and Time
3 G L1 0.0Hz 0V Oil pres. detection Start attempts 0 G 0.00 0.00 0.00Hz MB operations 0
4 G 0 0 0A Fuel level detection Voltage 0V G PF 0.00 0.00
0.00 GB operations 0
5 BB L1 0.0Hz 0V 0.0V - G 0 0 0kW -
Line View 6 View 7 View 8 View 9 View 10
1 - After treatment Engine dashboard EIC T. Coolant and P total
2 Synchroniser II EIC Tier 4 Icons EIC Engine Icons EIC T. Turbo Oil Current and Q total
3 - - - EIC T. Exh. Right Pf and kW %
Operator's manual 4189341314C EN Page 12 of 22

Line View 6 View 7 View 8 View 9 View 10
4 - - - EIC T. Oil GOV and AVR
output
5 - EIC Regeneration info - EIC T. Fuel Ramp down/up
setpoint
Line View 11 View 12 View 13 View 14 View 15
1 P GTot and P % G Angle L1L2 0deg P 0kW 0% P available 0kW Angle 0deg
2 Q GTot and Q % G Angle L2L3 0deg Q 0kvar 0% P available 0% G Angle L1L2 0deg
3 BB freq and G freq G Angle L3L1 0deg S 0kVA 0% P consumed 0kW BB Angle L1L2
0deg
4 BB and G AVR reg. type - P consumed 0% BB Angle L2L3
0deg
5 kW % and kvar % GOV reg. type - - -
Line View 16 View 17 View 18 View 19 View 20
1 G G f-L1 0.00Hz - - -
2 G 0V G f-L2 0.00Hz - - -
3 G 0V G f-L3 0.00Hz - - -
4 G 0V - - - -
5 G - - - -
3.3.2 Display text
Configure the display views
You can configure the display views with the utility software:
1. Select the Configuration of the user views button in the toolbar.
2. In the pop-up window, select the display view you want to change.
3. Select the display line you want to change.
4. In the pop-up window, select the text you want and click OK.
Operator's manual 4189341314C EN Page 13 of 22

Display text
You can select five of the display texts for each display view.
3.4 Status texts
Status text Condition
ACCESS LOCK The configurable input is activated, and the operator tries to activate one of the blocked keys.
Aux. test ##.#V ####s The battery test is activated.
COOLING DOWN ###s Cooling-down period is activated.
DG BLOCKED FOR START The generator has stopped and has active alarm(s).
EDG READY AUTO The controller is in auto mode and ready to start in case of blackout.
EDG READY SEMI The controller is in semi-auto mode and ready for external signals or operator input.
EDG RUNNING SEMI The genset is running in semi-auto mode. The breaker is open.
EMERGENCY SUPPLY The controller is in auto mode and supplying power from the emergency generator due to
blackout on the mains busbar.
EXT. STOP TIME ###s The extended stop timer is running.
FULL TEST ###.#min Test mode is activated and test timer counting down.
GB ON BLOCKED The generator is running, the GB is open and there is an active Trip GB alarm.
GB TRIP EXTERNALLY Some external equipment has tripped the breaker. An external trip is logged in the event log.
GEN. RUNNING LOCAL Genset running in local mode.
GEN. RUNNING REMOTE Genset running in remote mode.
GEN. SUPPLY LOCAL Genset is supplying busbar in local mode.
GEN. SUPPLY REMOTE Genset is supplying busbar in remote mode.
GENSET READY REMOTE The controller is in remote mode and ready to respond.
GENSET READY LOCAL The controller is in local mode and waiting for operator input.
GENSET STOPPING Cooling down has finished.
Hz/V OK IN ###s The voltage and frequency on the genset is OK. When the timer runs out the generator breaker
can be closed.
IDLE RUN The idle run input is active.
IDLE RUN ###.#min The idle run function is active. During a start the genset will not go to nominal RPMs. During a
stop the genset will not stop before the timer has expired.
ISLAND ACTIVE The controller is in remote mode and supplying power.
Operator's manual 4189341314C EN Page 14 of 22

Status text Condition
RUN COIL ON Run coil is active during the start sequence.
SHUTDOWN OVERRIDE The configurable input is active.
SIMPLE TEST ###.#min Test mode is activated and test timer counting down.
START DG(s) IN ###s The start genset set point has been exceeded. The genset will start when the timer expires.
START PREPARE The start prepare relay is activated.
START RELAY OFF The start relay is deactivated during the start sequence.
START RELAY ON The start relay is activated.
STOP DG(s) IN ###s The stop genset set point has been exceeded. The genset will stop when the timer expires.
TB TRIP EXTERNALLY Some external equipment (not the controller) has tripped the breaker. An external trip is
logged in the event log.
VOLT/FREQ OK IN ###s The voltage and frequency will be okay in ###s.
3.5 Service view
You can use the service view to see the status of the controller. You can change the passwords in the service menu, but not
the other controller settings.
From the view menu, push the button and select Service View . Use the and buttons to go through the
parameters in the service view, and use the button to select the parameters.
Service view example
Operator's manual 4189341314C EN Page 15 of 22

3.6 Engine shortcuts
3.6.1 PID configuration
You can use the engine shortcuts menu to configure the PID set points.
On the controller
1. From the view menu, push the Shortcut button to see the menu.
2. Use the Up and Down buttons to go to Engine shortcuts menu, and push the button.
PID references
• Only active inputs are shown in the list.
• You can also see the values in the utility software. Select General Purpose PID from the left menu. There are a total of 2
reference values.
Manual regulation (up and down)
• Used for PID1.
• Not active during ramp up/down.
3.6.2 ECU Diagnose and Force Regeneration
You can activate ECU diagnose from the engine shortcuts menu. You can also use the menu to inhibit or force regeneration.
ECU Diagnose
Use ECU Diagnose to read ECU data without starting the engine.
To activate ECU diagnose on the controller:
1. Push the Shortcut button.
2. Select Engine shortcuts.
3. Select ECU Diagnose.
The diagnostics timer is activated when you select ECU Diagnose, and the controller starts to read the ECU data when the
diagnostic timer expires. To configure this timer, go to Parameters in the utility software and select parameter 6701.
Operator's manual 4189341314C EN Page 16 of 22

Force Regeneration
To inhibit or force regeneration:
1. Push the Shortcut button.
2. Select Engine shortcuts.
3. Select Force Regeneration.
4. Select Inhibit or Force.
3.7 Exhaust after-treatment 4/Stage
AGC 150 meets the Tier 4 V requirements. The user can use the display to monitor (and control) both the
engine, and the exhaust after-treatment system.
After-treatment page
No. Referent Symbol Description
1 After-treatment status -
2 Engine emission system failure Emission failure or malfunction.
3 Diesel Particle Filter Regeneration is needed.
4 Page name -
5 Controller status -
6 Diesel Particle Filter Inhibit Regeneration is inhibited.
7 High temperature - Regeneration There is a high temperature and regeneration is in process.
8 HC burn-off Hydrocarbon accumulation that requires burn-off.
Operator's manual 4189341314C EN Page 17 of 22

No. Referent Symbol Description
9 Engine emission system failure level Emission failure or malfunction, with the severity.
10 Diesel Particle Filter level Regeneration needed, with the severity.
11 DEF level warning Low DEF level.
12 DEF shutdown DEF problem stops normal operation.
13 DEF level inducement
Mid-level inducement.
Severe inducement.
14 Diesel Exhaust Fluid DEF quality is low.
Operator's manual 4189341314C EN Page 18 of 22

Engine dashboard
No. Referent Symbol Description
1 Water in fuel There is water in the fuel.
2 Engine interface status An engine warning.
3 Page name - -
4 Controller status -
5 Engine interface status An engine shutdown.
6 Engine interface status An engine malfunction.
7 Cold start The engine is cold.
8 High engine coolant temperature The engine coolant temperature is high.
9 Low engine oil pressure The engine oil pressure is low.
10 Fuel filter clogging The fuel filter is blocked.
11 Air filter clogging The air filter is blocked.
12 LIMIT lamp Only for MTU engines.
Operator's manual 4189341314C EN Page 19 of 22

No. Referent Symbol Description
13 Oil change The engine needs an oil change.
14 High engine oil temperature The engine oil temperature is high.
NOTE Grey symbols show that communication is available for the referent. An engine type might not support all of the
referents.
Operator's manual 4189341314C EN Page 20 of 22
Other manuals for AGC 150
9
Table of contents
Other Deif Marine Equipment manuals
Popular Marine Equipment manuals by other brands

Konsberg
Konsberg AIS 200 installation manual

Federal Signal Corporation
Federal Signal Corporation G-SND instruction manual

Clarion
Clarion M502 Owner's manual & installation manual

Pittway
Pittway SYSTEM SENSOR PA400 Series Installation and maintenance instructions

E2S
E2S Minialert IS-mC1 instruction manual

Venitem
Venitem DOGE EV12 installation manual