manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Delixi
  6. •
  7. Circuit Breaker
  8. •
  9. Delixi NAVIGATOR Series User manual

Delixi NAVIGATOR Series User manual

CDV2s
Motor Circuit Breaker
NAVIGATOR
Series
User Manual
Please carefully read this User Manual before installing
and operating the product, and keep this manual properly
for future reference
Safety Notice
Please carefully read this instruction before the installation, operation, run, maintenance, and inspection,
and follow the contents of the instruction to properly install and operate this product.
Danger:
●Do not operate the contactor with your wet hands;
●Do not touch the energized parts during operation;
●Mark sure that the product is deenergized during the maintenance and service;
●Do not use the short circuit method for product testing;
Caution:
●The installation, maintenance and service shall be performed by the qualified professional;
●Various characteristics of product have been set in factory, and cannot be removed or adjusted
without permission during operation;
●Please confirm that the product operating voltage, rated current, frequency and characteristics meet
the operating requirements before use;
●In order to prevent circuit breaker between phases, the exposed wires or copper buses at the terminal
block shall be subject to the insulation treatment;
●If found damage or abnormal sound when unpacking, please stop the machine immediately and
contact the supplier;
●When scrapping the product, please dispose the product waste properly. Thanks for your cooperation.
About CDV2s
●Panel introduction
1. Inlet terminal
2. Top aux. contact protective cover
3. Start button
4. Lock ring
5. Stop button
6. Outlet terminal
7. Trip test
8. Setting current range
9. Setting button
10. Product specification
11. Certification mark and sandard
12. Rated voltage, rated insulation voltage, and screw
tightening torque
13. Technical parameters under AC-3
14. Production date
Normal Operation, Installation, and Transport Conditions
●Normal Operation and Installation Conditions
(1) The ambient air temperature is not higher than +40℃, and is not below -5℃; the average value within 24
hours does not exceed +35℃;
(2) The altitude of the installation site does not exceed 2000m;
(3) The relative humidity of the atmosphere does not exceed 50% at the maximum ambient temperature of +40℃,
and a higher relative humidity is allowed lower temperatures, such as 90% at 20℃. Protective measures shall be
taken for condensation occasionally occurred due to temperature changes;
(4) The external magnetic field nearby the circuit breaker installation site shall not exceed 5 times of this earth
magnetic field in any direction;
(5) Installed in a place where there is no shock vibration for rain and snow intrusion;
(6) Pollution level: Level 3;
(7) Installation category: Class III;
(8) Rated frequency: IP20;
(9) Flashover distance: top and bottom 40mm; left and right 40mm; front and back 0mm.
●Normal Storage and Transport Conditions
(1) Temperature: -25℃ ~ +55℃;
(2) Relative humidity: ≤95%;
(3) Please handle the product gently, do not upside it down, and prevent harsh collision during transport;
Outline and Installation Dimensions
Installation and Disassembly Method
●Check that the working voltage, rated current, frequency and characteristics of the product meet the working
requirements before installation.
●It is forbidden to use the circuit breaker if damage or loose assembly.
●When the circuit breaker is used in a closed environment, and the adjacent circuit breakers are energized
simultaneously, appropriate derating is required, or a 9mm mounting clearance is kept between the adjacent
circuit breakers (this clearance can be empty or a side-mounted auxiliary module).
35mm rail
Install Disassemble
Accessory installation diagram
or
or
Model
Name
Spec.
Installation
location
Max. Installation
quantity
AEV2s
Instantaneous aux. contact
(front-mounted)
2NO, 1NO+1NC
Right above
1
ANV2s
Instantaneous aux. contact
(side-mounted)
2NO, 1NO+1NC
Left side
2
AUV2s
Undervoltage release
110~115V, 220~240V,
380~400V, 415V
Right side
1
ASV2s
Shunt release
110~115V, 220~240V,
380~400V, 415V
Right side
1
Shunt and undervoltage release
Install
1. Hang the hook at the upper part of the release in the
circuit breaker hanging hole;
2. Press teh hook located at the lower end of release;
3. Align the connecting rod of release with the
mechanism hole on the circuit breaker;
4. Combine the release with the circuit breaker
together, hange the hook and then release.
Disassemble
1, 2. Press the hook at the lower end of release, and
rotate it outwards;
3. Move the hook upwards after leaving the body to
remove the release.
Instantaneous Aux. Contact
Install
1. When the circuit breaker is in the OFF state, hange
the upper hook of auxiliary contact onto the circuit
breaker, and align the connecting rod with the hook of
circuit breaker mechanism;
2. When pressing the lower hook of auxiliary
contact, combine the auxiliary contact with the circuit
breaker together, release the hook of auxiliary contact,
and confirm that the auxiliary contact is firmly hung
onto the circuit breaker;
3. After installation, press the Start/Stop button of
circuit breaker to prevent no blockage of mechanism.
Disassembe
1. Press the lower hook of auxiliary contact;
2. Rotate the auxiliary contact outwards;
3. Move the hook upwards after leaving the body to
remove the auxiliary conatct.
Install AEV2s11 or AEV2s20
Installation
1. Pry the top auxiliary contact shield upwards;
2. Attach the flat side of the top auxiliary contact against the circuit breaker;
3. Align the installation position and insert it down.
Debugging and Operation
(1) Check whether the setting current range of motor circuit breaker is consistent with the rated operating current
of motor, and replace if necessary;
(2) Confirm that the motor circuit breaker for damage or abnormal sound; manually operate it several times and
check the mechanism works flexibly and reliably without blockage; the circuit breaker can put into the operation
only after passing those inspections.
(3) The product setting current has been set to the minimum value in factory. Before use, set the current to the
scale line consistent with the rated operating current of motor. If the motor trips in the starting process, increase
the current setting value appropriately until the motor circuit breaker can work normally.
(4) It is recommended to use single-core PVC insulated copper wire with prefabricated U-shaped ends in main
circuit, and the cross-sectional area of the wire is listed in table below:
Rated operating
current (A)
0<Ie≤8
8<Ie≤12
12<Ie≤20
20<Ie≤25
25<Ie≤32
Cross-sectional
area of the wire
(mm2)
1.0
1.5
2.5
4.0
6.0
Maintenance and Service
●Perform the maintenance regularly, and remove dust on the surface of the circuit breaker timely.
●It is forbidden to disassemble the circuit breaker to replace the internal parts without permission. In case of
failure of circuit breaker, please contact the customer service department or dealer for solution, or stop the
operation.
Company Commitment
Under the condition that users follow the use and storage conditions and the product are well sealed, within 36
months from the production date, our company will provide repair and replacement service free of charge for any
damage or abnormal operation due to poor manufacture quality. A paid repair will be provided if the warranty
period expires. For any damage due to one of the following situations, a paid repair will be given even if within
the warranty period:
(1) Improper operation, maintenance, or storage;
(2) Modified without permission or improper repair;
(3) Damage due to falling off or caused during installation after purchase;
(4) Force majeure such as earthquakes, fires, lightning strikes, abnormal voltages, and secondary disasters;
If you have any question, please contact the dealer or our company’s customer service department.
Customer service hotline: 400-826-8008
Certificate
DELIXI ELECTRIC LTD
Name: Motor circuit breaker
Model: CDV2s
This product passes the inspection and is allowed to be
shipped.
Standard: GB/T 14048.2 GB/T 14048.4
Inspector: Check 06
Production date: See label on inner box
DELIXI ELECTRIC LTD
Address: Delixi High-Tech Industrial Park, Liushi Town, Leqing City, Zhejiang P/C: 325604
Tel: (86-577) 6177 8888
Fax: (86-577) 6177 8000
Customer Service hotline: 400-826-8008
www.delixi-electric.com
The first edition of this manual was issued on Jan. 2021.

Other manuals for NAVIGATOR Series

4

This manual suits for next models

1

Other Delixi Circuit Breaker manuals

Delixi NAVIGATOR Series User manual

Delixi

Delixi NAVIGATOR Series User manual

Delixi NAVIGATOR Series User manual

Delixi

Delixi NAVIGATOR Series User manual

Delixi NAVIGATOR Series User manual

Delixi

Delixi NAVIGATOR Series User manual

Delixi Knight Series User manual

Delixi

Delixi Knight Series User manual

Delixi CDB6i User manual

Delixi

Delixi CDB6i User manual

Delixi CDW3 Series User manual

Delixi

Delixi CDW3 Series User manual

Delixi NAVIGATOR DZ47L Series User manual

Delixi

Delixi NAVIGATOR DZ47L Series User manual

Popular Circuit Breaker manuals by other brands

Eaton LTS-L/160/00 Assembly instructions

Eaton

Eaton LTS-L/160/00 Assembly instructions

ABB HD4/R Installation and service instructions

ABB

ABB HD4/R Installation and service instructions

LEGRAND DMX3 manual

LEGRAND

LEGRAND DMX3 manual

Siemens SIMATIC PN Installation and operating manual

Siemens

Siemens SIMATIC PN Installation and operating manual

Noark A32 user manual

Noark

Noark A32 user manual

SALTEK DA-075-DJ25 installation instructions

SALTEK

SALTEK DA-075-DJ25 installation instructions

IFM DF21 Series installation instructions

IFM

IFM DF21 Series installation instructions

Cooper Crouse-Hinds CEAG GHG 624 Series operating instructions

Cooper Crouse-Hinds

Cooper Crouse-Hinds CEAG GHG 624 Series operating instructions

ABB Sace Emax UL Listed Installation, service and maintenance instructions

ABB

ABB Sace Emax UL Listed Installation, service and maintenance instructions

Eaton AEGIS AG II IT DN0 Series installation instructions

Eaton

Eaton AEGIS AG II IT DN0 Series installation instructions

Siemens 8GK4730-3KK.0 Series operating instructions

Siemens

Siemens 8GK4730-3KK.0 Series operating instructions

Siemens 3VT9524-4TG30 quick start guide

Siemens

Siemens 3VT9524-4TG30 quick start guide

Siemens Sentron 3VA9157-0PK1 Series operating instructions

Siemens

Siemens Sentron 3VA9157-0PK1 Series operating instructions

ETI EFI-4B Instructions for mounting

ETI

ETI EFI-4B Instructions for mounting

WEG UBW800S user manual

WEG

WEG UBW800S user manual

Toshiba HV6FS-MLD instruction manual

Toshiba

Toshiba HV6FS-MLD instruction manual

Westinghouse CAS-8 instructions

Westinghouse

Westinghouse CAS-8 instructions

Siemens 3VT9300-8CB30 operating instructions

Siemens

Siemens 3VT9300-8CB30 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.