Digiplex EVO48 User manual

High Security and Access System
EVO48 V1.20
EVO192 V1.20
Installation Guide
Includes Keypad Installation


EVO Control Panel
Table of Contents
Introduction..................................................................... 1
Features of EVO48 .................................................................. 1
Features of EVO192 ................................................................ 1
Hardware Difference ................................................................ 1
Specifications ........................................................................... 1
Installation....................................................................... 2
Recommended Installation Procedure ..................................... 2
Location & Mounting ................................................................ 2
Earth Ground............................................................................ 2
AC Power ................................................................................. 2
Backup Battery......................................................................... 2
Auxiliary Power Terminals........................................................ 2
Bell/Siren Output ...................................................................... 2
Programmable Outputs ............................................................ 2
Keyswitch Connections ............................................................ 2
Access Control Connections .................................................... 2
Calculating Power Requirements ............................................. 4
Keypad Zone Connections....................................................... 5
Addressable Zone Connections ............................................... 5
Double Zone Connections........................................................ 6
Combus Connections............................................................... 6
Fire Circuits .............................................................................. 7
Telephone Line Connections ................................................... 7
Built-in RTC.............................................................................. 7
Programming Methods .................................................. 8
WinLoad Uploading/Downloading Software* ........................... 8
Paradox Memory Key............................................................... 8
Module Broadcast .................................................................... 8
Programming Through a Keypad ............................................. 8
Module Programming Mode ..................................................... 8
Zone Programming......................................................... 9
Zone Programming ................................................................ 10
Zone Numbering .................................................................... 10
Zone Doubling (ATZ).............................................................. 10
Zone Definitions ..................................................................... 10
Zone Partition Assignment ..................................................... 11
Zone Options.......................................................................... 11
Input Speed............................................................................ 12
EOL on Hardwire Zones......................................................... 13
Keypad Numbering ................................................................ 13
Remote Control Programming .................................... 14
Hardware Requirements ........................................................ 14
Remote Control Template ...................................................... 14
Keyswitch Programming ............................................. 15
Keyswitch Numbering ............................................................ 15
Keyswitch Definitions ............................................................. 15
Keyswitch Partition Assignment ............................................. 15
Keyswitch Options.................................................................. 15
Arming and Disarming Options .................................. 16
Arming Follows Partition ........................................................ 16
Trouble Latch ......................................................................... 16
Restrict Arming on Supervision Loss ..................................... 16
Restrict Arming on Tamper .................................................... 16
Restrict Arming on AC Failure................................................ 16
Restrict Arming on Battery Failure ......................................... 16
Restrict Arming on Bell or Auxiliary Failure ........................... 16
Restrict Arming on TLM Failure ............................................. 16
Restrict Arming on Module Troubles ..................................... 16
Timed Auto-Arming................................................................ 16
No Movement Auto-Arming ................................................... 16
Auto-Arming Options ............................................................. 17
Switch To Stay Arming .......................................................... 17
Always Force Arm when Regular Arming .............................. 17
Auto Force on Stay Arming.................................................... 17
Follow Zone Switches to Entry Delay 2 ................................. 17
One-Touch Features.............................................................. 17
Exit Delay............................................................................... 17
Keypad Lock-out Feature ...................................................... 17
Bell Squawk ........................................................................... 18
Ring-back............................................................................... 18
Maximum Bypass Entries ...................................................... 18
Display “Bypass” If Armed ..................................................... 18
Alarm Options ............................................................... 19
Bell/alarm Output ................................................................... 19
Bell Cut-off Timer................................................................... 19
Wireless Transmitter Supervision Options............................. 19
Police Code Timer ................................................................. 19
Tamper Recognition Options ................................................. 19
Keypad Panic Options ........................................................... 20
Event Reporting............................................................ 21
Reporting Enabled ................................................................. 22
Report Codes......................................................................... 22
Report Arming and Disarming ............................................... 23
Monitoring Station Phone Number......................................... 24
Account Number .................................................................... 24
Account Number Transmission.............................................. 24
Reporting Formats ................................................................. 24
Event Call Direction ............................................................... 24
Pager Delay ........................................................................... 25
Recent Close Delay ............................................................... 25
Power Failure Report Delay................................................... 25
Power Failure Restore Report Delay ..................................... 25
Repeat Pager Report Code Transmission............................. 25
Auto Test Report.................................................................... 25
Disarm Reporting Options ..................................................... 25
Zone Restore Report Options................................................ 25
Auto Report Code Programming ........................................... 26
Closing Delinquency Timer.................................................... 26
Dialer Options ............................................................... 27
Telephone Line Monitoring .................................................... 27
Tone/Pulse Dialing................................................................. 27
Pulse Ratio ............................................................................ 27
Busy Tone Detection ............................................................. 27
Switch To Pulse ..................................................................... 27
Bell On Communication Fail .................................................. 27
Keypad Beep on Successful Arm or Disarm Report.............. 27
Dial Tone Delay ..................................................................... 27
VDMP3 Voice Module ................................................... 28
VDMP3 Installation Instructions............................................. 28
Feature activation (PGMs)..................................................... 28
VDMP3 Setup Instructions..................................................... 28

Reference & Installation Manual
Programmable Outputs................................................ 29
PGM Activation Event............................................................ 29
PGM Deactivation Option ...................................................... 29
Flexible PGM Deactivation Option ......................................... 29
PGM Deactivation Event........................................................ 29
PGM Timer ............................................................................ 29
PGM1 Becomes a 2-wire Smoke Detector Input*.................. 29
PGM Test Mode..................................................................... 29
PGM Initial Status .................................................................. 29
System Settings and Commands................................ 30
Hardware Reset..................................................................... 30
Software Reset ...................................................................... 30
Installer Code Lock ................................................................ 30
Daylight Savings Time ........................................................... 30
Daylight Savings Time Schedule........................................... 30
Battery Charge Current.......................................................... 30
Combus Speed ...................................................................... 30
Transmit Zone Status on Serial Port...................................... 30
Serial Port Baud Rate ............................................................ 30
Partitioning............................................................................. 31
Shabbat Feature .................................................................... 31
Installer Function Keys .......................................................... 31
Module Reset......................................................................... 31
Locate Module ....................................................................... 31
Module Programming ............................................................ 31
Module and Label Broadcast ................................................. 31
System Date & Time.............................................................. 31
Quick Module Scanning......................................................... 31
Module Scanning ................................................................... 31
Serial Number Viewing .......................................................... 31
Power Save Mode ................................................................. 31
Auto Trouble Shutdown ......................................................... 32
No AC Fail Display................................................................. 32
Multiple Action Feature .......................................................... 32
System Labels ....................................................................... 32
Access Codes ............................................................... 34
Installer Code......................................................................... 34
Access Code Length.............................................................. 34
System Master Code ............................................................. 34
Programming Access Codes ................................................. 34
User Options.......................................................................... 34
Partition Assignment.............................................................. 35
Access Control....................................................................... 35
Access Control: System Features .............................. 36
Common Access Control Terms............................................ 36
Programming Overview ......................................................... 36
Enable Access Control .......................................................... 36
Door Numbering .................................................................... 36
Access Levels........................................................................ 36
Access Schedules ................................................................. 36
Backup Schedules ................................................................. 36
Holiday Programming ............................................................ 36
Schedule Tolerance Window ................................................. 36
Door Access Mode ................................................................ 37
Code Access.......................................................................... 37
Card and Code Access.......................................................... 37
Skip Exit Delay When Arming With Access Card .................. 37
Restrict Arming on Door ........................................................ 37
Restrict Disarming on Door.................................................... 37
Door Access During Clock Loss ............................................ 37
Burglar Alarm On Forced Door or Door Left Open ................ 37
Logging Access Control Events ............................................ 37
WinLoad Software ........................................................ 38
Panel Identifier ...................................................................... 38
PC Password......................................................................... 38
PC Telephone Number.......................................................... 38
Call Back Feature.................................................................. 38
Call WinLoad ......................................................................... 38
Answer WinLoad ................................................................... 38
Answering Machine Override Delay ...................................... 38
Ring Counter ......................................................................... 38
Event Buffer Transmission .................................................... 38
In-Field Firmware Upgrade.................................................... 38
Appendix 1: Automatic Report Code List .................. 40
Appendix 2: Contact ID Report Code List .................. 42
Appendix 3: Keypad Installation Instructions ........... 44
Index .............................................................................. 50
Warnings ....................................................................... 54
1.0

EVO Control Panel 1
1 Introduction
The Digiplex EVO is a security and access control system with 8 on-board
zone inputs (16 with zone doubling) that is expandable to 48 or 192 zones
via the 4-wire combus. The EVO control panel features up to 999 users, 8
partitions, 32 doors and can support up to 254 modules in any combination.
The Digiplex EVO system provides the highest level of protection for banks,
high-security military and government sites, luxurious residential homes
and any place where maximum security is essential. These systems are
designed to be easy to use, and the modular concept of these systems
provides installers with labour-saving features that make expanding,
installing and servicing these systems quick and convenient.
Expand the EVO system by adding plug-and-play expansion modules
anywhere and in any combination on the 4-wire combus. Modules are
connected to the combus at the most convenient location and then their
zone inputs are assigned to the desired zone and partition. Also, only a
module’s used inputs are assigned to zones in the system. Keyswitches,
remote controls and unused module inputs do not use up zones. Once
installed, all combus modules, including motion detectors, can be
programmed remotely via a keypad or the WinLoad upload/download
software.
EVO also supports 32 virtual zones in addition to its security zones and
access control doors. Virtual zones can be used to automate PGM
activations without occupying a security zone and without affecting the
system’s security functions. The EVO system is a logical solution to every
installer’s security, access control and home automation installation needs.
1.1 Features of EVO48
Digital combus:
• Provides constant power, supervision and two-way communication
between the control panel and all its modules
• Supports up to 127 modules
• Connect modules up to 914m (3000ft) from the panel
• Sabotage-proof technology without additional wiring
8 on-board zones (16 w/ zone doubling) expandable to 48 zones via
4-wire combus
Built-in access control features
In-field firmware upgradeable via 307USB and WinLoad
Compatible with NEware
Automatic Daylight Saving Time feature
2 on-board solid-state relays PGM outputs (+ 3 optional), negative or
positive triggering
PGM1 can be used as a 2-wire smoke input
96 user codes
4 partitions
1024 events buffered
Program remote controls using the master or installer codes
Up to 96 remote controls with one MG-RTX3
Built-in-real-time clock backup battery
1.7A switching power supply
1 supervised bell output, auxiliary output and telephone line
Push button software reset (reset to default values and restart)
Push button to activate or deactivate the Auxiliary output
Fits in a 28cm x 28cm x 7.6cm (11in x 11in x 3in) metal box
The EVO series share the same programming for easy panel substitution
1.2 Features of EVO192
Same features as the EVO48 plus:
Expandable to 192 zones
5 on-board solid-state PGM outputs, negative or positive triggering
Supports up to 254 expansion bus modules
999 user codes
8 partitions
2048 events buffered
Up to 999 remote controls with one MG-RTX3
1.3 Hardware Difference
The programing for the EVO48 and EVO192 panels is identical. However,
certain differences may affect how many elements can be programmed.
1.4 Specifications
Control Panel (Non-UL systems)
AC Power: 16Vac, 20/40VA, 50-60Hz
Battery: 12Vdc, 7Ah minimum
Auxiliary Power: 12Vdc 600mA typical, 700mA maximum,
fuseless shutdown at 1.1A
Bell Output: 1A, fuseless shutdown @ 3A
PGM Output: PGM1 to PGM4 100mA solid-state relays with
+/- trigger, PGM5 Form C relay output rated at
5A/28Vdc N.O. / N.C.
Operational Temperature: -20°C to +50°C (4°F to +122°F)
All control panel outputs are rated to operate between 10.8Vdc and
12.1Vdc
Control Panel (UL compliant systems)
AC Power: 16Vac, 40VA, 60Hz
Battery: 12Vdc, 7Ah minimum
Auxiliary Power: 11.4 to 12.5Vdc, 200mA maximum, fuseless
shutdown at 1.1A
Bell Output: 11.4 to 12.5Vdc, 1A maximum, fuseless
shutdown @ 3A
PGM Output: PGM1 to PGM4 100mA solid-state relays with
+/- trigger, PGM5 Form C relay output rated at
5A/28Vdc N.O. / N.C.
All control panel outputs are rated to operate between 11.4Vdc and
12.5Vdc
Specifications may change without prior notice.
Feature EVO48 EVO192
Zones 48 192
Partitions 4 8
Users 96 999
On-board PGMs* 2 5
Modules 127 254
General Note 1
Please note that only LCD and Grafica keypads can be used to program the
EVO system. LED keypads cannot be used to program the system.
General Note 2
Please note that the steps may differ when programming with the Grafica
keypad (DNE-K07). If not indicated, refer to the complete “Grafica User
Manual”, which can be downloaded for free from our website at
paradox.com

2 Reference & Installation Manual
2 Installation
2.1 Recommended Installation Procedure
1. Connect a small group of modules, including a keypad. See Figure 3
on page 3 for connection information.
2. Connect the battery and AC power. Enter section [4000] (see section
13.20 on page 31). Only the Clock Loss trouble and/or Bell Absent
trouble should appear. Verify the connection if a module does not
appear in section [4000], or if a module trouble occurs.
3. Disconnect AC power and the battery, follow steps 2, 3 and 4 for other
modules.
4. If modules were removed, enter [4005](see section 13.18 on page
31).
5. Connect an LCD keypad at various points from the control panel and
use the keypad’s built-in voltmeter.
2.2 Location & Mounting
Select a site that is not accessible to intruders and leave at least 2" around
the box to allow proper ventilation and heat dissipation. The site should be
dry and close to an AC, ground and telephone line connection.
2.3 Earth Ground
Connect the ground connector to the enclosure and cold water pipe or
grounding rod as per local electrical codes.
2.4 AC Power
Use a 16.5Vac (50/60Hz) transformer with a minimum 20VA rating. For
increased power use a 40VA rating. For UL Listed systems, use model
#BE156240CAA. For CSA listed systems, use model #BE116240AAA. Do
not use any switch-controlled outlets to power the transformer.
Do not connect the transformer or the backup battery until all wiring is completed.
When powering up the EVO control panel, the panel will begin a module scan.
2.5 Backup Battery
Connect a 12Vdc 7Ah rechargeable acid/lead or gel cell backup battery
(YUASA model #NP7-12 recommended). Verify the polarity, as reversed
connections will blow the battery fuse. For details on how to set the Battery
Charge Current to either 350mA or 850mA, see section 13.6 on page 30.
2.5.1 Battery Test
The control panel conducts a dynamic battery test under load every 60
seconds. If the battery is disconnected, if its capacity is too low or if the
battery voltage drops to 10.5 volts or less when there is no AC, the “Battery
Trouble” message will appear in the Trouble Display. At 8.5 volts, the panel
shuts down and all outputs close.
2.6 Auxiliary Power Terminals
The auxiliary power supply can power accessories in the security system. A
fuseless circuit protects the auxiliary output against overload and shuts it
down if the current exceeds 1.1A. Auxiliary power will resume once the
overload condition has restored. Press and hold the AUX button for two
seconds to turn AUX power on and off.
2.7 Bell/Siren Output
The bell output supplies 12Vdc upon alarm and can support one 30-watt or
two 20-watt sirens. The bell output will automatically shut down if the
current exceeds 3A. If the load on the BELL terminals returns to normal
(3A), the control panel will re-instate power to the BELL terminals. Please
verify correct polarity.
For connection of self-contained bell/siren, see
Figure 3
on page 3.
When the bell output is not used, the “Bell Absent” message appears in the
Trouble Display. To avoid this, connect a 1k
resistor across the bell output. UL
Note: The keypads must be programmed to beep with all troubles.
2.8 Programmable Outputs
PGM1 to PGM4 are 100mA (max.) solid-
state relays with +/- trigger. PGM5 is a 5A/
28Vdc N.O./ N.C. relay output. They can be
set at either normally open or normally
closed. If the current draw on PGM1 to
PGM4 is to exceed the current output, we
recommend using a relay as shown in
Figure 1.
2.9 Keyswitch Connections
Connect the keyswitches to the keypad,
control panel, or Zone Expansion Module's
hardwired input terminals as shown in
Figure 2.
2.10 Access Control Connections
For all access control explanations and
connection drawings, refer to Access Control:
System Features on page 36.
Figure 1: PGM & Relay
Figure 2: Keyswitch

EVO Control Panel 3
Figure 3: EVO Control Panel Wiring Diagram
AUX Power (Auxiliary):
Provides up to 700mA. Refer to
Table 1 on page 4
When installing the combus wires in a noisy environment, or when connecting the combus across separate buildings, you
must use a shielded cable. Refer to section 2.15.1 on page 6.
Please see UL and ULC Warnings on page 54 for applicable UL/ULC warnings and information.
Door Contact
* if EOL is enabled in
the control panel
Bell/Siren
AWG#14 single
conductor solid
copper wire
Ground
clamp
Cold water
pipe
grounding
To metallic
enclosure
For the hardwired connections, see
Single Zone Input Connections on page
6 and Double Zone Connections on
page 6.
Combus
Four pin connector
can be used for
quick installation
of a keypad or
module.
Built-in RTC
See page 7.
12Vdc 7Ah Rechargeable
Acid/Lead or Gel Cell
Backup Battery
Red "STATUS" LED:
Flashing - Indicates proper
operation.
Always On - Panel is using
a phone line.
Fast Flash - Indicates a control
panel failure.
Off - Control panel error.
Used for In-Field Firmware
Upgrade through a
307USB
Direct Connect Interface.
Press and hold the Reset
button for 2 seconds to restart
the panel without removing
power.
Optional on EVO48
Bell/Siren
The sum of the current
drawn from the BELL and
AUX must be limited to
2.0A. Exceeding this limit will
overload the panel power supply
and lead to complete system
shutdown.
PLEASE NOTE: When powering up the EVO control panel, the panel will begin a module scan to verify if all the modules
connected to the panel are operational. The scanning process will take between 30 seconds and 3 minutes to complete
depending on the number of modules connected to the control panel. The module scan is complete when the LCD
keypad begins to show the partition status. Only after the module scan is complete will the control panel be fully
operational.
Connection for Self-Contained Bell/Siren
40VA transformer strongly recommended
The combus supports a maximum of 127 (EVO48)
or 254 (EVO192) modules. Although external power
supplies can be used to provide power to modules
connected far from the control panel, the total
distance of all runs of wire combined cannot
exceed 914m (3000ft). For example, if ten runs of
wire measuring 305m (1000ft) each are connected
to the control panel, the total distance would be
3048m (10, 000ft), which exceeds the system's
capacity.
Before adding any module to the control panel
make sure you shutdown the AUX output by
pressing and holding the AUX button for 3
seconds.
Charging and battery test
LED (every 60 seconds).
VDMP3 voice module module
connects directly to the control panel via the EBUS
and DIALER connectors
(See ‘VDMP3 Installation Instructions” on page 27.)
AUX LED and AUX control button.
(Activates and deactivates the auxiliary
output)
PGM Trigger: This Jumper
allows you to choose whether
the solid-state relay PGMs are
grounded (-) or give out 12V (+).

4 Reference & Installation Manual
2.11 Calculating Power Requirements
1. Using Table 1, calculate the total number of milliamps (mA) required by each device, module, and accessory in the system. Please take into account
devices connected to the control panel’s PGM outputs. Since the BELL output has its own power supply, do not include the sirens connected to it in the
calculation.
2. If Grand Total is less than 700mA, go to step 3. If the value is greater, an external power supply is required (see Figure 5 on page 5) to provide the
additional power needed. Proceed with step 3 and refer to the example in Figure 4 on page 5.
3. Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only a specific number of milliamps
(mA). Using Table 2, determine how many milliamps each length of wire can support. Please note that the total number of milliamps (mA) can never
surpass 700mA.
Table 1: Power Requirement Calculation
Description QTY. mA used by each Total mA
Grafica Graphic LCD Keypads (DNE-K07): _______ X 130mA = __________ mA
LCD Keypads (EVO641): _______ X 110mA = __________ mA
LCD Keypads with Built-in Reader (EVO641R): _______ X 120mA = __________ mA
LED Keypads (DGP2-648): _______ X 110mA = __________ mA
Motion Detector Modules (DG85, DGP2-50/60/70): _______ X 30mA = __________ mA
Door Contact Modules (DGP2-ZC1): _______ X 15mA = __________ mA
1-Zone Expansion Modules (DGP2-ZX1): _______ X 30mA = __________ mA
4-Zone Expansion Modules (APR3-ZX4): _______ X 30mA = __________ mA
8-Zone Expansion Modules (APR-ZX8): _______ X 30mA = __________ mA
Magellan Wireless Expansion Modules (MG-RTX3): _______ X 35mA = __________ mA
4-PGM Expansion Modules (APR3-PGM4): _______ X 150mA = __________ mA
Printer Modules (APR-PRT3): _______ X 25mA = __________ mA
DVACS Modules (DGP2-DVAC): _______ X 40mA = __________ mA
Annunciator Modules (DGP2-ANC1): _______ X 20mA = __________ mA
InTouch Voice-Assisted Arm/Disarm Modules (APR3-ADM2): _______ X 105mA = __________ mA
Hub and Bus Isolator (APR3-HUB2): _______ X 50mA = __________ mA
Access Control Module (DGP-ACM12):
Note: The DGP-ACM12 consumes 130mA from its own power supply.
The DGP-ACM11 consumes 120mA when connected on the combus for power.
_______ X 120mA = __________ mA
Listen-In Module (DGP-LSN4) _______ X 60mA = __________ mA
Internet Module (IP100) _______ X 110mA = __________ mA
Plug-In Voice Module (VDMP3) _______ X 35mA = __________ mA
Other devices such as hardwired motion detectors __________ mA
Maximum available milliamps = 700mA GRAND TOTAL __________ mA
Table 2: Milliamps (mA) Limitations For Each Run of Wire
Gauge: 18AWG,Surface: 0.823mm2Gauge: 22AWG,Surface: 0.326mm2Gauge: 24AWG,Surface: 0.205mm2
Length of each run
of wire
Available
milliamps (mA)
Length of each run
of wire
Available
milliamps (mA)
Length of each run
of wire
Available
milliamps (mA)
30m(100ft.) 700 30m(100ft.) 700 30m(100ft.) 700
61m(200ft.) 700 61m(200ft.) 682 61m(200ft.) 429
91m(300ft.) 700 91m(300ft.) 454 91m(300ft.) 286
122m(400ft.) 700 122m(400ft.) 341 122m(400ft.) 214
152m(500ft.) 690 152m(500ft.) 273 152m(500ft.) 171
183m(600ft.) 575 183m(600ft.) 227 183m(600ft.) 143
213m(700ft.) 493 213m(700ft.) 195
244m(800ft.) 431 244m(800ft.) 170
274m(900ft.) 383 274m(900ft.) 151
305m(1000ft.) 345 305m(1000ft.) 136
457m(1500ft.) 230
610m(2000ft.) 172
762m(2500ft.) 138
914m(3000ft.) 115

EVO Control Panel 5
Figure 4: Sample Power Requirement Calculations
Do not use the same transformer for the control panel and the external power
supplies. Do not install modules more than 914m (3000ft) from the control panel.
2.12 Keypad Zone Connections
Every keypad, except Grafica, has one hardwire input terminal.
Even with the ATZ feature enabled in the control panel, only one device can be
connected to the keypad’s hardwired input terminal. Tamper is not recognized on
keypad zones. The keypad zone follows the control panel’s EOL definition.
The keypad communicates the status of the zone to the control panel via
the combus. The detection device is connected as shown in Figure 3 on
page 3.
Figure 5: External Power Supply Connections
2.13 Addressable Zone Connections
The control panel includes eight hardwired input terminals for use with
traditional hardwired (non-combus) door contacts, smoke detectors and/or
motion detectors.
The control panel also supports hardwire zone expansion modules. Figure
6shows single zone (ATZ disabled) hardwire input terminal connections
recognized by the Digiplex EVO system. For UL listed installations, use
EOL resistor part #2011002000.
Power required by devices connected to control panel’s
auxiliary output must not exceed the auxiliary output’s limit:
(A) + (B) + (C) + (D) + (E) + (F) + (G) = 368mA<700mA = OK
Control Panel
aux. output
= 700mA
61m (200ft)15m (50ft)
APR-PRT3
(A) = 25mA
EVO641
(D) = 110mA
7.5m (25ft)
15m (50ft)
DGP2-70
(E) = 30mA
7.5m (25ft)
APR-ZX8
(B) = 30mA
30m (100ft) 22 AWG
EVO641
(F) = 110mA
15m (50ft)
EVO641
(G) = 110mA
91m (300ft)
290m (950ft)
DGP2-60
(C) = 30mA
305m (1000ft)
As indicated in Table 2 on
page 4, this run of wire can
support 700mA. Total mA on
this run of wire:
(A) 25mA + (B) 30mA =
55mA<700mA = OK
As indicated in Table 2 on
page 4, this run of wire
can support 454mA. Total
mA on this run of wire:
(D) 110mA + (E) 30mA +
(F) 110mA + (G) 110mA
= 360mA<454mA = OK
As indicated in Table 2 on
page 4, this run of wire
can support 136mA. Total
mA on this run of wire:
(A) 25mA + (C) 30mA =
55mA<136mA = OK
Module
Module
Power Supply
152m (500ft) from control panel
152 (500ft) from control panel’s aux. output
Therefore this run = max. 273mA
610m (2000ft) from control panel
152m (500ft) from power supply
Therefore this run = max. 273mA
Milliamps required by devices connected
to a power supply do not draw power
from the control panel’s auxiliary output.

6 Reference & Installation Manual
Figure 6: Single Zone Input Connections 2.14 Double Zone Connections
Enabling the ATZ feature (see section 4.3) allows you to install two
detection devices per input terminal. Connect the devices as shown in
Figure 7. For UL listed Burglary System installations only, use EOL resistor
part #2011002000.
Figure 7: Double Zone Connections
2.15 Combus Connections
The 4-wire combus can support 127 (EVO48) or 254 (EVO192) modules.
Use star and/or daisy chain configuration. The total length of wire cannot
exceed 914m (3000ft).
Before connecting a module to the combus, remove AC and battery power from the
control panel.
2.15.1 Connecting the Combus in Noisy Environments
When installing the combus wires in proximity to high electrical
interferences or across separate buildings, use shielded cables:
Within the Same Building: Strip the outer jacket at one end of the
shielded cable to expose the shield and connect the shield to the control
panel ground (not the dialer ground), while leaving the shield at the other
end of the cable open (floating).
† Enable ATZ (see section 4.3 on page
10) and connect as follows (extra input
cannot be used)
N.C. Contacts, No EOL
CONTROL PANEL TERMINAL
N.C., With EOL
Ul/ULC Configuration
CONTROL PANEL TERMINAL
N.O., With EOL
Ul/ULC Configuration
CONTROL PANEL TERMINAL
N.C. Contacts, No EOL,
With tamper recognition
CONTROL PANEL TERMINAL
N.C. With EOL, With Tamper
& Wire Fault Recognition
UL/ULC Configuration
CONTROL PANEL TERMINAL
N.O., With EOL, With Tamper
& Wire Fault Recognition†
CONTROL PANEL TERMINAL
N.C., No EOL Resistor
CONTROL PANEL TERMINALS
N.C., With EOL and Tamper & Wire Fault
Recognition (UL/ULC)
CONTROL PANEL TERMINALS
N.C., No EOL, With Tamper Recognition
CONTROL PANEL TERMINALS

EVO Control Panel 7
Across Separate Buildings: Strip the outer jacket at one end of the
shielded cable to expose the shield. In the same building as the control
panel, connect the exposed shield to any earth ground available, while
leaving the shield at the other end of the cable open (floating). The same
configuration applies for any subsequent building.
2.16 Fire Circuits
Assign the smoke detectors connected to the control panel or zone
expansion input terminals to a zone and define the zone's parameters as a
Fire Zone (see section 4.4.12 and section 4.4.13 on page 11).
2.16.1 Smoke Detector Installation (2-Wire)*
PGM1 can be defined as a 2-wire
smoke detector input (see section 12.6
on page 29). Connect the 2-wire smoke
detectors as shown in Figure 8. If a line
short occurs or the smoke detector
activates, whether the system is armed
or disarmed, the control panel will
generate an alarm. If the line is open,
the “Zone Fault” trouble indication
appears in the Trouble Display and the
report code is sent to the monitoring
station, if programmed.
*UL Note: Not to be used with UL Listed systems.
2.16.2 ESL CleanMe® Installation
Connect ESL smoke detectors like the standard smoke detectors. Avoid
connecting more than 20 ESL smoke detectors. When an CleanMe signal
is sent, the control panel will generate a Zone Fault trouble and may
transmit the Fire Loop report code to the monitoring station. The trouble will
be cleared if there is no CleanMe signal for 255 seconds. If an alarm
occurs, the trouble will be cleared until it is detected again.
2.16.3 Smoke Detector Installation (4-Wire)
Recommended: System Sensor model
2112/24D smoke detectors. Connect the
4-wire smoke detectors and a relay as
shown in Figure 9. To comply with UL955,
install the 4-wire smoke detectors with 18
gauge wire. If power is interrupted, the
relay causes the control panel to transmit
the Fire Loop Trouble report programmed
in section [2906].
To reset (unlatch), connect the smoke
detector’s negative (-) to a PGM. Then
program the PGM with the “Smoke
Detector Power Reset” activation event
(see section 12.1 on page 29; Event
Group #067, start # 004, end # 004) to
interrupt power to the smoke detector for
four seconds when the [CLEAR]and
[ENTER] keys are pressed and held for two
seconds.
If ATZ is enabled (see section 4.3 on page 10), do not use the extra input (doubled
zone).
Figure 10: Telephone Line Connection Examples
2.17 Telephone Line Connections
The telephone lines can be connected directly to the control panel or
through a CA38A or RJ31 as shown in Figure 10.
UL Note: Installer must verify line seizure after every installation
For TBR-21 compliance, please note the following:
1. The EVO can be connected to the telephone network via an RJ-11
connector.
2. The Maximum Dialing Attempts cannot exceed 15 attempts (page 25).
2.18 Built-in RTC
The RTC will save the EVO’s internal clock when both the AC and battery
power have been lost. The RTC uses a 3V lithium battery (CR2032) with a
battery life of 11 years. Change the battery as shown below:
Figure 11: Changing the RTC’s Battery
Reprogram the control panel’s clock after changing the battery.
Danger of explosion exists if the lithium battery is incorrectly replaced. Replace only
with the same or equivalent type recommended by the manufacturer. Dispose of used
batteries according to the manufacturer’s instructions.
Figure 8:
2-Wire Detectors
Note: It is recommended that the smoke
detectors be connected in a daisy chain
configuration.
PGM1 becomes
input# 255
Smoke detectors
1KW
EOL
N.O. contacts
Figure 9: 4-Wire Detectors
Note: It is recommended that the
smoke detectors be connected in a
daisy chain configuration.
EVO
Dialer
Main line
Ground
clamp
Example 2:
Example 1:
EVO
Dialer
Ground
clamp
Main line
3V Lithium Battery
(CR2032)
Insert the battery with
the positive facing up
and the negative facing
down.
* For installations without EOL, remove 1K

8 Reference & Installation Manual
3 Programming Methods
3.1 WinLoad Uploading/Downloading Software*
We recommend programming the control panel with WinLoad. Refer to
WinLoad Software on page 38 for details.
* UL Note: Not verified by UL
3.2 Paradox Memory Key
The Paradox Memory Key can copy the programmed contents of one
control panel into as many others. Not to be used with UL Listed
systems.
Copy to Memory Key
1. Insert the Memory Key (PMC-4) onto the control
panel’s connector labelled “MEM KEY”.
2. To copy the contents to the Memory Key except
zone numbering and sections [0501] to [0532],
enter installer programming mode, then enter
section [4020]. (Depending on the memory key, the
labels may or may not be included.)
To copy the contents to the Memory Key including
zone numbering and sections [0501] to [0532],
enter section [4021]. (Depending on the memory
key, the labels may or may not be included.)
3. When the keypad emits a confirmation beep, remove the Memory Key.
Remove the write protect jumper.
Download to Control Panel
1) Insert the Memory Key onto the control panel’s
connector labelled “MEM KEY”.
2) To download the contents of the Memory Key except
zone numbering and sections [0501] to [0532], enter
installer programming mode and then enter section
[4010]. (Depending on the memory key, the labels
may or may not be included.)
To download the contents of the Memory Key
including zone numbering and sections [0501] to [0532], enter installer
programming mode and then enter section [4011].(Depending on the
memory key, the labels may or may not be included.)
3) When the keypad emits a confirmation beep, remove the Memory Key.
Figure 12: Using the Memory Key
3.3 Module Broadcast
Keypads and other modules can also be programmed easily by using
Module Broadcast (see section 13.16 on page 31). Once a module is
programmed, its sections can be sent to other similar modules through the
combus.
3.4 Programming Through a Keypad
Use the “EVO Programming Guide” to record how the sections were
programmed. To enter programming mode:
For LCD Keypads: The control panel will save the data and go to the next
section or press the [ENTER]key to save the data and go to the next
section. Press the [CLEAR]key go to the preceding step or to erase the
current data entry.
For Grafica Keypads: Press Grafica’s center action key (Save) to save the
data and go to the next section. Press the right action key (Exit) to go to the
preceding step or press the left action key (Clear) to erase the current data.
3.4.1 Feature Select Programming
Most of the options are programmed using the Feature Select Method.
For LCD Keypads: The option is considered ON when the number
appears within the brackets on the LCD keypad. Turn options ON and OFF
by pressing the corresponding keys on the keypad and then press [ENTER]
to save.
For Grafica Keypads: Select or clear the check boxes or set the options by
pressing the corresponding keys on the keypad. The feature is considered
ON when its check box is selected. Press the Grafica’s center action key
(Save) to save.
3.4.2 Decimal Programming
Sections may require 3-digit decimal values from 000 to 255.
3.4.3 Hexadecimal Programming
Sections may require Hexadecimal values from 0 to F. Press:
For LCD Keypads:
[0] to [9] = values 0 to 9 respectively
[STAY] key = A [DISARM]key = D
[FORCE]key = B [BYP]key = E
[ARM] key = C [MEM]key = F
For Grafica Keypads:
[0] to [9] = values 0 to 9 respectively
[#] = A to F (press the key until the desired letter appears)
3.5 Module Programming Mode
To program a Module with a keypad, enter Module Programming Mode:
The control panel will redirect all programming to the selected module. To
exit the Module Programming Mode, press the [CLEAR]key on LCD
keypads, or the right action key (Exit) on Grafica keypads.
Jumper ON =
Can copy and download
contents of the Memory Key
Jumper OFF =
Cannot override contents
of the Memory Key
1. Press and hold the [0] key.
2. Key in the [INSTALLER CODE] (default = 000000).
3. Key in the 4-digit [SECTION].
4. Key in required [DATA]. Refer to the “EVO Programming Guide” or to
the corresponding sections in this manual.
1. Press and hold the [0] key.
2. Key in the [INSTALLER CODE] (default = 000000).
3. Key in section [4003].
4. Key in 8-digit [SERIAL NUMBER] of the module.
5. Key in 3-digit [SECTION]and required [DATA].Refer to the “Module
Programming Guide” for details.

EVO Control Panel 9
4 Zone Programming
Enter Section [0400], then
enter the number of the
zone you want to program
Enter the zone’s 8-digit
serial and 3-digit input
number (The input number
is not needed for module
with only one input)
Enter the zone’s parameters
(01) (*2*****) default
Enter the zone’s report
codes
(00) (00) (00) (00) default
Enter the zone’s label
Press [ENTER] to save and
go to the next zone
Pressing [CLEAR] twice will
exit the zone programming
menus. Press [ENTER]
before pressing clear to
save your modifications.
Zone Definition Partition Zone Option
_____ _____ 1 2 3 4 5 6 7 8
0 - Disabled (default)
1- Entry Delay 1
2- Entry Delay 2
3- Follow
4- Instant
5- 24Hr Buzzer
6- 24Hr Burglary
7- 24Hr Hold-up
8- 24Hr Gas
9- 24Hr Heat
A- 24Hr Water
B- 24Hr Freeze
C- Delayed 24Hr
Fire
D- Standard 24Hr
Fire
E- Stay Delay 1
F- Stay Delay 2
1 - Assigned to Partition 1
(default)
2- Assigned to Partition 2
3- Assigned to Partition 3
4- Assigned to Partition 4
5- Assigned to Partition 5
6- Assigned to Partition 6
7- Assigned to Partition 7
8- Assigned to Partition 8
[1] Auto Zone Shutdown Enabled
[2] Bypass Enabled (default)
[3] Stay Zone
[4] Force Zone
[5] [6] Zone Alarm Type
off off Steady Alarm
off on Pulsed Alarm
on off Silent Alarm
on on Report Only
[7] Intellizone
[8] Delay before Transmission
.
Ademco slow, Silent Knight fast, SESCOA, Ademco express or Pager formats:
Key-in desired 2-digit hex values from 00 to FF.
Ademco format:
Use section [4032] to program a set of default Ademco report codes from the Auto
Report Code Programming on page 26. Then to program the remaining report
codes or to change some of the defaults, enter the individual sections and key-in
the desired 2-digit hex value found in the Appendix 2: Contact ID Report Code List
on page 42.
SIA format:
Use section [4032] to program a set of SIA report codes from the Auto Report Code
Programming on page 26. Codes that have not been set to default can be set to
default manually by entering FF in the appropriate section. To disable the reporting
of an event, enter 00 in the appropriate section
Alarm Report Code Alarm Restore
Report Code
Tamper Report
Code
Tamper Restore
Report Code
__ / __ __ / __ __ / __ __ / __
In any Zone Programming option, pressing [ACC] will save the data and go
to the next zone on the same option screen. Pressing [TRBL] will save the
data and go to the previous zone on the same option screen.
Input 2
Hardwired
Device B
Control Panel
SN#:020000A2
APR3-ZX8 Module
SN#: 34000041
Input 5
Detector A
SN#: 21000033
C
OMMUNICATION
N
ETWORK
Input Terminals
1 2 3 4 5 6 7 8
Detector A:
Hardwired Device A:
Hardwired Device B:
Hardwired Device C:
Zone#
1 =
2 =
3 =
4 =
Section#
[0001]
[0002]
[0003]
[0004]
Serial#
21000033
1A000252
020000A2
34000041
Input#
N/A
N/A
002
005
Keypad
SN#: 1A000252
Keypad Zone
Hardwired
Device C
Hardwired
Device A
Input Terminals
1 2 3 4 5 6 7 8
Combus

10 Reference & Installation Manual
4.1 Zone Programming
Two different methods can be used to program zones:
4.1.1 Using section [0400]
Allows you to program zones 001 through 192 as shown in the diagram on
page 9.
In any Zone Programming option, pressing [ACC] will save the data
and go to the next zone on the same option screen. Pressing
[TRBL] will save the data and go to the previous zone on the same
option screen.
4.1.2 Using zone serial and input numbers
If you are not using an EVO641 or an EVO641R keypad, you can only
program zones 1 to 96 through sections [0001] to [0096].
4.2 Zone Numbering
SECTION [0400]
SECTIONS [0001] TO [0096]
• To assign an addressable PIR or door contact to the combus, program
the module’s serial number into the section corresponding to the zone.
• To assign a detection device connected to a module or control panel's
hardwired input terminal, program the module's or control panel's serial
number and the input number to the desired zone. See the “Digiplex
Modules Programming Guide” for details of its input numbers (input
numbers not required for keypad zones).
If PGM1 is defined as a smoke detector input (see section 12.6 on page 29), the
control panel will recognize it as input # 255.
4.2.1 Clearing a Zone’s Numbering
Using section [0400]
1. Enter the zone number you wish to delete.
2. Press [0] all the way through the serial/input, parameters and report
codes screen.
3. Press [ENTER]to exit.
Using an LCD Keypad:
1. Enter a section number between [0001] to [0096].
2. Press [0] and then [ENTER]to save and exit.
Using a Grafica Keypad:
1. Enter a section number between [0001] to [0096].
2. Press [0] to clear the serial number.
3. Highlight the input number and then press [0] to clear the data.
4. Press Grafica’s center action key (Save) to save and exit.
4.3 Zone Doubling (ATZ)
SECTION [3033]: OPTION [8]
(default = disabled) Fire Zones cannot be doubled.
4.4 Zone Definitions
4.4.1 Zone Disabled
SECTION [0400]: FIRST DIGIT = 0
SECTIONS [0101] TO [0196]: FIRST DIGIT = 0
Disables the corresponding zone. Zones are disabled by default.
4.4.2 Entry Delays 1 and 2
SECTION [0400]: FIRST DIGIT = 1 AND 2
SECTIONS [0101] TO [0196]: FIRST DIGIT = 1 AND 2
(default Entry Delay 1= 030, Entry Delay 2 = 060) A zone defined as Entry
Delay 1 follows the Entry Delay 1 Timer of its assigned partition. A zone
defined as Entry Delay 2 follows the Entry Delay 2 Timer of its assigned
partition. Each partition includes two Entry Delay Timers. To program an
Entry Delay Timer, key in the desired 3-digit delay value (001 to 255
seconds) into the corresponding section.
These are the same timers used for Stay Delay zones.
4.4.3 Follow Zones
SECTION [0400]: FIRST DIGIT = 3
SECTIONS [0101] TO [0196]: FIRST DIGIT = 3
The control panel waits until the end of the Entry Delay before generating
an alarm if an Entry Delay zone opens before the Follow zone.
4.4.4 Instant Zones
SECTION [0400]: FIRST DIGIT = 4
SECTIONS [0101] TO [0196]: FIRST DIGIT = 4
When an armed Instant zone opens, the control panel immediately
generates an alarm.
4.4.5 24Hr Buzzer Zones
SECTION [0400]: FIRST DIGIT = 5
SECTIONS [0101] TO [0196]: FIRST DIGIT = 5
Whenever a 24Hr Buzzer zone opens, the control panel activates the
keypad buzzer to indicate that the zone was breached. The control panel
will report the alarm, but will not enable the bell/siren output. Enter any valid
access code on the keypad to stop the buzzer.
The keypads must be assigned to the same partition as the 24Hr Buzzer zone or the
buzzer will not activate. UL Note: Not to be used for perimeter protection.
4.4.6 24Hr Burglary Zones
SECTION [0400]: FIRST DIGIT = 6
SECTIONS [0101] TO [0196]: FIRST DIGIT = 6
When a 24Hr Burglary zone opens, the control panel will immediately
generate a burglary alarm.
4.4.7 24Hr Hold-up Zones
SECTION [0400]: FIRST DIGIT = 7
SECTIONS [0101] TO [0196]: FIRST DIGIT = 7
When a 24Hr Hold-up zone opens, the control panel will immediately
generate an alarm.
The SIA FSK reporting format includes specific codes to identify the
alarm as a Hold-up, Gas, Heat, Water, or Freeze Alarm.
Zone
Number
Zone
Numbering
Zone
definitions
Zone Partition
Assignment Zone Options
1 [0001] [0101] [0201] [0301]
2 [0002] [0102] [0202] [0302]
+1 per zone +1 per zone +1 per zone +1 per zone
96 [0096] [0196] [0296] [0396]
Input Doubled Zone Input
Input 01 Input 09 (ATZ of Input 01)
Input 02 Input 10 (ATZ of Input 02)
Input 03 Input 11 (ATZ of Input 03)
Input 04 Input 12 (ATZ of Input 04)
Input 05 Input 13 (ATZ of Input 05)
Input 06 Input 14 (ATZ of Input 06)
Input 07 Input 15 (ATZ of Input 07)
Input 08 Input 16 (ATZ of Input 08)
Partition 1
Entry Delay 1 Timer: [3111]
Entry Delay 2 Timer: [3112]
Partition 2
Entry Delay 1 Timer: [3211]
Entry Delay 2 Timer: [3212]
Partition 3
Entry Delay 1 Timer: [3311]
Entry Delay 2 Timer: [3312]
Partition 4
Entry Delay 1 Timer: [3411]
Entry Delay 2 Timer: [3412]
Partition 5
Entry Delay 1 Timer: [3511]
Entry Delay 2 Timer: [3512]
Partition 6
Entry Delay 1 Timer: [3611]
Entry Delay 2 Timer: [3612]
Partition 7
Entry Delay 1 Timer: [3711]
Entry Delay 2 Timer: [3712]
Partition 8
Entry Delay 1 Timer: [3811]
Entry Delay 2 Timer: [3812]

EVO Control Panel 11
4.4.8 24Hr Gas Zones*
SECTION [0400]: FIRST DIGIT = 8
SECTIONS [0101] TO [0196]: FIRST DIGIT = 8
When a 24Hr Gas zone opens, the control panel will immediately generate
an alarm.
4.4.9 24Hr Heat Zones**
SECTION [0400]: FIRST DIGIT = 9
SECTIONS [0101] TO [0196]: FIRST DIGIT = 9
When a 24Hr Heat zone opens, the control panel will immediately generate
an alarm.
** UL Note: UL Listed compatible devices must be used for UL systems. For
UL Listed systems, this type of zone should be programmed as a pulsing Fire
alarm.
4.4.10 24Hr Water Zones*
SECTION [0400]: FIRST DIGIT = A
SECTIONS [0101] TO [0196]: FIRST DIGIT = A
When a 24Hr Water zone opens, the control panel will immediately
generate an alarm.
4.4.11 24Hr Freeze Zones*
SECTION [0400]: FIRST DIGIT = B
SECTIONS [0101] TO [0196]: FIRST DIGIT = B
When a 24Hr Freeze zone opens, the control panel will immediately
generate an alarm.
* UL Note: UL Listed compatible devices must be used for UL systems. For UL
Listed systems, this type of zone must be programmed as a silent auxiliary
alarm.
4.4.12 Delayed 24Hr Fire Zone (Not to be used with UL Listed systems)
SECTION [0400]: FIRST DIGIT = C
SECTIONS [0101] TO [0196]: FIRST DIGIT = C
The Delayed 24Hr Fire Zone definition from Figure 14 on page 12 is used in
homes where a smoke detector often generates false alarms. A zone
programmed as Fire becomes normally open and requires an EOL resistor.
The keypads must be assigned to the same partition as the Delayed 24Hr Fire zone
for the buzzer to activate.
* UL Warning: For UL/ULC installations, a Fire zone cannot be bypassed and its
alarm type must be Pulsed (audible).
4.4.13 Standard 24Hr Fire Zone
SECTION [0400]: FIRST DIGIT = D
SECTIONS [0101] TO [0196]: FIRST DIGIT = D
A zone programmed as Fire becomes normally open and requires an EOL
resistor. When a Standard 24Hr Fire Zone triggers, the control panel can:
• send a Zone Alarm report code (see section 9.2.1 on page 22).
• send a Fire Loop Trouble Report (see section 9.2.11 on page 23) if a
tamper/wiring fault occurs on a Fire Zone. A “Zone Fault Trouble” will
also appear in the keypad's Trouble Display.
• generate a Fire alarm, which can be silent, pulsed, steady or report only.
Fire alarms generate an intermittent signal (see Figure 13).
* UL Warning: For UL/ULC installations, a Fire Zone cannot be bypassed
and its alarm type must be Pulsed (audible).
Figure 13: Bell/Siren Output During Fire Alarm
4.4.14 Stay Delay Zone
SECTION [0400]: FIRST DIGIT = E AND F
SECTIONS [0101] TO [0196]: FIRST DIGIT = E AND F
Using the Regular or Force arming methods, the control panel processes
the zone as an Instant zone (see section 4.4.4 on page 10). Using the Stay
or Instant arming methods and the zone is triggered, the control panel will
not generate an alarm until the programmed Stay Delay elapses. A zone
defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned
partition. A zone defined as Stay Delay 2 follows the Entry Delay 2. To
program the Entry Delay Timers, refer to Entry Delays 1 and 2 on page 10.
4.5 Zone Partition Assignment
SECTION [0400]: SECOND DIGIT = 1 TO 8
SECTIONS [0101] TO [0196]: SECOND DIGIT = 1 TO 8
Assign zones to one partition.
4.6 Zone Options
The zone options from are described below. Refer to the EVO programming
guide for additional information on Zone Programming.
4.6.1 Auto Zone Shutdown
SECTION [0400]: OPTION [1]
SECTIONS [0101] TO [0196]: OPTION [1]
(default = 000) When enabled, the control panel will stop generating alarms
once the Auto Zone Shutdown Limit is reached. It resets every time the
partition that is assigned to the corresponding zone is armed. To program
the Auto Zone Shutdown Limit, enter the desired 3-digit counter (000 to
015) into section corresponding to the desired partition (000 = disabled):
4.6.2 Bypass Zones
SECTION [0400]: OPTION [2]
SECTIONS [0101] TO [0196]: OPTION [2]
(default = enabled) Allow zones to be Manually Bypassed.
4.6.3 Stay Zones
SECTION [0400]: OPTION [3]
SECTIONS [0101] TO [0196]: OPTION [3]
Only zones with option [3] enabled will be bypassed when the partition is
Stay armed or Instant armed. All other zones will remain activated. Fire
Zones cannot be set as Stay Zones.
4.6.4 Force Zones (Not to be used with UL Listed systems)
SECTION [0400]: OPTION [4]
SECTIONS [0101] TO [0196]: OPTION [4]
Only zones with option [4] enabled can be bypassed when the partition is
Force armed. Fire Zones cannot be Force Zones.
Partition 1: [3114] Partition 5: [3514]
Partition 2: [3214] Partition 6: [3614]
Partition 3: [3314] Partition 7: [3714]
Partition 4: [3414] Partition 8: [3814]

12 Reference & Installation Manual
4.6.5 Alarm Types
SECTION [0400]: OPTION [2] & [6]
SECTIONS [0101] TO [0196]: OPTIONS [5] & [6]
4.6.6 Intellizone*
SECTION [0400]: OPTION [7]
SECTIONS [0101] TO [0196]: OPTION [7]
(default = 032) If an alarm condition occurs on a zone with option [7]
enabled, the control panel triggers the Intellizone Delay. Fire Zones cannot
be set as Intellizones. An alarm will only be generated if the selected
conditions occur during the Intellizone Delay:
1. An alarm occurs on another zone defined as Intellizone.
2. The zone in alarm restores and reoccurs.
3. The zone stays in alarm for the entire Intellizone Delay.
Key in the desired 3-digit delay value (010 to 255 seconds, default value is
32 seconds) into the section corresponding to the desired partition
Any value less than 10 seconds will be replaced by the default
value of 32 seconds.
* UL Note: For UL Listed systems, the detection pattern of both zones must
be installed so that each zone has the capability of protecting the area alone.
4.6.7 Intellizone Options
Use these options to enable or disable different Intellizone related options.
Figure 14: Delayed 24Hr Fire Zone
4.6.8 Delay Before Alarm Transmission
SECTION [0400]: OPTION [8]
SECTIONS [0101] TO [0196]: OPTION [8]
(default = 000) When an alarm condition occurs on a zone with option [8]
enabled, the alarm will not be reported to the monitoring station until the
end of the Alarm Transmission Delay. Disarming the system cancels any
report originating from this zone. To program the Alarm Transmission Delay,
access section [3055].
4.7 Input Speed
(001 to 255 X 30msec, default = 600ms)
The Input Speed defines how quickly the control panel responds to an open
zone detected on any hardwired input terminal (does not apply to
addressable motion detectors and door contacts). Set the Input Speed (001
to 255 X 30ms, default = 600ms):
Option Feature Description
[5] [6]
OFF OFF Steady Alarm sends the report code and activates the bell
output
ON OFF Pulsed Alarm sends the report code and pulses the bell output
(see Figure 14)
OFF ON Silent Alarm sends the report code, but the bell output is not
activated. Partition must be disarmed.
ON ON Report Only sends the report code. Disarming is not required.
Partition 1: [3110] Partition 3: [3310] Partition 5: [3510] Partition 7: [3710]
Partition 2: [3210] Partition 4: [3410] Partition 6: [3610] Partition 8: [3810]
Partition 1: [3126] Partition 3: [3326] Partition 5: [3526] Partition 7: [3726]
Partition 2: [3226] Partition 4: [3426] Partition 6: [3626] Partition 8: [3826]
Option Description
[1] Intellizone Delay (default = disabled)
The zone stays in alarm for the entire Intellizone Delay.
[2]
Intellizone Double Knockout and Zone Crossing (default =
disabled)
The zone in alarm restores and reoccurs or an alarm occurs on
another zone defined as Intellizone
[3] Intellizone Zone Crossing (default = disabled)
An alarm occurs on another zone defined as Intellizone.
[5] Police Code is Generated on Zone Crossing Only (default =
disabled)
[0961] Input 01 [0973] Input 13 (ATZ of Input 01)
[0962] Input 02 [0974] Input 14 (ATZ of Input 02)
[0963] Input 03 [0975] Input 15 (ATZ of Input 03)
[0964] Input 04 [0976] Input 16 (ATZ of Input 04)
[0965] Input 05 [0977] Input 13 (ATZ of Input 01)
[0966] Input 06 [0978] Input 14 (ATZ of Input 02)
[0967] Input 07 [0979] Input 15 (ATZ of Input 03)
[0968] Input 08 [0980] Input 16 (ATZ of Input 04)
Latch alarm and transmit
report code as described
in section 4.4.13
Delayed Fire Zone
Triggered
Bell/siren silenced. Delay report
transmission an additional 90s.
Activate bell/siren output & delay
report transmission for 30s.
Has the zone
closed within
30s?
Yes
Yes
Yes
Yes
No
No
No
No
Has a 2nd
Delayed Fire
Zone opened
in 30s?
Any key on
keypad
pressed
within 30s?
Problem
corrected?
END
Alarm Disabled

EVO Control Panel 13
4.8 EOL on Hardwire Zones
SECTION [3033]: OPTION [7]
(default = disabled) If detection devices connected to hardwired input
terminals use 1kend of line resistors, enable option [7] in section [3033].
For details on using EOL resistors, refer to Addressable Zone Connections
on page 5 and Double Zone Connections on page 6.
4.9 Keypad Numbering
SECTIONS [2801] TO [2832]
Keypad Numbering identifies the keypad in the event buffer. The keypad is
assigned to a Keypad Number from 1 to 32 through the keypad's serial
number in sections [2801] to [2832].

14 Reference & Installation Manual
5 Remote Control Programming
5.1 Hardware Requirements
5.2 Remote Control Template
It is possible to set up to 16 different button templates which can then be
assigned to individual users. Each user is pre-programmed with a default
remote control button pattern: (1 B) (C 0) (template 1).
If the EVO48 System Includes:
MG-RTX3 Wireless Expansion Module And EVO641 / EVO641R keypad
Up to 96 remote controls can now be programmed into the EVO control
panel and configured using a master code or installer code.
If the EVO192 System Includes:
MG-RTX3 Wireless Expansion Module And EVO641 / EVO641R keypad
Up to 999 remote controls can now be programmed into the EVO control
panel and configured using a master code or installer code.
If the System Includes:
MG-RTX3 Wireless Expansion Module But does not include:EVO641 /
EVO641R keypad. Remote controls must be stored in the wireless
expansion module (32 remotes per MG-RTX3) by enabling option [1] in
section [3029].
Section Option Description
[2940]
Default button
Te m p l at e
To select a button template as
the default template, enter (00)
to (15) representing button
templates in sections [2900] to
[2915].
[2941]
Assign Button
Te m p l at e
To assign a button template to
a user, select user when
prompted, then enter (00) to
(15) representing button
templates in sections [2900] to
[2915].
Section Template# Button Options
[2900] Template 1 (__/__) (__/__)
[2901] Template 2 (__/__) (__/__)
[2902] Template 3 (__/__) (__/__)
[2903] Template 4 (__/__) (__/__)
[2904] Template 5 (__/__) (__/__)
[2905] Template 6 (__/__) (__/__)
[2906] Template 7 (__/__) (__/__)
[2907] Template 8 (__/__) (__/__)
[2908] Template 9 (__/__) (__/__)
[2909] Template 10 (__/__) (__/__)
[2910] Template 11 (__/__) (__/__)
[2911] Template 12 (__/__) (__/__)
[2912] Template 13 (__/__) (__/__)
[2913] Template 14 (__/__) (__/__)
[2914] Template 15 (__/__) (__/__)
Button 1 Button 2 Button 3
Button 2+3
Disarm
MG-REM1
MG-REM2
Default
(1 B) (C 0)
Regular
Arm
Utility
Key 1
Utility
Key 2 Disabled
Disarm:
cannot be
modified
+
+
(1B) (C0) (00) (00) future use
Table 3: Template Entries
Entry Function Entry Function
[0] Button Disabled [8] Panic 1
[1] Regular Arm [9] Panic 2
[2] Stay Arm A = [stay] Panic 3
[3] Instant Arm B = [force] Utility Key 1
[4] Force Arm C = [arm] Utility Key 2
[5] N/A D = [disarm] Utility Key 3
[6] N/A E = [byp] Utility Key 4
[7] N/A F = [mem] N/A

EVO Control Panel 15
6 Keyswitch Programming
6.1 Keyswitch Numbering
SECTIONS [0501] TO [0532]
Keyswitch Numbering allows you to assign any hardwired input in the
system to any of the 32 keyswitch zones in the control panel (see Figure
15). UL Note: Do not use Keyswitches in UL Listed systems.
Figure 15: Example of Keyswitch Numbering
6.2 Keyswitch Definitions
Keyswitch Definitions determine how a keyswitch is used.
6.2.1 Keyswitch Disabled
SECTIONS [0601] TO [0632]: FIRST DIGIT = 0
Disables keyswitch input.
6.2.2 Momentary Keyswitch
SECTIONS [0601] TO [0632]: FIRST DIGIT = 1
To arm or disarm a partition using the Momentary Keyswitch, turn on the
keyswitch for three seconds then turn it off.
6.2.3 Maintained Keyswitch
SECTIONS [0601] TO [0632]: FIRST DIGIT = 2
To arm a partition using the Maintained Keyswitch, turn the switch from the
ON to the OFF position. Disarm it by setting the key on the ON position.
6.2.4 Generates a Utility Key Event on Open
SECTIONS [0601] TO [0632]: FIRST DIGIT = 3
To program a keyswitch to generate a Utility Key Event:
1. Program the Activation Event of a PGM output with the Utility Key
Event corresponding to the desired keyswitch (see PGM
Programming Table in the "EVO Programming Guide": Event Group
048).
2. Enable option [3] in the section corresponding to the desired
keyswitch.
6.2.5 Generates a Utility Key Event on Open and Close
SECTIONS [0601] TO [0632]: FIRST DIGIT = 4
A Utility Key Event can be generated whenever the keyswitch input is
opened or closed. The Utility Key Events increase from 32 to 64 events;
one event for each state.
When a keyswitch is defined with the Generate a Utility Key Event on Open
and Close option, the Keyswitch Partition Assignment and Keyswitch
Options are disabled. To program a keyswitch to generate a Utility Key
Event:
1. Program the Activation Event of a PGM output with the Utility Key
Event corresponding to the desired keyswitch (see PGM Programming
Table in the "EVO Programming Guide": Event Group 048).
2. Enable option [4] in the section corresponding to the desired
keyswitch.
6.3 Keyswitch Partition Assignment
SECTIONS [0601] TO [0632]: SECOND DIGIT = 1 TO 8
Each keyswitch must be assigned to one partition.
6.4 Keyswitch Options
Each keyswitch zone can be programmed with one or more options.
6.4.1 Disarm Only
Sections [0601] to [0632]: Option [3]
When enabled, the keyswitch can only disarm assigned partitions. The type
of disarming is determined by the other Keyswitch Options selected.
6.4.2 Stay/Instant Disarm Option (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [4]
When enabled, the keyswitch can only disarm assigned Stay or Instant
armed partitions. When option [4] is disabled, the keyswitch can disarm
partitions armed using any arming method.
6.4.3 Arm Only (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [5]
When enabled, the keyswitch can only arm assigned partitions. The type of
arming is determined by the other Keyswitch Options selected.
6.4.4 Regular Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [6] TO [8]
With disabled, the arming option will be Regular arming.
6.4.5 Stay Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [6]
Activating the keyswitch will Stay Arm the partition.
6.4.6 Force Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [7]
Activating the keyswitch will force arm the selected partition.
6.4.7 Instant Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [8]
This option is identical to Stay arming except that all armed zones will
become Instant Zones (see section 4.4.4 on page 10).
Only one of the arming options (Stay, Force, Instant and Regular)
can be selected.
Control Panel
SN#: 020000A2
Keyswitch B Keyswitch C
Keyswitch
Zone # Section Serial# Input#
Keyswitch A: 1 = [0501] 020000A2 001
Keyswitch B: 2 = [0502] 34000041 002
Keyswitch C: 3 = [0503] 34000041 006
Input 2
Input 6
Keyswitch A
Input 1
Input Terminals
1 2 3 4 5 6 7 8
C
OMMUNICATION
N
ETWORK
Zone Expansion Module
SN#: 34000041
Input Terminals
1 2 3 4 5 6 7 8
Combus

16 Reference & Installation Manual
7 Arming and Disarming Options
7.1 Arming Follows Partition
(default = disabled) A partition can be set to follow the arming and
disarming status of one or more partitions.
7.2 Trouble Latch
SECTION [3033]: OPTION [6]
With the Trouble Latch feature disabled, when a trouble occurs and is
corrected, the trouble is automatically cleared and no longer displayed.
With the Trouble Latch feature enabled, the trouble will remain displayed
until it is manually cleared by the user. To clear the trouble, the user must
enter the trouble display and then exit the trouble display. For LCD and
LED keypads, press [CLEAR]to exit. For Grafica keypads, press the left
action key (Back) to exit.
Only troubles that have been corrected can be cleared. If a
trouble has not been corrected, it will continue to be displayed
even if the user tries to clear the trouble by using the method
described above.
7.3 Restrict Arming on Supervision Loss
SECTION [3034]: OPTION [4]
(default = disabled) When enabled, arming is restricted if a supervision
loss signal from the Magellan Wireless System MG-RTX3 is received.
7.4 Restrict Arming on Tamper
SECTION [3034]: OPTION [8]
(default = disabled) When enabled, the control panel prevents arming if it
detects a tamper on a zone or module (see section 8.5 on page 19).
Partitions will not arm until the Installer Code is entered and the tamper
trouble conditions are corrected.
7.5 Restrict Arming on AC Failure
SECTION [3035]: OPTION [1]
(default = disabled) When enabled, the control panel prevent arming if it
detects a loss of AC power.
7.6 Restrict Arming on Battery Failure
SECTION [3035]: OPTION [2]
(default = disabled) When enabled, the control panel prevents arming if it
detects a battery loss or if the battery voltage is less than 10.5V.
7.7 Restrict Arming on Bell or Auxiliary Failure
SECTION [3035]: OPTION [3]
(default = disabled) When enabled, the control panel prevents arming if:
• the bell or siren is disconnected
• the Bell Output has exceeded its current limits
• the Auxiliary Outputs have exceeded their current limits
7.8 Restrict Arming on TLM Failure
SECTION [3035]: OPTION [4]
(default = disabled) When enabled, the control panel can prevent arming if
it is unable to access the telephone line.
7.9 Restrict Arming on Module Troubles
SECTION [3035]: OPTION [5]
(default = disabled) When is enabled, the control panel uses the same
Restrict Arming options for the modules connected to the combus.
7.10 Timed Auto-Arming
(default = disabled) The control panel arms the selected partition every day
at the time set (see section 7.10.1). A 60-second Exit Delay (default value)
triggers before the partition arms. It can be cancelled or postponed by
entering a valid access code. If zones are open, the control panel arms the
partition and considers all open zones as temporarily bypassed (except
24hr. zones). The control panel transmits the Auto-Arming report code
programmed in section [3910]. The control panel will transmit the Late to
Close report code programmed in section [3912]. Enable option [1] in the
desired section:
7.10.1 Auto-Arm Timer
Enter the time when the partition should arm in the desired section:
7.10.2 Postpone Auto-Arming
(default = 000) It is possible to postpone auto-arming for a preset amount of
time by entering a valid user code during the exit delay. The delay is set by
entering a number between 001 and 255 in the appropriate section. That
number represents for how many increments of 15 minutes the arming will
be postponed.
7.11 No Movement Auto-Arming
(default = disabled) If no movement occurs in a partition for the specified
period, the control panel will automatically arm that partition. The Auto-
Arming Option determines the arming method (see section 7.12). The
control panel will transmit the No Movement report code programmed in
section [3913] upon arming. The control panel will always transmit the Late
to Close report code [3912]. Enable option [2] in the desired section:
7.11.1 No Movement Timer
(default = 000) Select the section corresponding to the desired partition and
program the time without movement necessary before the control panel will
arm and/or send the No Movement report code. If No Movement Auto-
Arming is disabled, the control panel can still send the No Movement report
code. Enter the time period (001 to 255 x 5 minutes, 000 = disabled) when
the partition should arm in the desired section:
7.11.2 No Movement Schedule
It is possible to program the No-movement arming option for each partition
to follow a schedule. These schedules, which function like access
schedules, will ensure that No-Movement arming only occurs during these
specified periods and not at any moment when there is no movement.
Section:
Partition 1: [3121]
Partition 2: [3221]
Partition 3: [3321]
Partition 4: [3421]
Partition 5: [3521]
Partition 6: [3621]
Partition 7: [3721]
Partition 8: [3821]
Partition arms & disarms with:
Option [1] = Partition 1
Option [2] = Partition 2
Option [3] = Partition 3
Option [4] = Partition 4
Option [5] = Partition 5
Option [6] = Partition 6
Option [7] = Partition 7
Option [8] = Partition 8
Partition 1: [3122] Partition 3: [3322] Partition 5: [3522] Partition 7: [3722]
Partition 2: [3222] Partition 4: [3422] Partition 6: [3622] Partition 8: [3822]
Partition 1: [3101] Partition 3: [3301] Partition 5: [3501] Partition 7: [3701]
Partition 2: [3201] Partition 4: [3401] Partition 6: [3601] Partition 8: [3801]
Partition 1: [3120] Partition 3: [3320] Partition 5: [3520] Partition 7: [3720]
Partition 2: [3220] Partition 4: [3420] Partition 6: [3620] Partition 8: [3820]
Partition 1: [3122] Partition 3: [3322] Partition 5: [3522] Partition 7: [3722]
Partition 2: [3222] Partition 4: [3422] Partition 6: [3622] Partition 8: [3822]
Partition 1: [3107] Partition 3: [3307] Partition 5: [3507] Partition 7: [3707]
Partition 2: [3207] Partition 4: [3407] Partition 6: [3607] Partition 8: [3807]
This manual suits for next models
1
Table of contents
Other Digiplex Security System manuals