This brief instruction of mounting the FlexxPump 125 DLS
addresses to experienced users. Please visit
www.dls-schmiersysteme.de to download the complete user
manual including all safety instructions.
1. Product details FlexxPump 125 DLS
No. Description
0 FlexxPump 125 DLS
1 LCD
2 Electric interface M12x1
3 Lubricant outlet / M16 male thread for bottom mounting
4 M5 female thread for bottom mounting
5 Serial number
6 M5 female thread for rear mounting
7 Cartridge sensor
8 Lubricant inlet with thread for cartridge
9 Nameplate with designation and CE mark
0
2. Technical data
Housing
Mounting options backside: female thread M5 (2x)
bottom: f. thread M5 (1x), m. thread G1/4(1x)
Max. Torque mounting 3 Nm
Mounting position upright
Operating temperature -10 bis +60 °C
Lubricant and hydraulic
Number of lubrication
points
up to 4 by using splitters*
up to 10 by using progressive distributors*
Max. Pressure 50 (-10 % / +15 %) bar
Grease delivery Per stroke 0,15 cm³
Electrics
Operating voltage 24 (20...28) V
Protection 0,75 (slow blow) A
Protection class IP 54
* The stated value is down to the individual application and may
extensively differ in some cases (depending on the lubricant and further
conditions).
3. Mounting
1. Remove the yellow protective cap from the top of the lubricant
inlet of the FlexxPump 125 DLS.
2. Unscrew the yellow protective cap counterclockwise from the
lubricant outlet on the bottom of of the FlexxPump 125 DLS.
Remove the black protective cap from the electrical interface
on the bottom of the FlexxPump 125 DLS.
3. To connect the FlexxPump 125 DLS with an external power
supply system add a proper connecting cable to the electrical
interface on the bottom of the FlexxPump 125 DLS.
4. Turn the cap on the lubricant cartridge counterclockwise and
pull it off.
5. Place the full lubricant cartridge with the lable up front on the
FlexxPump 125 DLS. Turn the lubricant cartridge twice clockwi-
se onto the FlexxPump 125 DLS.
DANGER
Damaged or awed electrical connections or un-
licensed hot components lead to heavy injuries or
even death.
4. Commissioning
1. Mechanical fastening
Fix the FlexxPump 125 DLS mechanically through the M5
female threads or through the G1/4 male thread of the lubricant
outlet. Pay particular attention to the maximum tightening
torques permissible for the M5 female threads!
2. Electrical connection
3. Power on
4. Execute FIL function
5. Hydraulic connection
Connect the consumer hydraulically to the FlexxPump 125 DLS.
If you connect tubes to the FlexxPump 125 DLS, make sure that
tubes and connectors are installed tightly, cleanly and correctly.
Ideally, use tubes prelled with the appropriate lubricant.
5. Operation and settings
5.1 Default settings, operating mode: impulse mode PUL
Impulse mode PUL enables embedding the FlexxPump 125 DLS in
an external control (PLC) to command and control the device. The
number of strokes (one stroke=0.16 cm³) dispensed now depend on
the PLC’s signals.
1
2
4
3
56
7
8
9
5.2 Input and output signals
PIN assignment - time control
PIN Assignment Colour
1 +24 V DC brown
2 unallocated white
3 ground blue
4 output signal black
Type: M12x1 female connector; 4-pin; A-coded
The FlexxPump 125 DLS can be switched off completely by switching
off the supply voltage.
The output signal at PIN 4 can be tapped for further processing
(e.g. indicator light or external control). The maximum permissible
current output must not exceed
Imax < 20mA. No inductive load (e.g. relay) may be connected!
In pulse control mode the FlexxPump 125 DLS operates as a pulse-
controlled lubrication system only if unalterable input signals (high
level) are transmitted from the PLC to the FlexxPump 125 DLS via
PIN 2 in a dened sequence. the FlexxPump 125 DLS signals the
respective status to the PLC via high/low levels which can be tapped
off at PIN 4.
To operate the FlexxPump 125 DLS via an external controller
(PLC) in pulse control mode a program corresponding to the
communication protocol must be created in the PLC.
PIN2: Input signal PLC FlexxPump 125 DLS
The FlexxPump 125 DLS provides the following unalterably dened
control signals (input signals) which must be transmitted from the
PLC to the FlexxPump 125 DLS via PIN 2 of the electrical M12x1
interface as high level (+24 V DC).
The control signals must be generated as high level (+24 V) by the
external controller (PLC) over certain times with a tolerance of +/-
0.1 seconds.
Signal length in
seconds
Description Function
2 high Signal 2 seconds 1 stroke
12 high Signal 12 seconds FIL-Function
14 high Signal 14 seconds Error acknowledgement
32
1
4