DOD Technologies EC20x User manual

EC20x
Electrochemical Gas Detector Cabinet
Operating Manual

3
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
Chapter 1 – Overview
1.1 Introduction
DOD Technologies’ EC20x Gas Detector Cabinet is designed to house a series of single-point electrochemical
gas detectors – see specifications for compatibility. While creating a centralized hub, the EC20x is fully
customizable from the factory. This transforms a seemingly ordinary cabinet into a robust toxic gas
monitoring system (TGMS) with improved transport time and extractive detection from distances up to 600
feet.
1.2 Theory of Operation
The EC20x simply requires AC power (110VAC or 230VAC – pump dependent), sample tubing - 1/4” OD x
3/16” ID FEP Teflon (up to 20 points) and exhaust tubing – 3/8” OD x ¼” ID x 25’ maximum (two required and
provided with your system).
The cabinet comes standard with (4) pumps total (one for points 1-10, one for points 11-20, and one backup
pump for each in case of a pump failure). If the instrument detects a pump failure, the backup pump switches
automatically and notifies the user of the problem via a Form C (NO, NC, COM) output relay (one output relay
for each primary pump). The EC20x also has a redundant power supply in case of failure and (2) Form C
relays to notify the user in the event of a failure.
WARNING : If the system is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.

8
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
Chapter 3 – Maintenance Alarms
Maintenance alarms are intended for the user to indicate a pump or power supply has failed. However, the
system will continue to operate utilizing the redundant/backup unit. While the system will continue to
operate, maintenance is recommended as soon as possible to maintain operation with a backup unit in place.
3.1 Vacuum Pumps with Form C Relays
The EC20x utilizes primary and redundant vacuum pumps with Form C Relays:
•Pump 1 primary for points 1-10
•Pump 2
redundant
for points 1-10
•Pump 3 primary for points 11-20
•Pump 4
redundant
for points 11-20
Figure 3.1 – EC20x control DIN rail view
Figure 3.1.1 – View of Form C Relays for maintenance alarms

9
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
3.2 Normal Operation of Form C Relays for Maintenance Alarms
3.2.1 Vacuum Pump PUMP1FAIL Form C Relay
The Form C relay LED indicator is OFF under normal operation. Meaning the main vacuum pump is
running the system. The relay is under the NC (normally closed contact position). Also note the Latching
relay PUMP 1 RED LED is ON.
Figure 3.2.1
If the system is running with the Redundant/Backup pump the Form C relay LED indicator is ON under the
maintenance alarm condition. Meaning the Redundant/Backup pump is running the system. The relay is
under the NO (normally open contact position). Also note the Latching relay PUMP 1 RED LED is OFF.
Figure 3.2.1.1

10
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
3.2.2 Vacuum Pump PUMP3FAIL Form C Relay
The Form C Relay LED indicator is OFF under normal operation. This indicates the primary vacuum pump is
running the system. The relay is under the NC (normally closed contact position). Also note the Latching relay
PUMP 3 RED LED is ON.
Figure 3.2.2
If the system is running with the Redundant/Backup pump the Form C Relay LED indicator is ON under the
maintenance alarm condition. This indicates the Redundant/Backup pump is running the system. The relay is
under the NO (normally open contact position). Also note the Latching relay PUMP 1 RED LED is OFF.
Figure 3.2.2.1

11
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
3.2.3 Power Supply Maintenance Alarm P/S 1 FAIL
The Form C Relay LED indicator is ON under normal operation. This indicates the main power supply is
running the system. The relay is under the NO (normally open contact position). Also note the
redundancy module LED1 and P/S 1 DC OK green LEDs are ON.
Figure 3.2.3
If the system is running with the Redundant/Backup pump the Form C Relay LED indicator is OFF under
the maintenance alarm condition. This indicates the main power supply is running the system. The relay
is under the NC (normally closed contact position). Also note the redundancy module LED1 and P/S 1 DC
OK green LEDs are OFF.
Figure 3.2.3.1

12
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
3.2.4 Power Supply Maintenance Alarm P/S 2 FAIL
The Form C Relay LED indicator is ON under normal operation. This indicates the main power supply is
running the system. The relay is under the NO (normally open contact position). Also note the
redundancy module LED2 and P/S 2 DC OK green LEDs are ON.
Figure 3.2.4
If the system is running with the Redundant/Backup pump the Form C relay LED indicator is OFF under
the maintenance alarm condition. Meaning the main power supply is running the system. The relay is
under the NC (normally closed contact position). Also note the redundancy module LED2 and P/S 2 DC
OK green LEDs are OFF.
Figure 3.2.4.1

13
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
3.3 4-20mA EC20x Centralized Option (2-910-003)
When this option is installed, each extractive gas detector unit has the 4-20mA pre-wired to terminal
blocks. Those pre-wired to terminal blocks are numbered according to the point.
Figure 3.3

14
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
Chapter 4 – EC20x Modbus Interface Option for Cosmos PS-7-M
Optional Modbus communication protocol for New Cosmos PS-7-M units provide a remote means to
monitor the entire system. *
Please contact us for info regarding other compatible gas detector units.
4.1 EC20x Modbus Interface (Option 2-910-002)
NOTE: The DIP switches are accessible when the address plate is removed. To remove the address plate,
refer to 7-1. “Operation Procedure” of the PS-7-M series gas detector’s instruction manual.

15
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
4.2 DIP Switch Setup
MODE DIP SWITCH: Set Far right dip switched as follows below, Left switch off, and Right switch ON.
Set the IP address type: “DY” or “ST” Select the IP address type between “Dynamic” and “Static” by using the
IP address type switch. When “Dynamic” is selected, IP address will be automatically assigned to the
detector. The setting here is active when the “ETHERNET (Modbus TCP)” is selected with the mode change
switch.
The EC-20x Cosmos PS-7-M is to be set to ST (Static IP address) and ETHERNET as shown in the images
and table above. Further details contained in the PS-7-M Communications Specifications Guide.
Example above is for point 8 (Binary 1000).
Set the address by sliding the eight address setting switches to the “1” or “0” positions. The 8-digit number is
an 8-bit binary number representing the address. The address settable range is 1 (0000 0001) to 254 (1111
1110). Further details contained in the PS-7-M Communications Specifications Guide.

18
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
Chapter 5 – EC20x Modbus/TCP Operation
1. Network access for MODBUS/TCP and Remote viewing on the EC20x is provided through LAN port 2
on the Beckhoff IPC inside the unit as shown below.
2. The default IP Address on port 2 is 192.168.16.212
3. To use the configuration utility and/or change the IP address download and install Tight-VNC. (Tight-
VNC install https://www.tightvnc.com/download.php )
4. Using Tight-VNC connect to the default IP address above with a password of dod675.
5. Once the remote connection is established use these steps to change the IP address.
a. Minimize or close the application.
b. Click on Start->Control Panel
c. Select Network connections

19
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
d. From here you can change the IP shown below as X1 which should have the default IP
address. Do not change the port X2 with IP 192.168.100.55, This is the port used to
communicate to the sensors.
6. Once the IP on port X1 is changed, the connection will be lost, but you should now be able to remote
from the local network.
7. In order to restart the application either :
a. Power cycle the unit or
b. Click on the start menu, and select run and Enter
“\Hard Disk\DOD\EC20\EC20.exe” (With Quotation Marks)
5.1 General Operation – Application Window
1. Remoting to the machine is done using Tight-VNC as shown above.
2. The application window shown below will be used to enable and disable different points, as well as
save the desired configuration for use on startup.
3. One other feature is the get initialization data button. This will retrieve any data from the
electrochemical sensors that is normally only retrieved on startup.

20
DC-ITD-EC20xMAN01_A DODtec.com
REV 12/21/2022 815-788-5200
EC20x Cabinet Operating Manual
4. In order to disable a sensor, Click on the gray disable button on the bottom half of each icon. An
example of disabled sensors is shown below with sensors 1, 3 and 5 being disabled.
5. In order to enable any disabled points, follow the same instructions as above by clicking the bottom
half of a disabled icon that is now green labeled “enable”.
6. Once the desired configuration is created, click the “save configuration” button at the bottom of the
screen.
7. Once this is done, the configuration is ready to be loaded on startup.
8. The final feature of this application is the “Get Initialization Data” button. This button retrieves any
data that is normally only retrieved on boot of the application if that is desired.
Table of contents
Other DOD Technologies Gas Detector manuals
Popular Gas Detector manuals by other brands

BMB Technology
BMB Technology COD18 user guide

Code
Code GS290K installation guide

New Cosmos Electric
New Cosmos Electric KD-12 instruction manual

Riken Keiki
Riken Keiki GD-A80D-AS Series operating manual

Crowcon
Crowcon Xgard Bright Installation, operation and maintenance instructions

LEGRAND
LEGRAND 675 28 quick start guide