DOLD DMP 96 A User manual

DOLD GMBH . Blumenstrasse 33 . 70736 Fellbach . Germany
Phone +49 (0)711/95152-0 . Fax +49 (0)711/95152-19 . info@dold-regler.de . www.dold-regler.de
Operating Instructions DMP 96 A
Single-channel controller Two-point controller
Continuous-action controller
with one limit-value contact
Program versions: 020H0 020H3 020H6
020H1 020H4 020H7
020H2 020H5 020H8
Soll
Ist
32
K2
K1
4
°C
DMP 96 A
P
1
Before connecting the regulator it is essential to read
this Manual and follow it's instructions.
(Subject to technical changes)

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 2
Contents
1. INSTALLING THE CONTROLLER:........................................................................4
1.1 Directions for installation...............................................................................................................4
1.2 Identification plate:.........................................................................................................................5
1.3 Connecting the controller: .............................................................................................................6
1.3.1 Auxiliary power:..........................................................................................................................6
1.3.2 Terminal connection diagram:....................................................................................................6
1.4 Mechanical Data:...........................................................................................................................6
2. TECHNICAL DATA, INPUTS:.................................................................................7
2.1 Analog inputs:................................................................................................................................7
2.1.1 Technical Data, inputs:...............................................................................................................7
2.1.2 Error-handling at input:...............................................................................................................8
2.2 Digital inputs:.................................................................................................................................8
3. CONTROL RESPONSE: ........................................................................................8
3.1 Controller function:........................................................................................................................8
3.1.1 Two-point controller:...................................................................................................................9
3.1.2 Continuous-action controller:......................................................................................................9
3.1.3 Three-point response:................................................................................................................9
3.2 Actuator function: ..........................................................................................................................9
4. OUTPUTS:............................................................................................................10
4.1 Potential-free relay contacts, make contact: ...............................................................................10
4.2 Logic output (optional):................................................................................................................10
4.3 Analog output: .............................................................................................................................10
4.3.1 Technical data, analog output:.................................................................................................10
4.4 Output responses in cases of error:............................................................................................11
5. DISPLAY:..............................................................................................................11
5.1 Upper 7-segment display ............................................................................................................11
5.2 Lower 7-segment display.............................................................................................................12
5.3 LED's:..........................................................................................................................................12
6. EXPLANATIONS OF SYMBOLS:.........................................................................12

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 3
7. OPERATION:........................................................................................................13
7.1 Setting parameters on the various levels:...................................................................................13
7.2 The various levels: ......................................................................................................................14
7.3 Setting the setpoint:.....................................................................................................................14
7.3.1 Setting the setpoint via the operator level: ...............................................................................14
7.3.2 Setting the setpoint level via the setpoint entry level:...............................................................15
7.4 The configuration level:...............................................................................................................15
7.4.1 Switching response of the K 2 limit-value contact:...................................................................19
7.5 The parameterization level:.........................................................................................................19
7.6 The self-optimization level:..........................................................................................................20
7.6.1 Monitoring the optimization process:........................................................................................22
7.7 The information level:..................................................................................................................23
8. LINE COMPENSATION, ZERO-POINT OFFSET:................................................24
8.1 Line compensation:.....................................................................................................................24
8.2 Zero-point offset:.........................................................................................................................24
9. ERROR MESSAGES:...........................................................................................25
9.1 Error messages (display): ...........................................................................................................25
10. PROGRAM VERSION: .......................................................................................25
11. IMMUNITY: .........................................................................................................26

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 4
1. Installing the controller:
1.1 Directions for installation
Important: These directions for the installation of
DOLD devices have to be adhered to:
If these directions are not adhered to the device may not work accurately, be destroyed
or it may result in data being lost.
Read all directions carefully before connecting the device.
Connection to be carried out only by experts.
This device is not a safety device. Safety devices have to be installed according to the relevant
directions for use.
Check if the power-supply voltage corresponds to rated voltage indicated on the identification
plate before connecting and putting the device into operation. Fluctuations in the main voltage
are only admissible within the indicated limits (specifications/identification plate).
The described device is designated for the installation of switchboards.
Electrical connections are to be carried out according to the connecting plan and the directions
of the local electric supply company or the relevant regulations of the VDE respectively.
Other consumers must not be connected to the mains terminals.
In the event of mains interruptions, which lead to a malfunctioning of the device, relevant meas-
ures must be taken to avoid interruptions or interruptions must be filtered out by an external hum
eliminator. The device is equipped with an internal hum eliminator.
On installation the sensor lines have to be shielded. The screen must be single-ended. With re-
gard to thermoelement pick-ups the compensating lead has to be laid as far as the control ter-
minals. The device and inductive consumers as well as sensor lines/signal lines and high ten-
sion lines have to be placed in such a way that any mutual interference is excluded (placed
separately; not parallely laid). go-and-return lines should be laid parallely and, if possible,
twisted.
Non-insulated sensors of a multi-channel control have to be adjusted to the same potential
(max. potential difference: + 3.5 V eff.). Otherwise insulated sensors must be used (Warning:
Ceramics insulations (Al-Oxide) can be conducting >400 °C).
Post-connected contactors have to be equipped with RC protective allocations according to the
manufacturer's instructions. If an internal protective allocation is mentioned in the connection
plan of the device this has to be taken into account in the event of external allocation. If external
allocation is missing short-term voltage peaks may result which lead to faster contact wear and
may cause interference.
The preadjustment of all parameters has to be checked during operation and adjusted to the lo-
cal conditions (installation)! Wrongly adjusted parameters may cause serious malfunctions!
Not all controlled systems can be controlled by parameters measured by means of self-
optimising; therefore, on principle, control response is to be checked for stability.

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 5
The load circuits of the relays have to be protected against excessive currents in order to avoid
the relay contacts becoming welded together.
The device must not be installed in an ex-area.
If used for purposes other than originally intended the device may be damaged and cause dam-
age to connected installations.
The life time of the relays is limited to 106switching cycles at a load of 500 VA. Thus it is to a
high degree dependent on the frequency of switching cycles.
Time per switching cycle Time after which 106switching cycles are reached
(operation: 8 hours/day at a load of 500 VA)
120 s about 11.4 years
60 s about 5.7 years
30 s about 2.8 years
This table is invalid for Solid-State-Relay.
At low loads life time increases with regard to the values indicated in the table.
The device is to be protected against moisture (especially condensing moisture) and excessive
contamination. If this is not assured the device is liable to malfunctions.
Unplug connecting plugs only longitudinally to plug direction. Under no circumstances must the
connecting plugs be plugged in or out obliquely!
Furthermore care must be taken that the surrounding temperature corresponds to the values
shown in the specifications. Sufficient air circulation must be provided.
These operating instructions do not contain all directions to regulations, standards etc. which
become effective when using this device in connection with other installations. These regula-
tions, standards etc. must be ascertained and abided to by the purchaser.
1.2 Identification plate:
The following information is
important and should be given
Type of controller
Factory number
Program version
Model number
DMP 96 A
Operating voltage:
Switching capacity:
Factory number:
Input:
Logic input:
Outputs:
Model No:
ASP 675XXX
XXX V +/-10%
500 VA at 230 V AC
XXXXXX FXXPXXHXX
configurable function
Logic outputs
relay
Program version:
Type of controller
as per order
as per order
as per order
XXXXX
Terminal connection diagram number
whenever you have any technical
questions:
XXXXX
XXXXXXXXXX
Figure 1: DMP 96 A identification plate

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 6
1.3 Connecting the controller:
1.3.1 Auxiliary power:
Auxiliary power (operating voltage) as per identification plate:
Standard: 230 V AC (±10%), 48...62 Hz,
Power consumption, depending on model: ≤6 VA,
Not affected by voltage fluctuations within the defined rangeTerminal connection diagram:
1.3.2 Terminal connection diagram:
This connection diagram shows maximum terminal assignment for the controller when all con-
nection possibilities are used. The appropriate terminal assignment (depending of the type of
controller used) can be found in the accompanying connection diagram.
Connection diagram number according to identification plate: ASP 675XXX
5
12
14
15
13
10
11
9
8
7
6
3
4
2
1
Operating voltage
-
+U/I output
Logic input
thermometer,
Logic outputs (optional)
-
+
-
+
Relay outputs
K 2
K 1
Caution:
Terminal 2 (-) and
terminal 6 (-) do not
have the same
potential!
thermometer, Thermal converter
-
+
3-wire leads
Resistance Resistance
2-wire leads
Figure 2: DMP 96 A connection diagram
1.4 Mechanical Data:
Protection class: VDE 0631
Insulation group: C as per DIN VDE 0110 b
Type of protection: As per DIN VDE 0470 (replaces DIN 40 050)
EN 60 529 / IEC 529
Front panel: IP 50 (optionally: IP 54 with the proper mounting
and a suitable sealing ring)
Housing: IP 30
IP 20

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 7
Housing: Pull-out housing for mounting control panel per DIN 43 700
with a B fastener as per DIN 43 835 (M 4 screw clamp)
Material: PPO, glass-fiber reinforced (Noryl GFN2SE1)
self-extinguishing, non-dripping
fire protection class UL 94 V1
Front panel dimensions: 96 x 96 mm DIN 43 700
Control panel cutout: 92+0.8 x 92+0.8 mm
Recess depth: approx. 92 mm including screwed plug connector
Terminal connections: Screwed socket strips
nominal cross section 2.5 mm2
Weight: approx. 500 g
Ambient conditions: Operating temperature range: 0...+50°C
Storage temperature range: -30...+70°C
Climatic utilization category: as per DIN 40 040,
corresponding to 75% relative humidity
without moisture condensation.
2. Technical data, inputs:
2.1 Analog inputs:
Input as per identification plate or sensor ID:
•Pt 100 three-wire lead
•Fe-CuNi thermal converter, Type L
•Ni Cr-Ni thermal converter, Type K.
Sensor ID:
Sensor: Sensor
ID: ID according to
ordering key: Max. display
range: Max. setpoint
range: Program
version:
Pt 100 P 1 P 1 -69...149°C -50...100°C 020H0
Pt 100 P 2 P 2 -69...249°C -50...200°C 020H1
Pt 100 P 3 P 3 -69...349°C -50...300°C 020H2
Pt 100 P 4 P 4 -69...699°C -50...600°C 020H3
Pt 100 P 5 P 5 -169...149°C -150...100°C 020H4
Fe-CuNi Type L
tL1 L 1 -24...499°C 0...450°C 020H5
Fe-CuNi Type L
tL2 L 2 -24...899°C 0...850°C 020H6
Ni Cr-Ni Type K
tn1 K 1 -24...649°C 0...600°C 020H7
Ni Cr-Ni Type K
tn2 K 2 -24...1299°C 0...1200°C 020H8
(See Information Level, Section 8.7, for instructions on querying sensor ID).
2.1.1 Technical Data, inputs:
Pt 100: Sensor current: constant 1 mA DC
Calibration precision: ≤0,15 % F.S.
Linearity error: ≤0,1% F.S.
Temperature drift characteristics: ≤100 ppm/K
Equipped with sensor breakage cutoff and short circuit fuse

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 8
Pt 100 three-wire lead: Automatic line resistance compensation via software
(maximum permissible line resistance: 50 Ωper lead)
Pt 100 two-wire lead: Line resistance correction (line compensation) of max. 9 Ω
possible via software (external bridge clamps 2-3),
Thermal converter: Calibration precision: ≤0.15% F.S.
Linearity error: ≤0.15% F.S.
Temperature drift characteristics
(without reference point compensation): ≤80 ppm/K
Effect of line resistance: ≤2µV/Ω
Reference point compensation
Error recognition using a controller reference point >70°C
Sensor breakage cutoff
General: Measurement cycle: 1 s
Resolution: ≥12 bit
LRC and diode protection circuit for each input
Measuring-circuit
monitoring: Error shown on display
Protective circuits: Hardware watchdog and power-fail
Data backup: EE-PROM, semiconductor storage,
Hardware-protected calibrated values
2.1.2 Error-handling at input:
If the input signal leaves the maximum display range (for sensor ID) this is recognized as an er-
ror, evaluated, and shown on the display (error message "Er 1"). See section 4.4, page 11.
2.2 Digital inputs:
Logic input via potential-free contact, with configurable function
Contact:
Function: Contact open Contact closed
Setpoint switchover Enter value for setpoint 1 Enter value for setpoint 2
Stop function - Control contact K 1 deactivated
Programming block Programming function block Programming function release
3. Control response:
3.1 Controller function:
Control response is configurable:
•Two-point response for heating or cooling, with adjustable hysteresis
•Two-point response for heating or cooling with PDPID – control characteristic and self-
optimization algorithm

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 9
•Continuous-action control response for heating and cooling with PDPID – control character-
istic and self-optimization algorithm
•Three-point response with adjustable hysteresis
•Three-point response with one-sided PDPID – control characteristic and self-optimization al-
gorithm
3.1.1 Two-point controller:
Relay output K 1: Switching function configurable: Control contact or limit comparator
Relay output K 2: Switching function configurable: Limit-value contact (with adjustable
hysteresis) and limit comparator
Options: Logic output in place of relay output K 1 or K 2,
actual-value output.
3.1.2 Continuous-action controller:
Output 1: Characteristic curve configurable (heating or cooling):
Control output (relay output K 1 eliminated)
Relay output K 2: Switching function configurable: Limit-value contact (with adjustable
hysteresis) or limit comparator
Option: Logic output in place of relay output K 2
3.1.3 Three-point response:
Three-point response is configurable:
Relay output K 1 heating, relay output K 2 cooling,
Relay output K 1 cooling, relay output K 2 heating,
Options: Logic output in place of relay output K 1 or K 2,
actual-value output.
3.2 Actuator function:
Reconfiguration of the "Aut" parameter makes it possible to use the unit as an actuator (actuator
mode: parameter "Aut" set to OFF on the configuration level)
The
key can be used to switch smoothly back and forth between the control
ler
functions (automatic function) and the actuator (manual function).
The manipulated variable (%) set on the operator or setpoint entry level is relative to the cycle
time (with relay output) or to output deviation (with continuous-action output).
The currently activated function is stored in the EE-PROM. When the unit is powered up it is in
the state of the function last stored.
Display:

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 10
Display:
Function: Upper 7-segment display Lower 7-segment display
Controller current actual value setpoint
Actuator current actual value alternation between
" -y- " / manipulated variable
4. Outputs:
Outputs as per identification plate and accompanying terminal connection diagram:
4.1 Potential-free relay contacts, make contact:
Contact load: ≤250 V AC, ≤8 A resistive load
at 500 VA typically 106switching cycles
4.2 Logic output (optional):
Logic outputs for activating solid-state relays,
(in place of relay outputs K 1 or K 2):
Open collector, not galvanically separated, short-circuit-proof,
typically: 0/10 V DC, maximum: 20 mA.
4.3 Analog output:
Analog output as per order and identification plate
Two-point controller: actual-value output (optional): range limits configurable
Continuous-
action controller: Control output: characteristic curve (heating or cooling) configurable
Current output: output value configurable: 0...20 mA
4...20 mA
Voltage output: output value as per order: 0...1 V DC
0...2 V DC
0...5 V DC
4.3.1 Technical data, analog output:
Current and voltage output: resolution: 8 Bit
Current output: load: ≤250 Ω
Voltage output (short-circuit-proof): internal resistance Ri: ≤250 Ω
Note: Any current output present but not needed must have a terminating resistor of ≤250 Ω
or a bridge (terminals 5-6).

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 11
4.4 Output responses in cases of error:
Output response in cases of sensor error:
•Relay or logic outputs: Outputs assume the state defined on the configuration
level.
•Analog output: (continuous-action controller, actual-value output):
output U: 0...1 V DC, 0...2 V DC, 0...5 V DC: output signal: 0 V DC
output I: 0...20 mA output signal: 0 mA
output I: 4...20 mA output signal: 0 mA
Incorrect actual-value response due to sensor error or response exceeding the set range:
Actual value X
Set analog range
Beginning of range "AnL" End of range "AnH"
Error message "Er.1" Error message "Er.1"
c) 0...5 VDC
d) 0...20 mA
e) 4...20 mA
a) 1 VDC
d) 20 mA
e) 20 mA
b) 0 VDC
d) 0 mA
e) 0 mA
a) 0 VDC
d) 0 mA
e) 0 mA
a) 0 VDC
d) 0 mA
e) 4 mA
(X < display range) (X > display range)
b) 2 VDC a) 0 VDC
b) 0...2 VDC
b) 0 VDCb) 0 VDC a) 0...1 VDC
c) 5 VDC c) 0 VDCc) 0 VDCc) 0 VDC
Max. display range
Figure 3: Actual-value response in cases of error
5. Display:
•Actual-value and setpoint display: resolution adjustable
•Setpoint display: display range adjustable.
General information:
Powering up:
When power is turned on the following displays appear:
•On the upper 7-segment display: the parameter "P.nr".
•On the lower 7-segment display: the current program number "X.X".
After approx. 5 s the controller switches to normal operating mode.
Outputs are inactive during a cold start.
5.1 Upper 7-segment display
shows:
•the actual value
•parameter designation in entry mode

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 12
5.2 Lower 7-segment display
shows:
•setpoint
•parameter value in entry mode
•alternation between " -y- " / manipulated variable when actuator function is activated (man-
ual function)
•alternation between setpoint (auxiliary setpoint) / "Opt" during the self-optimization proce-
dure.
5.3 LED's:
LED: K 1 yellow lights up when output K 1 is active
LED: K 2 yellow lights up when output K 2 is active
LED: 1 green lights up when continuous-action controller is functioning
LED: 2 green lights up when logic input is activated (contact closed)
6. Explanations of symbols:
Display: Meaning:
"P.nr" Current program number
"SP.1" Setpoint 1
"SP.2" Setpoint 2
" -y- " Manipulated actuator value
"Cod" Code entry
"Con" Enter configuration level
"Cor" Line compensation or zero-point offset
"rA.H" Set upper limit of setpoint range
"rA.L" Set lower limit of setpoint range
"Co.1" Configuration, relay contact K 1
"Co.2" Configuration, relay contact K 2
"Fd.1" fault on control output K 1
"Fd.2" fault on control output K 2
"rES" Display resolution
"Aut" Configuration of automatic function
"Co.u" Configuration of setpoint setting
"Co.A" Configuration of analog input
"An.H" Setting of upper measuring range limit for actual-value output
"An.L" Setting of lower measuring range limit for actual-value output
"Co.L" Configuration of logic input
"3-P" Configuration of three-point response
"uSr" Enter setpoint entry level
"PAr" Enter parameterization level
"Pb.1" Proportional band, control contact K 1
"ti.1" Reset time, control contact K 1
"td.1" Derivative action time, control contact K 1
"CY.1" Cycle time, control contact K 1
"HY.1" Switching hysteresis, control contact K 1
"bd.1" Symmetrical. spreading, limit comparator K 1
"LA.2" Absolute setpoint value, limit-value contact K 2
"Lr.2" Relative setpoint value, limit-value contact K 2
"bd.2" Symmetrical. spreading, limit comparator K 2
"HY.2" Switching hysteresis, limit-value contact K 2

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 13
Display: Meaning:
"noP" Relay contact K 2 deactivated
"tun" Enter self-optimization level
"HLP" Correcting setpoint
"OPt" Self-optimization activated
"inF" Enter information level
"SEn" Sensor ID
"Er.1" Sensor error message
"Er.9" System error message
7. Operation:
The operating structure of the DMP 96 A controller includes six separate levels:
Setting the setpoint (depending on configuration):
•via the operator level.
•via the setpoint entry level (by entering a code).
•the configuration level, where line compensation, range limits, control functions, switching
functions of the limit-value contact, and error allocations are defined.
•the parameterization level, which contains all parameters for adjusting the controller to the
control loop.
•the self-optimization level for setting the correcting setpoint and for starting or aborting
self-optimization.
•the information level for querying current program number and sensor ID.
7.1 Setting parameters on the various levels:
current value: +1
after approx. 3 s: +10
after approx. 6 s: +100
current value: -1
after approx. 3 s: -10
after approx. 6 s: -100
P
display value is accepted
The program returns to normal operating mode after the last parameter has been confirmed.
If no key is pressed within 20 seconds, the program automatically returns to normal operating
mode without accepting any value that has been changed.
After confirming an incorrect code number: Do not press any key for approx. 20 seconds.
Wait for program to return to normal operating
mode.
Enter new code.

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 14
7.2 The various levels:
Press briefly Operator level (only when function is released)
Code
100
Press for 3 s Information level
P
P
P
(setpoint setting)
Self-optimization level
111
Code
77
Code Setpoint entry level (only when function is released)
Code
55 Parameter level
P
P
P
(setting of control parameters)
(starting and aborting of self-optimization)
(setpoint set by entering code)
(querying of current program number, sensor)
Code
155 Configuration level
P
(configuration of range limits,
control functions, etc.)
(only when function is released)
Figure 4: The various levels
7.3 Setting the setpoint:
How the setpoint is set depends on configuration (parameter ”Co.u” on the configuration level).
The setpoint can be set on the:
•operator level (factory configuration)
•setpoint entry level (setting made by entering a code number).
7.3.1 Setting the setpoint via the operator level:
PPress key briefly to jump to the operator level
Display: Parameter: Range: Factory
setting:
"SP.1" Setpoint 1 "rA.L...rA.H"
0.0°C

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 15
Display: Parameter: Range: Factory
setting:
"SP.2" Setpoint 2
(appears only for configuration "Co.L" = 01) "rA.L...rA.H"
0.0°C
" y " Setpoint manipulated variable
(appears only for configuration "Aut" = OFF) 0.0...100% 0.0%
PDisplay value is accepted
When configuring parameter ”Co.u” = on (setting setpoint via setpoint entry level) it is not possi-
ble to jump to the operator level.
7.3.2 Setting the setpoint level via the setpoint entry level:
PPress for approx. 3 s to get display: " Cod "
100
Enter code: 77
PConfirm code: Display: " uSr "
PJump to setpoint entry level.
Display: Parameter: Range: Factory
setting:
"SP.1" Setpoint 1 "rA.L...rA.H"
0.0°C
"SP.2" Setpoint 2
(appears only for configuration "Co.L" = 01) "rA.L...rA.H"
0.0°C
" y " Setpoint manipulated variable
(appears only for configuration "Aut" = OFF) 0.0...100% 0.0%
PDisplayed value is accepted
When configuring parameter ”Co.u” = OFF (setting setpoint via operator level) it is not possible
to jump to the setpoint entry level.
7.4 The configuration level:
PPress for approx. 3 s to get display: " Cod "
100

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 16
Enter code: 155
PConfirm code: Display: " Con "
PJump to configuration level.
Display: Parameter: Range: Factory
setting:
"Cor" Line compensation and zero-point offset -25...25.0°C
0.0°C
"rA.H" Set upper limit of setpoint range
(end of setpoint range) max. set-
point range
by sensor ID
(Section 2.1)
max. set-
point range
by sensor ID
(Section 2.1)
"rA.L" Set lower limit of setpoint range
(beginning of setpoint range)
Note: With configuration "rA.H" = "rA.L" it is
not possible to set the setpoint on the
operator level.
With configuration "rA.H" <"rA.L"
the keys or can be used
to switch back and forth between the
set values
max. set-
point range
by sensor ID
(Section 2.1)
0.0°C
"Co.1" Configuration of control output or limit com-
parator K 1
Two-point controller / three-point response:
01: Cooling controller with hysteresis
setting towards plus
02: Cooling controller with PID feedback
03: Limit comparator closed in goodband
(hysteresis fix at 0.5 K)
04: Heating controller with adjustable
hysteresis towards minus
05: Heating controller with PID feedback
06: Limit comparator open in goodband
(hysteresis fix at 0.5 K)
Continuous-action controller:
(parameter "Co.A" = 03 or 04,
relay contact K 1 deactivated).
02: rising characteristic with PID "cool-
ing" feedback
05: falling characteristic with PID "heat-
ing" feedback
01...06 05

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 17
Display: Parameter: Range: Factory
setting:
"Co.2" Configuration of limit-value contact K 2
00: Relay deactivated (no function)
01: Absolute limit value of make contact
relative to rising temperature
02: Limit value travels with setpoint,
make contact relative to rising temp.
03: Limit comparator closed in goodband
(hysteresis fix at 0.5 K)
04: Absolute limit value, break contact
referenced to rising temperature
05: Limit value travels with setpoint,
break contact relative to rising temp.
06: Limit comparator open in goodband
(hysteresis fix at 0.5 K)
00...06 00
"Fd.1"
"Fd.2"
Error allocation, outputs K 1; K 2
Output K 1
Output K 2
on: Output active in the event of error
OFF: Output inactive in the event of error
on...OFF
OFF
OFF
"rES" Display resolution
00: resolution 0.1K
01: resolution 1K
00...01 00
"Aut" Automatic function
on: Automatic function mode activated
(controller)
OFF: Automatic function mode deactivated
(actuator).
The key can be used to switch
from automatic function mode (con-
troller) to manual function mode (ac-
tuator).
on...OFF on
"Co.u" Setting of setpoint via setpoint entry level
on: Setting of setpoint via setpoint entry
level activated
OFF: Setting of setpoint via setpoint entry
level deactivated (setpoint set via
operator level).
on...OFF OFF
"Co.A" Analog output:
Analog output of actual value (optional):
00: Analog output deactivated
01: Voltage/current output: 0...1 V DC,
0...2 V DC, 0...5 V DC or 0...20 mA
02: Current output: 4...20 mA
Continuous-action controller:
(parameter "Co.A" = 03 or 04),
configure the desired control function (pa-
rameter "Co.1" = 02 or 05), (relay contact K 1
is deactivated):
03: Voltage/current output: 0...1 V DC,
0...2 V DC, 0...5 V DC or 0...20 mA
04: Current output: 4...20 mA
00...04 00

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 18
Display: Parameter: Range: Factory
setting:
"An.H" Analog output of actual value
High-end value of measuring range limit max. display
range de-
pendent on
sensor ID
(Section 2.1)
end of set-
point range
dependent
on sensor ID
(Section 2.1)
"An.L" Analog output of actual value
Low-end value of measuring range limit max. display
range de-
pendent on
sensor ID
(Section 2.1)
0.0°C
"Co.L" Configuration of logic input
00: Logic input deactivated
01: Changing setpoint selection
contact open: setpoint 1
contact closed: setpoint 2
02: Stop function
(not in effect with continuous-action
control output!)
Contact closed:
control contact K 1 deactivated and
setpoint display goes dark
(lower display)
03: Programming block
Contact closed:
programming function released
Contact open:
programming function blocked
(jump to configuration, para- me-
terization, setpoint entry and self- opti-
mization levels blocked).
00...03 00
"3-P" Three-point response
on: Three-point response activated
OFF: Three-point response deactivated
Configuring three-point response
e.g.: heating K 1: "Co.1" = 04 or 05,
cooling K 2: "Co.2" = 02
cooling K 1: "Co.1" = 01 or 02,
heating K 2: "Co.2" = 05
spreading (parameter ”Lr.2”) toward
plus or setting towards minus.
on...OFF OFF
Important: After any change of configuration or reconfiguration of outputs K 1 and
K 2 (parameters "Co.1" and "Co.2") the corresponding parameters on
the parameterization must be set and adapted to the directly controlled
member.
After any change of configuration or reconfiguration of the setpoint ran-
ge (parameters "rA.H" and "rA.L") the setpoint settings on the operator
level, and the setpoint entry level must be checked and adapted to the
setpoint range.

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 19
7.4.1 Switching response of the K 2 limit-value contact:
Switching function relative to rising actual value
Absolute limit value
b) Hysteresis "HY.2"
Setpoint value "LA.2"
a) Make contact (01)
b) Break contact (04)
Actual value X
a) Hysteresis "HY.2"
Limit value changing with setpoint value
b) Hysteresis fix "HY.2"
Spreading ("SP.X" + "Lr.2")
a) Make contact (02)
b) Break contact (05)
Actual value X
a) Hysteresis fix "HY.2"
Setpoint value "SP.X"
Limit comparator closed in commodity load area
Setpoint value "SP.X"
Coding (03)
actual value X
Hysteresis 0.5 K
Symmetrical spreading "bd.2"
Symmetrical spreading "bd.2"
Hysteresis 0.5 K
Limit comparator closed in commodity load area
Setpount value "SP.X"
Actual value X
Hysteresis 0.5 K
Symmetrical spreading "bd.2"
Symmetrical Spreading "bd.2"
Hysteresis 0.5 K
Coding
(06)
Figure 5: Switching response of the K 2 limit-value contact
7.5 The parameterization level:
Setting control parameters:
PPress for approx. 3 s to get display: " Cod "
100
Enter code: 55
PConfirm code: Display: " PAr "

DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006 20
PJump to parameterization level.
Depending on the configuration of the outputs (configuration level) only those parameters are
accessible which are needed for the specific function.
Display: Parameter: Range: Factory
setting:
"Pb.1" Proportional band, control contact K 1
(Pb = 0.1...200% relative to setpoint ran
ge
according to sensor ID, Section 2.1)
0.1...200%
"Co.1" = 02, 05 5.0%
"ti.1 " Reset time, control output K 1
(adjustment zero = time 0) 0...999 s
"Co.1" = 02, 05 250 s
"td.1" Derivative action time, control output K 1
(adjustment zero = time 0) 0...500 s
"Co.1" = 02, 05 50 s
"CY.1" Cycle time, control output K 1 1...200 s
"Co.1" = 02, 05 30 s
"HY.1" Hysteresis, control output K 1 0.1...5% of set-
point range limit
dependent on
sensor ID
"Co.1" = 01, 04
1.0 K
"bd.1" Symmetrical spreading, limit comparator
K 1 (hysteresis fix at 0.5 K) 0.1...99.9 K
"Co.1" = 03, 06 5.0 K
"LA.2" Absolute setpoint, limit-value contact K 2 max. display ran-
ge dependent on
sensor ID
"Co.2" = 01, 04
0.0 °C
"Lr.2" Spreading, limit-value contact K 2 travel-
ing with setpoint -99...99.9 K
"Co.2" = 02, 05 0.0 K
"bd.2" Symmetrical spreading, limit comparator
K 2 (hysteresis fix at 0.5 K) 0.1...99.9 K
"Co.2" = 03, 06 5.0 K
"HY.2" Hysteresis, limit contact K 2 0.1...20% of set-
point range limit
dependent on
sensor ID
"Co.2" = 01, 02,
04, 05
1.0 K
7.6 The self-optimization level:
The DMP 96 A controller is equipped with an optimization routine for the automatic adaptation of
the controller to the controlled system.
The optimization algorithm is based on modified Ziegler-Nicols rules, according to which the cha-
racteristic data of the system are calculated after an oscillation test in a closed-loop control cir-
cuit.
These characteristic data (particularly period and amplitude of oscillation) form the basis for cal-
culating specific parameters.
Depending on the control function (heating controller or cooling controller), parameters are calcu-
lated for either the heating or the cooling side.
Table of contents
Other DOLD Controllers manuals

DOLD
DOLD Safemaster Pro User manual

DOLD
DOLD SAFEMASTER BH 5902/01MF2 User manual

DOLD
DOLD MINISTART BL 9028 User manual

DOLD
DOLD Safemaster Pro User manual

DOLD
DOLD SAFEMASTER BG 5925/900 Operating instructions

DOLD
DOLD SAFEMASTER BH 5902/01MF2 Operating instructions

DOLD
DOLD MINISTART GF 9016 User manual

DOLD
DOLD MINISTART BL 9228 User manual
Popular Controllers manuals by other brands

Wet Sounds
Wet Sounds WWX-RGB-RS owner's manual

PIETRO FIORENTINI
PIETRO FIORENTINI APERFLUX 101 Technical manual

Kisi
Kisi Controller Pro 1.1 Handbook

Aprilaire
Aprilaire 8910 Specifications

Digitus
Digitus dbSentry Hardware installation manual

Field Controls
Field Controls 960524 Installation instructions addendum