Dontek AQUATEK User manual

AQUATEK
Instruction
Manual
dontekÿ
ELECTRONIC
MANUFACTURING
DESCRIPTION
The
AQUATEK
Controller
manages
your
pool
spa
and
heating
reguirements
from
your
smart
phone
via
the
home
WIFI.
It
will
control
single
and
many
multi
speed
pumps,
sanitiser,
heater,
solar
heating,
lights,
water
features,
pool/spa
valve
actuators
and
all
spa
eguipment
reguirements.
The
AQUATEK
Control
system
is
modular
and
can
accommodate
most
pool
control
reguirements
big
or
small.
AQUATEK
User
Manual
VI.
2
[002].docx
1

INSTALLATION
INSTRUCTIONS
A
THIS
APPLIANCE
IS
NOT
INTENDED
FOR
USE
BY
YOUNG
CHILDREN
OR
INFIRM
PERSONS
WITHOUT
SUPERVISION.
PLEASE
ENSURE
THAT
YOUNG
CHILDREN
ARE
SUPERVISED
TO
ENSURE
THEY
DO
NOT
PLAY
WITH
THE
APPLIANCE.
Ideally
,
as
with
all
pool
equipment
,
the
controller
should
be
installed
out
of
direct
weather.
CONTROLLER
MOUNTING
Find
a
suitable
location
to
mount
the
control
box.
The
controller
should
be
no
closer
than
3
metres
from
the
water's
edge,
at
a
minimum
BOOmm
above
ground
level.
The
power
cable
is
1.8m
long
and
should
be
plugged
directly
into
a
general
power
outlet,
not
into
an
extension
lead.
Fix
the
mounting
bracket
to
a
solid
structure
with
the
screw
and
wall
plug
kit
provided.
Slide
the
controller
on,
locking
it
into
place.
Adjust
the
screws
on
the
back
of
unit
to
ensure
a
snug
fit.
To
remove
unit,
lift
and
gently
pull
away
from
mounting
bracket.
Mount
the
pump
and
Sanitiser
according
to
the
manufacturer's
instructions.
POWER
OUTPUT
CONNECTIONS
The
240VAC
Output
Sockets
are
for
eguipment
to
be
controlled
via
the
AQUATEK
controller.
Each
socket
can
be
assigned
via
the
menu
and/or
app.
The
maximum
combined
load
for
both
sockets
on
the
master
controller,
is
9.9
AMPS
at
2370W.
HEATER
CONTROL
Set
the
heaters
temperature
limit
to
maximum
[40°C],
The
heaters
internal
control
will
be
interrupted,
to
turn
off
heating.
The
heater
interlock
cable
connects
to
the
green
socket
marked
INT
which
switches
on
[closes]
the
voltage
free
ND/C
relay
contacts
when
the
heater
is
to
be
turned
on.
The
heater
end
of
the
interlock
cable
connects
in
series
with
the
heater's
pressure/flow
or
fireman's
switch.
Contact
the
heater
manufacturer
for
the
best
location
to
connect
to.
The
heater
interlock
is
for
extra
low-voltage
[MAX
24V
at
lAmp]
switching
only.
Note:
If
the
heater's
flow
or
pressure
switch
circuit
is
2dOVac,
an
external
relay
[KITIO]
which
can
be
purchased
separately
,
is
to
be
connected
by
a
licensed
electrician.
If
the
heat
pump/gas
heater
is
equipped
with
a
"Demand
Heat"
function,
the
heater
interlock
cable
will
be
connected
into
the
socket
labelled
as
"Pump
Call".
The
controller
will
over-ride
the
filter
pump
when
flow
is
called
for
by
the
heat
pump
which
monitors
the
temperature
within
its
own
defined
run
times.
Connect
the
heater
cable
from
the
controller
output
to
the
heater's
connection
point.
Check
with
heater
manufacturer
for
correct
interlocking
procedure.
Note:
If
the
heater's
flow
or
pressure
switch
circuit
is
2dOVac,
an
external
relay
[KITH]
which
can
be
purchased
separately
,
is
to
be
connected
by
a
licensed
electrician.
VALVES
The
AQUATEK
has
4
valve
actuator
sockets
for
the
controlling
of
solar
heating,
water
features,
pool/spa
water
flow,
and
In
Floor
cleaning.
Note:
If
wiring
your
own
supplied
valve,
ensure
the
wires
are
as
follows:
[from
left
to
right]
White,
Red
then
Black.
The
red
and
white
are
for
direction
control
and
black
is
the
common.
Ensure
the
switch
on
the
valve
actuator
is
switched
to
an
ON
position.
Refer
the
valve
instructions
for
mounting
requirements,
cam
adjustments
etc.
Maximum
power
for
the
VALVE
output
is
24VA.
AQUATEK
User
Manual
VI.
2
[002].docx
2

SENSORS
POOL
SENSOR
The
pool
sensor
[Part
No.
TS02P]
must
be
fitted
into
the
heating
circuit,
upstream
of
the
heater
and
preferably
in
a
position
out
of
direct
sunlight.
It
is
recommended
that
a
lA.5mm
hole
be
drilled
in
the
side
of
the
PVC
pipe
[not
the
top
of
the
pipe
where
water
will
collect],
this
can
be
carried
out
using
a
Dontek
PD01
grinding
drill
or
a
small
pilot
hole
can
be
drilled
with
a
lA.Omm
drill-bit
used
spinning
in
a
counter
clockwise
direction
to
minimize
the
chance
of
shattering
pipe.
Insert
the
grommet
into
the
pipe
and
gently
push
in
the
sensor
barb.
Ideally
~30cm
of
the
cable
from
the
sensor
should
be
tied
to
the
shaded
side
of
the
pipe
to
prevent
extreme
ambient
conditions
leeching
into
the
sensor
via
the
copper
in
the
cable.
The
blue
sensor
plug
is
to
be
fitted
to
either
Sensor
1
or
2
port
located
beneath
the
controller.
ROOF
SENSOR
If
a
roof
sensor
[Part
No.
TS01P,
purchased
separately]
is
installed,
it
must
be
fitted
into
a
small
piece
of
collector
material
away
from
the
main
collector
but
on
the
same
aspect,
preferably
no
more
than
50cm
from
the
roof
gutter
[for
ease
of
sensor
replacement].
If
reguired,
the
roof
sensor
can
be
on
a
different
roof
as
the
solar
collector
as
long
as
the
alignment
to
the
sun
is
similarto
the
solar
collector.
For
encapsulated
collector
panels
use
the
manufacturer's
instructions
for
roof
sensor
placement.
The
red
sensor
plug
is
to
be
fitted
to
either
Sensor
1
or
2
port
located
beneath
the
controller.
SENSOR
NOTES:
All
excess
cable
must
be
removed;
coils
of
cable
are
not
permitted
under
any
circumstances
and
must
not
be
tied
to
2A0V
wiring.
If
the
cable
is
to
be
extended
with
non-genuine
cable
a
size
of
1A/020
should
be
used.
Note:
Any
cable
joins
should
be
soldered.
Heat
shrink
is
to
be
used
over
soldered
joints
to
eliminate
moisture
ingress.
EXPANSION
UNITS
The
AQUATEK
has
the
capacity
to
have
an
additional
2
expansion
units
connected
to
it.
Each
Expansion
Unit
has
an
additional
3,
240VAC
Output
sockets
that
are
controlled
via
the
AQUATEK
controller.
Up
to
an
additional
6
power
sockets
can
be
utilised
and
controlled
by
the
AQUATEK
master
controller.
The
Expansion
Units
are
rated
at
either
lOAmps
or
15Amps.
All
3
sockets
of
the
Expansion
Unit
are
rated
the
same.
3
sockets
at
lOAmps
or
3
sockets
at
15Amps.
EXPANSION
UNIT
Ideally,
as
with
all
pool
equipment,
the
Expansion
Unit/s
should
be
installed
out
of
direct
weather.
Find
a
suitable
location
to
mount
the
Expansion
Unit/s,
no
closer
than
3
metres
from
the
water's
edge,
at
a
minimum
600mm
above
ground.
MOUNTING
The
power
cable
is
1.8m
long
and
should
be
plugged
directly
into
a
general
power
outlet,
not
into
an
extension
lead.
Mount
as
per
main
controller.
The
240VAC
Output
Sockets
are
for
eguipment
to
be
controlled
via
the
AQUATEK.
Each
socket
can
be
assigned
via
the
menu
and/or
app.
The
maximum
combined
load
for
all
three
sockets
of
the
module
is
either,
9.9
Amps
/
2370
Watts,
or,
1A.9
Amps
/
3570
Watts.
Please
refer
to
the
unit's
rating
label.
The
15Amp
rated
expansion
unit
must
be
plugged
into
a
15Amp
rated
GPO.
AQUATEK
User
Manual
VI.
2
[002].docx
3

INSTALLATION
DIAGRAMS
The
AQUATEK'S
Master
Controller
and
an
Expansion
Unit.
MASTER
CONTROLLER
For
wiring
of
a
multi
speed
pump,
EXPANSION
UNIT/S
10
&
15AMP
f
!
?
|
EXP.
IN
1
3
2
r]
EXP.
OUT
|
If
Expansion
Unit
1,
the
connection
cable
from
the
master
controller
will
plug
in
here.
If
Expansion
Unit
2,
the
connection
cable
runs
from
here
to
Expansion
unit
1
EXP
OUT.
If
Expansion
Unit
1,
the
connection
cable
to
Expansion
Unit
2
EXP
IN
will
plug
in
here.
It
will
be
unused
if
there
is
no
Expansion
Unit
2.
If
Expansion
unit
2
connection
port
is
unused.
A
AQUATEK
User
Manual
VI.
2
[002].docx

Waterco Limited
Connection to Waterco ECO-V variable speed pumps
Waterco ECO-V variable speed pumps may be controlled via the Aquatek speed control function by inserting the
control cable wires into the PUMP CONTROL terminal block.
Colour order from left to right is yellow, black, white, green, red. When setting up via the app select RELTECH as
the pump type.

–
––
-–
–––
5
PIN
PUMP
CONNECTION
PLUG
THERALUX
RELTECH
-
SPECK
-
HENDEN
THERALUX
485
HAYWARD
485
PENTAIR
VS/F
-
RELTECH
485
P
-
OASIS
V
SERIES
-
PENTAIR
ENVIROMAX
1500
-THERALUX
-
RELTECH
-
SPECK
-
HENDEN
Yellow
Wire
Green
Wire
Brown
Wire
Red
Wire
Black
Wire
-
THERALUX
485
-
HAYWARD
485
Black
Wire
Yellow
Wire
Green
Wire
Red
Wire
Brown
Wire
-
PENTAIR
VS/F
None
Green
Wire
Yellow
Wire
None
None
-
DAB
None
Brown
Wire
Black
Wire
None
Red
Wire
-
INSNRG
[SUPPLIED
BY
INSNRG]
None
White/Orange
Stripe
Wire
Orange
Wire
None
None
-
INSNRG
[CAT5
CABLE]
None
Brown/Brown
Stripe
Wire
Brown
Wire
None
None
-
RELTECH
485
P
-
SUNLOVER
OASIS
V
SERIES
Green
Wire
Brown
Wire
Black
Wire
Yellow
Wire
Red
Wire
-
PENTAIR
ENVIROMAX
1500
Brown
Wire
Orange
Wire
Yellow
Wire
Green
Wire
Red
Wire
AQUATEK
User
Manual
VI.
2
[002].docx
5

PUMP
PRIMING
&
CONNECTION
Reltech
P
[485]
/
Oasis
V
Series
Turning
Off
Priming
a]
Quickly
press
the
'stop'
button
three
times.
b]
The
display
will
show
'P
Of
when
priming
is
turned
off.
Turning
On
485
Communication
a]
Hold
the
'stop'
button
for
10
secs.
b]
The
display
will
show
e.g.
'P
5'
[to
select
priming
time
in
minutes].
Press
'set'
button
to
move
to
next.
c]
The
display
will
show
e.g.
'2400'
[to
select
priming
speed
in
RPM],
Press
'set'
button
to
move
to
next.
d]
The
display
will
show
'Rb
Of.
Press
Up
or
Down
button
to
change
to
'Rb
On'.
Press
'set'
button
to
confirm.
e]
When
communication
with
Aquatek
is
successful,
the
display
will
show
'
----
'.
Pentair
enviroMAX
1500
Turning
Off
Priming
a]
Press
the
'Start
/
Stop'
button
to
start
the
pump.
b]
The
display
will
alternate
between
'Pri'
and
'2800'
and
'04:59'
to
show
priming
at
2800
RPM
for
5mins.
c]
Press
the
'-'
to
turn
the
priming
speed
down;
when
it
reaches
below
1700,
priming
is
turned
off.
d]
The
display
will
then
alternate
between
'Pri'
and
'Off'.
Note:
External
control
must
be
off.
Turning
On
External
Control
a]
Stop
the
pump
by
pressing
the
'Start
/
Stop'
button.
b]
Hold
the
'Start
/
Stop'
button
for
~5
seconds.
c]
The
light
next
to
'Ext.
Control
Only'
will
be
lighted
green.
d]
Press
the
'Start
/
Stop'
button.
e]
The
light
next
to
'Start
/
Stop'
will
be
lighted
green.
Pentair
VS/F
Turning
Off
Priming
a]
Disconnect
the
RS-485
communication
cable
from
the
pump.
b]
On
the
pump
control
module,
press
Menu
and
use
the
Arrow
buttons
to
scroll
and
select
"Priming".
c]
Use
the
Arrow
buttons
to
select
"Disabled",
then
press
the
Back
button
to
exit
the
menu.
d]
Re-install
the
communication
cable
to
the
pump.
Turning
On
External
Control
a]
Press
the
Menu
button,
use
the
Up
or
Down
arrow
to
scroll
to
Ext
Ctrl
and
press
Select.
b]
"Program
1"
will
be
displayed
and
press
Select
to
enter.
c]
"Operation
Mode"
will
be
displayed,
press
Select
and
use
the
Up
or
Down
buttons
to
choose
between
"Enabled"
or
"Pump
Off",
press
Save.
Note:
the
program
must
be
enabled
to
proceed
further
into
the
menu.
d]
Use
the
Up
or
Down
arrow
to
scroll
to
"Set
Type"
and
press
Select.
e]
Use
the
Up
or
Down
arrow
to
choose
between
"Speed"
or
"Flow"
settings
and
press
Save.
f]
Use
the
Up
or
Down
arrow
to
scroll
to
"Set
Speed/Flow"
[depending
on
what
was
chosen
in
the
previous
step],
press
Select
and
then
use
the
Up
&
Down
arrows
to
adjust
the
speed/flow
settings
to
what
is
required
&
press
Save.
g]
There
is
no
need
to
set
a
"Stop
Delay"
so
press
the
Save
button
to
save
your
settings
and
then
press
Back.
This
will
allow
you
to
set
"Program
2".
h]
Use
the
Up
or
Down
arrow
to
scroll
to
"Program
2"
and
repeat
steps
b]
to
g]
for
programs
2
to
4.
AQUATEK
User
Manual
VI.
2
[00E].docx
B

Hayward
/
Theralux
Note:
Theralux
pump
will
be
supplied
with
485
communication
already
enabled.
If
it
isn't,
follow
the
steps
below.
Turning
Off
Priming
a]
Priming
is
automatically
taken
off
when
the
below
connection
process
[4.2]
is
done.
Turning
On
485
Communication
a]
Hold
stop,
press
speed
2
to
show
"LOW".
b]
Press
speed
1
until
the
screen
shows
"10".
c]
Press
speed
2
to
show
"485".
d]
Press
stop
to
save
settings.
Once
there
is
control
over
the
pump,
the
pump
will
show
"NBUS".
Insnrg
1100
Turning
Off
Priming
a]
Press
Enter,
scroll
to
Priming.
b]
Set
Minutes
to
0.
Turning
On
External
Control
a]
Connect
the
pump
control
cable
between
the
pump
and
the
Aquatek
controller
and
control
is
automatically
instated.
Reltech/Theralux/Speck/Henden
[with
Fasco
Motor]
Turning
Off
Priming
a]
Disconnect
the
pump
communication
cable
from
the
pump.
b]
Press
and
hold
the
Stop
button
for
10
seconds
to
remove
the
priming
function.
c]
If
required,
adjust
pump
speeds
[as
per
manufacturer's
instructions]
to
suit
then
save
prior
to
reconnecting
the
communication
cable.
a]
DAB
E.Swim
Turning
Off
Priming
a]
Scroll
to
select
the
Settings
Wheel
[®]Press
Enter.
b]
Scroll
to
Priming
and
press
Enter.
c]
Change
Enable
to
NO.
Turning
On
External
Control
b]
Scroll
to
select
the
Settings
Wheel
[®],
Press
Enter.
c]
Scroll
to
External
Control
and
press
Enter.
d]
Scroll
to
Settings
and
press
Enter.
e]
Change
config
to
ENABLE.
f]
Change
source
speed
to
4-20mA.
AQUATEK
User
Manual
VI.
2
[002].docx
7

OPERATING
INSTRUCTIONS
LCD
SCREEN
In
Automatic
[Pool]
mode
the
LCD
screen
displays;
the
time
of
day,
what
time
the
current
filtration
cycle
will
finish/start
at,
if
more
than
one
filtration
cycle
is
set,
then
the
start
time
of
the
next
filtration
cycle
is
displayed,
current
pool
and
roof
temperatures
or
any
faults
are
displayed,
current
status
of
the
pump
[run/inactive],
Heat
Demand
time
[if
active],
and
whether
the
WIFI
is
active
or
disabled.
In
Spa
mode
the
LCD
screen
will
display;
the
time
of
day,
SPA
MODE
on,
pool
temperature
or
sensor
fault,
Temperature
-
both
current
temperature
and
set
temperature
of
the
spa,
pump
status,
and
WIFI
status.
LCD
INDICATORS
There
are
arrow
icons
on
the
LCD
screen
that
point
to
text
on
the
label.
CONTROLLER
BUTTONS
AUTO
Pressing
the
AUTO
button
will
run
the
controller
in
automatic
pool
mode.
If
the
AUTO
button
is
pressed
while
in
the
settings
menu,
the
changed
settings
will
be
used
but
not
saved.
If
there
is
a
power
failure
the
controller
will
retrieve
the
previously
saved
settings.
On
power-up
the
controller
will
start
automatic
pool
operation.
BACK
Pressing
the
BACK
button
will
allow
you
to
go
back
to
previous
menu
options.
ENTER
Pressing
the
ENTER
button
will
turn
on
the
LCD
backlight
or,
Pressing
the
ENTER
button
will
accept
the
currently
displayed
setting
option.
MENU
After
pressing
the
MENU
button,
a
range
of
options
can
be
selected
from
and
changed.
The
selectable
options
in
the
MENU
are
as
follows:
1]
FILTER
TIMES
2]
TEMPERATURE
3]
CONTROL
4]
TIMERS
5]
LIGHTS
B]
INSTALLER
MENU
UP
&
DOWN
The
UP
&
DOWN
buttons
allow
you
to
scroll
through
different
functions
and
or
settings
in
the
menus,
as
well
as
increasing
or
decreasing
temperature
settings.
SPA
The
SPA
button
allows
you
to
toggle
between
Pool
and
Spa
modes.
Pressing
the
SPA
button
begins
the
process
of
heating
the
spa
to
the
spa
temperature
limit.
The
pool/spa
valves
will
move
to
the
spa
and
prime
the
pump
if
required.
Heating
will
occur
to
the
displayed
set
temperature.
To
return
to
automatic
pool
operations
press
the
AUTD
button
or
press
the
SPA
button
to
return
to
automatic
pool
operations.
AQUATEK
User
Manual
VI.
2
[002].docx
8

3 MINS BACKWASH
ENDS IN xx:xx:xx
If
at
any
time
the
PUMP
button
is
pressed
the
pump
is
switched
on
and
the
following
will
be
displayed:
This
function
is
used
for
a
system
back
wash,
pool
vacuuming,
manually
running
the
system
for
a
set
amount
of
time,
running
the
filtration
system
after
adding
chemicals,
etc.
It
can
also
be
used
to
stop
the
pump
from
running
[if
maintenance
is
required]
for
a
set
amount
of
time.
Use
the
Up/Down
buttons
to
increase
or
decrease
the
amount
of
time
that
the
pump
will
run,
or
not
run.
The
countdown
timer
lets
you
know
how
much
time
is
left
until
the
manual
function
ends.
The
timer
amounts
after
the
3
minute
backwash
are:
The
timer
amounts
to
stop
the
pump
PUMP
ON:
30
MINS,
are
displayed
as
follows:
PUMP
ON:
1HR,
HOURS
OFF
01HR,
PUMP
ON:
2HR,
HOURS
OFF
02HR,
PUMP
ON:
3HR,
HOURS
OFF
03HR,
PUMP
ON:
5HR,
HOURS
OFF
05HR,
PUMP
ON:
9HR,
HOURS
OFF
09HR,
PUMP
ON:
10HR,
HOURS
OFF
10HR,
PUMP
ON:
15HR,
HOURS
OFF
15HR,
PUMP
ON:
20HR,
and
HOURS
OFF
20HR,
and
PUMP
ON:
2AHR.
HOURS
OFF
2AHR.
At
any
time
during
the
count
down,
if
you
press
the
ENTER
to
the
selected
time,
and
start
again.
button,
the
timer
will
reset
During
the
count
down,
if
you
press
the
PUMP
button
again,
the
controller
will
return
to
automatic
operation.
NOTE
It
is
advisable
to
go
into
Installer
Setup
first
and
enter
all
equipment
that
will
be
utilised/allocated
in
the
Menu
functions.
AQUATEK
User
Manual
VI.
2
[002].docx
9

↑ ↓
1) FILTER TIMES
2) TEMPERATURE
3) CONTROL
4) TIMERS
5) LIGHTS
6) INSTALLER MENU
•
•
MENU
The
menu
system
can
be
navigated
using
the
or
buttons.
All
selectable
and
changeable
values
will
be
displayed
on
the
LCD
screen.
Press
the
ENTER
button
to
accept
the
currently
displayed
item.
All
menu
items
are
shown
below:
1.
FILTER
TIMES
SANITISER
The
Sanitiser
must
be
set
to
operate
2dhrs
per
day
or
manually
On
as
the
AQUATEK
controller
will
control
the
number
of
hours
per
day
the
system
will
operate.
Refer
to
the
Sanitiser
instructions
for
2dhr
timer
setup,
dosing
and
mounting
reguirements.
You
have
the
option
to
choose
up
to
4
different
Filtration
Times.
When
you
select
the
FILTER
TIMES
menu
option,
the
screen
will
display:
FILTER
ON
TIME
1
OFF
When
you
select
ON
and
press
ENTER
the
screen
will
display:
FILTER
XX:XX
TIME
1
ON
XX:XX
Adjust
the
start
time
and
end
time
for
the
required
filter
cycle.
The
circulation
pump
will
run
between
these
times
for
filtration
purposes.
Once
you
have
set
the
first
filter
time,
you
will
then
be
asked
to
select
a
pump
speed
for
the
first
filter
cycle.
Note:
This
will
only
be
displayed
if
you
have
installed
a
Multi
Speed
Pump
through
the
Installer
Setup
[6.2].
You
won't
be
asked
for
a
pump
speed
if
Single
Speed
pump
was
selected
in
the
Installer
Setup
[6.2],
This
will
be
displayed
as:
FILTER
TIME
1
SPEED
1,
[2,3,
or
A
can
be
selected,
depending
on
pump],
Once
you
have
selected
a
speed
for
the
first
Filter
Cycle,
the
option
for
a
second
filter
cycle
will
be
displayed:
FILTER
ON
TIME
2
OFF
Set
and
adjust
as
with
Filter
Time
1
or
if
not
required
then
set
the
timer
to
OFF.
Repeat
the
above
steps
for
Filter
Time
3
and
t\.
Note:
You
can
run
different
pump
speeds
in
the
separate
filter
times.
Filter
cycle
1
may
run
at
speed
A,
filter
cycle
at
speed
2,
filter
cycle
3
at
speed
1,
and
filter
cycle
A
at
speed
L\.
For
example:
Filter
Time
1:
8.00
-
9.00
at
speed
Filter
Time
2:
9.00
-
15.00
at
speed
2.
Filter
Time
3:
15.00
-
16.00
at
speed
A.
AQUATEK
User
Manual
VI.
2
[002].docx
10

↑ ↓
↑ ↓
↑ ↓
↑ ↓
↑ ↓
2.
TEMPERATURE
When
you
enterTemperature
Settings,
the
first
setting
that
will
be
displayed
is:
POOL
TEMPERATURE
27°c
**
Range
is
OFF,
20°c
to
PO°c
in
l°c
increments.
Default
is
27°c.**
This
temperature
is
the
minimum
pool
temperature
that
you
would
like
the
Heater
to
heat
the
pool
to
if
a
heater
is
utilised.
The
temperature
limit
can
be
increased
or
decreased
with
the
or
buttons
to
a
temperature
of
your
choice.
Once
you
have
selected
a
Pool
Temperature,
press
Enter
and
the
temperature
will
be
set.
The
controller
will
then
display:
SPA
TEMPERATURE
37°c.
**Range
is
OFF,
20°c
to
PO°c
in
l°c
increments.
Default
is
37°c.**
This
is
the
temperature
that
you
would
like
the
SPA
to
be
at
when
in
use.
The
temperature
limit
can
be
increased
or
decreased
with
the
or
buttons
to
a
temperature
of
your
choice.
Once
you
have
selected
a
Pool
Temperature,
press
Enter
and
the
temperature
will
be
set.
The
controller
will
then
display:
SOLAR
TEMPERATURE
30°c.
**Range
is
OFF,
20°c
to
PO°c
in
l°c
increments.
Default
is
30°c.**
This
is
the
temperature
you
would
like
the
solar
to
heat
the
pool
to,
if
it
is
utilised.
The
temperature
limit
can
be
increased
or
decreased
with
the
or
buttons
to
a
temperature
of
your
choice.
Once
you
have
selected
a
Pool
Temperature,
press
Enter
and
the
temperature
will
be
set.
The
controller
will
then
display:
RUN
UNTIL
ON
HEATED
OFF
Use
the
or
buttons
to
select
which
option
you
would
like,
and
press
Enter.
If
you
select
ON,
the
system
will
utilise
the
Heat
Pump
or
Gas
Heater
to
continue
to
heat
the
pool
until
the
temperature
limit
is
reached
while
ignoring
the
set
Heat
Demand
times
set
in
Timers.
Once
the
Pool
Temperature
limit
is
reached
the
controller
will
automatically
return
to
the
scheduled
settings.
Note:
This
may
mean
that
the
filtration
pump
and
heater
may
be
running
for
continuous
extended
periods
of
time,
potentially
longer
than
2Phrs
straight.
The
controller
will
then
return
you
to
the
Main
Menu.
3.
CONTROL
In
this
menu
setting
you
will
be
able
to
manually
turn
on
any
socket
or
valve
that
has
been
allocated
an
appliance.
Socket
1
through
to
8,
and
valve
1
through
to
A,
if
allocated.
Press
Enter
to
open
the
setting
and
the
controller
will
display:
SI:
XXXXXXXXX
AUTO
Use
the
or
buttons
to
move
between
the
allocated
sockets
and
valves.
If
a
socket
or
valve
hasn’t
been
allocated
an
appliance,
then
it
won't
be
shown.
Press
the
Enter
button
to
toggle
between;
AUTO,
OFF,
&
ON.
Press
the
Auto
Button
to
return
all
appliances
to
normal
automatic
operation.
Please
remember
that
vou
will
also
need
to
turn
the
appliance
back
to
Auto,
otherwise
it
will
continue
to
run.
Note
1:
If
a
socket
has
been
set
to
ALWAYS
ON,
then
you
won't
be
able
to
turn
it
on
manually.
Note
2:
A
valve
allocated
to
Pool/Spa,
will
not
be
able
to
be
turned
on
using
this
menu
option.
AQUATEK
User
Manual
VI.
2
[002].docx
11

↑ ↓
↑ ↓
↑ ↓
↑ ↓
•
•
•
•
•
•
•
•
•
•
•
n.
When
you
enter
the
TIMER
menu,
you
can
set
a
number
of
the
allocated
appliances
on
a
timer.
The
appliance
has
to
be
allocated
a
socket
or
valve
to
be
allowed
a
Timer
setting.
Each
appliance
has
the
choice
of
either;
Off,
1
time,
or
2
timer
allocations.
**Note:
Time
periods
for
different
appliances
can
overlap
each
other.**
The
first
available
appliance
to
be
set
on
a
timer
will
be
displayed
as:
Socket
#X
XXXXXXXXXXXX.
Press
the
ENTER
button
to
be
able
to
adjust
the
time
setting
or
use
the
or
buttons
to
display
the
Appliance
to
be
set.
You
will
see
displayed:
xxxxxxxxxxx
TIME
1
ON.
Toggle
the
or
buttons
to
either
turn
the
appliance
ON
or
OFF
the
timer.
If
you
select
OFF
the
next
allocated
appliance
will
be
shown.
If
you
select
ON
then
the
controller
will
display:
XXXXXXXXXXXXX
TIME
1
FRM
XX.
XX
Use
the
or
buttons
and
the
Enter
button
to
allocate
a
start
time.
Once
the
time
has
been
entered,
the
next
display
will
be:
XXXXXXXXXXXXX
TIME
1
TO
XX.XX
Use
the
or
buttons
and
the
Enter
button
to
allocate
an
end
time.
Once
the
time
has
TIMERS
been
entered,
the
next
display
will
be:
XXXXXXXXXXXXX
TIME
2
ON/OFF
Adjust
TIME
2
setting
as
with
TIME
1.
Once
the
TIMER
setting
has
been
completed
you
can
move
onto
the
next
allowable
appliance.
Adjust
and
set
as
above.
Notes:
Socket
type
"Sanitiser"
is
not
allowed
on
appliance
timer,
as
it
follows
filter
timer.
Socket
type
"Filter
Timer"
is
not
allowed
on
appliance
timer,
as
it
follows
filter
timer.
Socket
type
"Solar"
is
not
allowed
on
appliance
timer,
it
follows
solar
configuration.
Socket
type
"Always
On"
is
not
allowed
on
appliance
timer.
Socket
type
"Blower"
is
not
allowed
on
appliance
timer,
used
only
in
Spa
mode.
Socket
type
"Jet
Pump"
is
not
allowed
on
appliance
timer,
used
only
in
Spa
mode.
Socket
type
"Ind
Heat
Pump"
is
not
allowed
on
appliance
timer,
it
follows
heating
configuration.
Valve
type
"Pool/Spa"
is
not
allowed
on
appliance
timer,
used
on
in
Pool/Spa
mode.
Valve
type
"Solar"
is
not
allowed
on
appliance
timer,
as
it
follows
solar
configuration.
Valve
type
"Feature
from
Solar"
is
not
allowed
on
appliance
timer
as
it
is
a
manual
function
only
and
will
only
activate
if
a
socket
has
been
allocated
to
be
an
'Independent
Solar
Pump'.
VF
contact
types
"Gas
Heater
&
Heat
Pump"
are
not
allowed
on
appliance
timers.
Ensure
when
vou
set
the
timers
for
different
appliances
that
the
maximum
combined
load
DOES
NOT
exceed
either
the
controllers
power
ratino.
or
the
power
ratino
of
the
expansion
unit/s
when
the
different
appliances
are
activated
at
the
same
time.
AQUATEK
User
Manual
VI.
2
[002].docx
12

↑ ↓
↑ ↓
•
5.
LIGHTS
SPECIAL
VALVE
FEATURES
In
this
menu
setting,
you
can
only
change
the
colour
of
your
allocated
Pool
and
Spa
light/s.
Garden
lights
are
not
given
the
option
of
colour
changing.
The
socket
number
and
the
brand/type
of
light
must
have
been
allocated
in
the
Installer
Setup
under
Appliances
[B.
3]
before
you
can
change
the
colours
through
this
menu
option.
When
you
enter
the
Lights
menu
the
controller
will
display
the
allocated
socket
number,
allocated
light
type,
and
the
brand/style
of
light.
For
example.
S6:
POOL
LIGHT
SINGLE
CQLQUR
The
or
buttons
can
be
used
to
move
between
the
allocated
lights
to
the
light
you
wish
to
change.
Once
the
Light
is
displayed
on
the
screen,
press
Enter
and
the
controller
will
display:
S6:
[Brand
name]
[current
colour]
Use
the
or
buttons
to
toggle
through
the
range
of
colours
[if
any]
associated
with
that
brand
of
pool
light.
Press
Enter
to
accept
the
colour
you
wish
to
choose.
If
you
so
wish
you
can
then
move
onto
another
allocated
socket
and
change
the
colour
settings
of
that
socket.
Adjust
the
colour
as
described
above.
Note:
A
maximum
of
3
sockets
can
be
allocated
to
lights,
whether
Pool,
or
Spa.
Each
socket/group
of
lights
will
be
the
same
colour
as
chosen
for
that
allocated
socket.
Feature
from
Solar
This
feature
gives
you
the
ability
to
be
able
to
utilise
an
independent
solar
heating
system
for
a
water
feature,
such
as
a
water
slide.
A
socket
needs
to
be
allocated
under
Appliances
as
a
solar
pump
and
a
valve
socket
allocated
as
a
Feature
from
Solar.
A
3
way
valve
with
actuator
needs
to
be
plumbed
in
after
the
solar
pump
but
before
the
water
goes
up
to
the
roof.
The
Feature
from
Solar
needs
to
be
turned
to
ON
under
the
Control
menu.
This
will
ensure
the
valve
is
turned
to
divert
water
to
the
water
feature
and
the
solar
pump
is
turned
on.
No
solar
heating
is
allowed
when
the
feature
is
utilised.
No
Timer
can
be
set
for
this
feature,
so
it
will
need
to
be
turned
to
OFF
or
AUTO
in
the
Control
menu.
Once
the
feature
is
turned
to
OFF
or
AUTO
the
solar
pump
may
turn
back
on
again
to
sample
the
water
temperature
and
resume
solar
heating
of
the
system
if
solar
gain
is
available.
Other
This
is
a
Timer
based
feature
for
a
valve
output.
When
the
feature
is
within
its
Timer
range
[or
manually
turned
On
or
Off]
it
will
turn
the
Valve
output
on.
This
output
can
be
utilised
to
turn
a
valve,
or
switch
on
a
contactor
point
for
an
additional
heater.
Note:
This
option
will
not
instigate
turning
a
filtration/circulation
pump
on.
AQUATEK
User
Manual
VI.
2
[002].docx
13

↑ ↓
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
6.
INSTALLER
MENU
The
Installer
Setup
is
where
you
will
go
to
enter
all
the
equipment
that
is
installed
on
the
Pool/Spa
system
and
can
have
its
settings
changed
in
the
Menu
functions
or
via
the
App.
6.
INSTALLER
MENU
6.1
APPLIANCES
Under
the
Installer
Menu
there
is
a
range
of
options
to
choose
from.
These
are:
1.
Appliances
2.
Pump
3.
Lights
A.
Heating
5.
Spa
B.
Heat
Demand
7.
Pump
Call
8.
Water
Feature
9.
Temperature
Sensor
10.
Expansion
Unit
11.
Set
Time
12.
WIFI
13.
Reset
Passcode
14.
Factory
15.
About
Use
the
or
buttons
to
toggle
through
the
list
of
menu
options.
When
the
option
you
want
is
displayed
on
the
screen,
press
the
Enter
button.
Appliances
can
be
allocated
on
up
8
power
sockets,
A
valves
and
1
VF
contact.
Socket
1-2,
Valves
1-4,
and
the
VF
Contact
are
all
located
on
the
master
controller.
Sockets
3,
A,
&
5
are
located
on
Expansion
Unit
1.
These
sockets
are
only
available
for
selection
if
the
expansion
unit
is
there
and
has
been
enabled.
Sockets
B,
7,
&
8
are
located
on
Expansion
Unit
2.
These
sockets
are
only
available
for
selection
if
the
expansion
unit
is
there
and
has
been
enabled.
The
list
of
appliances
available
to
choose
from
are
listed
below:
Sockets
Valves
Sanitiser
Water
Feature
Filter
Pump
Solar
Pump
Cleaning
Pump
Other
Blower
Always
On
Pool
Light
Jet
Pump
Spa
Light
Heating
Pump
[independent]
Garden
Light
None
Pool/Spa
Feature
from
Solar
Solar
Other
Water
Feature
None
In
Floor
VF
Contact
Gas
Heater
|sjone
Heat
Pump
AQUATEK
User
Manual
VI.
2
[002].docx
14

↑ ↓
↑ ↓
↑ ↓
↑ ↓
↑ ↓
6.1
APPLIANCES
CONTINUED
6.2
PUMP
When
you
enter
the
Appliance
Menu,
the
first
thing
that
will
be
displayed
is:
SOCKET
#1
[currently
allocated
appliance]
The
or
buttons
are
used
to
toggle
between
the
Sockets
of
the
Master
Controller
then
Expansion
Unit
1,
then
Expansion
Unit
2,
then
the
Valves
and
VF
Contact
of
the
Master
Controller.
Once
the
Appliance
you
want
to
change
is
displayed
on
the
screen,
press
Enter.
This
will
move
the
cursor
next
to
the
allocated
appliance.
Use
the
or
buttons
to
toggle
through
the
range
of
Appliances
that
can
be
selected
for
that
output.
Once
the
Appliance
you
want
to
select
is
displayed,
press
Enter.
The
Appliance
will
have
been
selected
and
the
controller
will
then
display
the
next
socket/valve/VF
contact:
SOCKET
#2
[currently
allocated
appliance]
Note:
When
you
move
onto
the
next
appliance
the
cursor
will
still
be
next
to
the
allocated
appliance.
If
you
wish
to
change
this
appliance
simply
use
the
or
buttons
to
toggle
through
the
range
of
allowable
appliances.
Press
Enter
to
select.
Keep
pressing
Enter
to
scroll
through
the
allocated
appliances
[if
there
is
another
socket,
valve,
or
VF
contact
you
wish
to
change]
until
the
appliance
you
wish
to
change
is
displayed.
Use
the
or
buttons
to
toggle
through
the
range
of
allowable
appliances.
Press
Enter
to
select.
Alternatively,
if
you
don't
want
to
change
any
more
appliances,
press
the
MENU
button
to
exit.
When
changing
the
Valve
appliances,
the
controller
will
display:
VALVE
#1
[currently
allocated
appliance]
The
Valve
appliance
is
changed
the
same
way
as
the
Socket
appliances.
Note:
The
Aquatek
Controller
will
only
turn
2
valves
at
the
same
time
,
ie
Pool/Spa
valves.
There
will
be
a
AO
second
delay
before
a
third
or
fourth
valve
will
be
turned.
When
changing
the
VF
Contact,
the
controller
will
display:
VF
CONTACT
[currently
allocated
appliance]
The
VF
Contact
is
changed
the
same
way
as
the
Socket
&
Valve
appliances.
SANITISER
The
Sanitiser
must
be
set
to
operate
2dhrs
per
day
or
manually
On
as
the
AQUATEK
controller
will
control
the
number
of
hours
per
day
the
system
will
operate.
Refer
to
the
Sanitiser
instructions
for
2dhr
timer
setup
and
dosing
requirements.
In
this
menu
option,
you
will
be
able
to
select
which
type
and
brand
of
filtration
pump
your
system
is
running
and
what
its
default
speed
will
be.
When
you
Enter
this
sub
menu
option,
the
controller
will
display
the
option
to
choose
either
a
Single
Speed
Pump
or
Multi
Speed
Pump:
PUMP
TYPE
MULTI-SPEED
Use
the
or
buttons
to
switch
between
the
2
options,
press
Enter
to
accept
the
option
you
require.
AQUATEK
User
Manual
VI.
2
[002].docx
15

↑ ↓
•
•
•
↑ ↓
6.2
If
you
Enter
SINGLE
SPEED,
the
controller
will
accept
the
option
and
return
you
to
the
Installer
Setup
Menu.
If
you
Enter
MULTI
SPEED,
then
the
controller
will
display:
PUMP
BRAND
RELTECH
Use
the
or
buttons
to
scroll
through
the
range
of
allowable
pump
brands.
Press
Enter
on
the
brand
you
wish
to
select
when
you
see
it
displayed.
The
options
for
brands
of
Multi
Speed
Pumps
are:
None
Theralux
Theralux
485
Reltech
Reltech
485
P
Hayward
485
Pentair
VS/F
Pentair
Enviromax
1500
Insnrg
DAB
Henden
PUMP
Speck
CONTINUED
Oasis
V
Series
Once
you
have
pressed
Enter
to
select
the
pump,
the
controller
will
ask
you
to
set
4
pump
speeds.
In
the
case
of
the
Theralux
485,
Hayward
485,
Reltech
485
P,
Henden
&
Insnrg
brand
pumps,
you
will
be
asked
to
set
the
speeds
in
RPM.
In
the
case
of
the
PentairVS/F,
Theralux,
Reltech
and
Speck
pumps,
you
will
set
the
default
speed
only
as
the
pump
has
pre-set
speeds.
In
the
case
the
DAB
brand,
you
will
be
asked
to
set
the
4
speeds
as
a
percentage.
Note:
The
Theralux
,
Speck
and
Reltech
pumps
only
have
3
speeds
to
choose
from
and
need
to
be
set
via
the
manufacturer's
instructions.
The
Pentair
VS/F
will
need
to
have
4
pump
speeds
set
via
the
manufacturer's
instructions.
Once
the
speeds
have
been
set
for
the
Theralux
485,
Hayward
485,
Reltech
485
P,
Insnrg,
Henden,
and
DAB
pumps,
the
controller
will
then
ask
what
Default
speed
you
would
like
the
pump
to
be
set
at.
This
is
displayed
as:
PUMP
DEFAULT
SPEED
X
Use
the
or
buttons
to
scroll
through
the
range
of
pump
speeds
[1,
2,
3,
&
4]
that
you
have
just
set.
Once
you
have
adjusted
the
default
speed,
press
Enter
to
accept.
The
controller
will
accept
the
default
speed
and
return
to
the
Installer
Setup
Menu.
AQUATEK
User
Manual
VI.
2
[002].docx
16

•
•
↑ ↓
↑ ↓
↑ ↓
•
•↑ ↓
•
6.3
LIGHTS
In
this
menu
option,
you
will
be
able
to
select
which
type
and
brand
of
Pool
&
Spa
lights
that
you
have
installed.
A
maximum
of
3
sockets
can
be
allocated
to
lights
,
whether
Pool,
or
Spa.
Each
of
the
3
sockets
will
run
a
Light
Transformer.
Each
socket/group
of
lights
will
be
the
same
colour
as
chosen.
Before
any
pool
or
spa
lights
can
be
setup
in
this
menu
option,
1,
2,
or
3
sockets
need
to
have
been
allocated
in
appliances
to
either
the
pool
or
spa
light.
When
you
enter
this
menu
option,
the
first
socket
that
has
been
allocated
will
be
displayed
along
with
the
allocated
appliance.
The
controller
will
display:
S2:
SPA
SINGLE
COLOUR
Use
the
or
buttons
to
scroll
through
the
allocated
sockets,
press
Enter
to
change
the
displayed
socket.
After
you
press
Enter,
the
cursor
will
be
located
on
the
second
line.
Use
the
or
buttons
to
scroll
through
the
allowable
brands
of
lights.
The
allowable
brands
and
types
are
as
follows:
AquaQuip
AquaQuip
INS
Aquatight
Spa
Electrics
Spa
Electrics
Multi
Plus
Astral
Pool
ModLite
Jandy
Single
Colour
[non-branded]
Press
Enter
to
select
the
light
brand
installed.
The
controller
will
now
display:
[For
Example]
AQUAQUIP
PURE
RED
Use
the
or
buttons
to
scroll
through
the
colours
that
are
associated
with
the
brand
of
light.
Once
the
colour
you
want
is
displayed
on
the
screen,
press
Enter
to
accept
the
colour.
If
there
is
only
one
socket
that
is
allocated
to
a
light,
the
controller
will
return
you
to
the
Installer
Setup
Menu.
If
there
is
more
than
one
socket
allocated
to
a
light,
the
controller
will
keep
you
in
this
menu
option.
You
can
use
the
or
buttons
to
scroll
through
the
other
allocated
sockets.
Press
Enter
when
another
allocated
socket
is
displayed
in
order
to
change
that
sockets
settings.
Change
the
settings
as
above.
Once
you
have
finished,
either
press
the
Back
Button
to
return
you
to
the
Installer
Setup
Menu
or
press
the
Menu
Button
to
return
the
controller
to
normal
operations.
AQUATEK
User
Manual
VI.
2
[002].docx
17

•
•↑ ↓
•
•
↑ ↓
↑ ↓
↑ ↓
6.4
In
this
Menu
option,
you
will
be
setting
up
the
type/s
of
heating
that
is
installed.
The
options
are:
Solar
Heat
Pump
Gas
Heater
When
you
enter
this
menu
option
the
first
thing
that
is
displayed
is:
SOLAR
1.
NONE
With
Solar
Heating,
you
have
the
options
of:
1.
None
2.
Separate
[Independent
plumbing]
3.
Valve
A.
Boosted
[Integrated
plumbing]
If
you
have
no
Solar
Heating
installed,
press
Enter
to
accept
1.
None
and
the
controller
will
move
you
onto
the
next
option.
If
you
have
an
independent
solar
heating
system,
use
or
buttons
to
scroll
down
to
2.
Separate
and
press
Enter.
If
you
have
a
system
where
a
valve
is
turned
to
send
water
into
the
solar
panels,
select
3.
Valve.
If
you
have
a
Boosted
[integrated]
system,
scroll
to
A.
Boosted
and
select.
Use
the
or
buttons
to
select
which
option
you
would
like,
and
press
Enter.
Once
you
have
selected
one
of
the
above
options,
the
controller
will
display:
SOLAR
ON
HEATING
WINTER
MODE
OFF
Use
the
or
buttons
to
select
which
option
you
would
like,
and
press
Enter.
Note:
If
you
selected
None
for
SOLAR,
then
the
above
option
will
not
be
displayed.
Once
you
have
pressed
Enter
to
select,
the
controller
will
display:
SOLAR
SPEED
X
The
controller
is
asking
what
speed
you
would
like
the
pump
to
run
at
when
solar
heating
is
asked
for.
Note:
This
option
will
only
appear
if
you
have
selected
either
Valve
or
Boosted
for
your
SOLAR
options.
Note:
If
you
are
running
a
single
speed
pump,
this
question
will
not
appear.
Use
the
or
buttons
to
select
which
pre-set
speed
you
would
like,
and
press
Enter.
Once
you
have
selected
the
pump
speed,
the
controller
will
then
display:
SOLAR
START
TIME
XX.XX
Adjust
as
above.
Once
you
have
adjusted
and
accepted
the
Solar
Heating
start
time,
the
controller
will
move
you
onto
the
next
option.
What
will
be
displayed
next
will
depend
upon
what
was
selected
for
VF
Contact
in
Appliance
Setup.
If
nothing
was
selected
under
VF
Contact
then
the
controller
will
return
you
to
the
Installer
Setup
Menu.
AQUATEK
User
Manual
VI.
2
[002].docx
18

↑ ↓
↑ ↓
•
•
•
↑ ↓
↑ ↓
↑ ↓
6.4
If
Heat
Pump
was
selected
under
VF
Contact
then
the
following
will
be
displayed:
HEAT
PUMP
ON
OFF
Use
the
or
buttons
to
move
the
cursor
to
either
ON
or
OFF.
Enter
On
to
enable
the
controller
to
run
the
Heat
Pump
or
OFF
to
disable
the
heater.
Press
the
Enter
button
to
accept.
Once
you
have
accepted
either
ON
or
OFF,
the
controller
will
display
a
choice
of
3
Heating
Installation
Type
options:
1.
FILTER
2.
INDEPENDENT
3.
INDEPENDENTWITH
SENSOR
You
will
use
the
or
arrows
to
select
the
option
that
best
suits
your
installation,
press
Enter
to
accept
and
the
controller
will
move
you
onto
the
next
option.
Filter
-
Meaning
that
the
heater
is
instailed
within
the
filtration
plumbing.
Independent
-
Meaning
that
the
heater
is
plumbed
in
separately
to
the
filtration
system
and
will
have
its
own
circulating
pump.
The
pool
will
be
heated
to
a
temperature
designated
by
the
independent
heater.
Independent
with
Sensor
-
The
heater
is
plumbed
independently,
but
the
Aquatek
will
controller
the
temperature
and
will
need
the
pool
sensor
drilled
into
the
pipe
in
front
of
the
Independent
heaters
circulation
pump.
If
Gas
Heater
was
selected
under
VF
Contact,
then
the
following
will
be
displayed:
GAS
HEATER
ON
HEATING
OFF
CONTINUED
If
you
select
ON,
the
controller
will
then
display:
GAS
HEATER
COOLDOWN
XXMIN
This
is
the
controller
asking
how
many
minutes
you
would
like
the
filtration
pump
to
run
for
once
the
Heater
has
stopped
heating.
Use
the
or
buttons
to
increase
or
decrease
the
amount
of
time.
The
range
of
time
for
the
Cool
Down
is
OOMins
to
59Mins.
Note:
This
function
is
here
to
help
prolong
the
life
of
a
Gas
Heater.
5Mins
is
an
acceptable
minimum
but
the
time
can
be
extended
if
so
desired.
Once
you
have
selected
the
timeframe
you
would
like
for
the
Gas
Heater
COOL
DOWN,
the
controller
will
ask
you
to
select
one
of
the
3
Heating
Installation
Types.
1.
FILTER
2.
INDEPENDENT
3.
INDEPENDENTWITH
SENSOR
You
will
use
the
or
arrows
to
select
the
option
that
best
suits
your
installation,
press
Enter
to
accept
and
the
controller
will
move
you
onto
the
next
option.
If
you
select
OFF,
the
controller
will
move
you
onto
the
next
option
and
display:
HEATING
PUMP
SPEED
X
Use
the
or
buttons
to
select
which
pre-set
speed
you
would
like,
and
press
Enter,
and
the
controller
will
exit
you
to
the
Installer
Setup
Menu.
AQUATEK
User
Manual
VI.
2
[002].docx
19
Table of contents
Other Dontek Controllers manuals

Dontek
Dontek Aquasun 3 FRP User manual

Dontek
Dontek Aquasun 2 User manual

Dontek
Dontek AQUASMART 5 SV User manual

Dontek
Dontek V2-1 User manual

Dontek
Dontek Aquasun 3 User manual

Dontek
Dontek H7 SV User manual

Dontek
Dontek AQUAHEAT H5TC User manual

Dontek
Dontek Aquasun 3CD User manual

Dontek
Dontek V2 Series Service manual

Dontek
Dontek AquaSun 3RB User manual