D+H VCD 204 User manual

VCD 204/yyy
99.831.09 1.4/02/22
Please order bracket sets separately
en Original instructions . . . . . . . . . . . . . . . . . . . . . . . Page . . . . . . . 2
E 222052
C US
VCD 204/yyy
With loop option
VCD 204/yyy
D+H Downloads

2/8 3/8
VCD 204 VCD 204
99.831.09 1.4/02/22 99.831.09 1.4/02/22
English English
Entrapment protection (see N.12 of Safety Notes; p 2/8)
In "CLOSE" direction the drive has an active
clamping protection for the main closing edge. With
an overload in the closing range 3 and 2 the drive
runs "OPEN" for 20 seconds, then drive "CLOSE"
again. If after three attempts a closing is not possible,
the drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s (0.2"/s). The drives were
not evaluated for entrapment protection.
Higher forces can occur on
besides closing edges.
Danger of violent pressure
in handaccessible area.
The dri ves were not evalua ted f or
entrapment protection.
All forces + approx. 20 % switch-off reserve (temporary)
Running speed and forces
6 mm/s (0.24"/s)
150 N (33.7 lbf)
(Safety cut-off force)
77 mm
(3")
6 mm/s (0.24"/s)*
200 N (45 lbf) **
23 mm
(0.9")
Closure Ranges
5 mm/s (0.2"/s)
150 N (33.7 lbf)
Main closing edge
Beside closing edge
Beside -
closing edge
! IMPORTANT ! Safety Notes
1. Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is
ensured by regular in-house training.
2. All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3. For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4. Observe enclosed red safety slip!
5. Danger of violent pressure in handaccessible area.
6. The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7. A suitable field wiring means should be provided in the end use application.
8. The mounting and routing of external wiring should be determined in the end product.
9. The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above
the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be
determined during the end product investigation.
13. The drive shall be connected to a Class 2 power supply.
For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.
Intended use
- Chain drive for electric opening and closing of
windows and flaps in the facade and roof area
- Useable for daily natural ventilation
- Operating voltage 24 V DC
- Only for inside mounting
Performance features
- Micro processor controlled electronics
- Individually programmable via Powerline (PLP1
with BI-BT 2 and SCS)
- Stroke programming with magnets
- Low running noises
- Connection via plug connector
- Tandem-safety function for operation of two
VCD 204 drives on one sash
Operating voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r ed safety slip!
Safety notes
Drive unit with 2,5 m (97.5") PVC cable. Dependent
on the type of window, different bracket sets are
available separately.
Extent of supply
Up to two VCD 204 drives and one locking drive can
be used in tandem. Combined TMS and BRV signal.
The BRV signal is only output when in the end
position - this prevents locking drives and modules
from malfunctioning.
During the learning phase, the activated stroke is
transferred to the tandem drive via the TMS+
function.
TMS+ / -BRV function
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Type VCD 204/yyy
Power supply 24 V DC / ± 20 %
Nominal current 0.35 A
Nominal force 200 N (45 lbf)
Nominal locking force approx. 2000 N (449.6 lbf) (excluding bracket)
Service life >20 000 double strokes
Duty cycle 30 % (With cycle time 10 minutes)
Housing Zinc-diecasting, powdercoated
Ingress protection IP 30
Temp. range 0 ... +60 °C (+32 °F ... + 140 °F)
Emission sound pressure level LpA ≤ 46 dB(A)
/
Nominal stroke length * ** 250 or 350 mm (see type plate)
Additional functions ** Closing edge protection activated (3 stroke repeatings);
Locking relief activated
*Adjustable with PLP 1 ** Programmable with PLP 1 and SCS
Technical data

2/8 3/8
VCD 204 VCD 204
99.831.09 1.4/02/22 99.831.09 1.4/02/22
English English
Entrapment protection (see N.12 of Safety Notes; p 2/8)
In "CLOSE" direction the drive has an active
clamping protection for the main closing edge. With
an overload in the closing range 3 and 2 the drive
runs "OPEN" for 20 seconds, then drive "CLOSE"
again. If after three attempts a closing is not possible,
the drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s (0.2"/s). The drives were
not evaluated for entrapment protection.
Higher forces can occur on
besides closing edges.
Danger of violent pressure
in handaccessible area.
The dri ves were not evalua ted f or
entrapment protection.
All forces + approx. 20 % switch-off reserve (temporary)
Running speed and forces
6 mm/s (0.24"/s)
150 N (33.7 lbf)
(Safety cut-off force)
77 mm
(3")
6 mm/s (0.24"/s)*
200 N (45 lbf) **
23 mm
(0.9")
Closure Ranges
5 mm/s (0.2"/s)
150 N (33.7 lbf)
Main closing edge
Beside closing edge
Beside -
closing edge
! IMPORTANT ! Safety Notes
1. Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is
ensured by regular in-house training.
2. All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3. For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4. Observe enclosed red safety slip!
5. Danger of violent pressure in handaccessible area.
6. The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7. A suitable field wiring means should be provided in the end use application.
8. The mounting and routing of external wiring should be determined in the end product.
9. The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above
the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be
determined during the end product investigation.
13. The drive shall be connected to a Class 2 power supply.
For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.
Intended use
- Chain drive for electric opening and closing of
windows and flaps in the facade and roof area
- Useable for daily natural ventilation
- Operating voltage 24 V DC
- Only for inside mounting
Performance features
- Micro processor controlled electronics
- Individually programmable via Powerline (PLP1
with BI-BT 2 and SCS)
- Stroke programming with magnets
- Low running noises
- Connection via plug connector
- Tandem-safety function for operation of two
VCD 204 drives on one sash
Operating voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r ed safety slip!
Safety notes
Drive unit with 2,5 m (97.5") PVC cable. Dependent
on the type of window, different bracket sets are
available separately.
Extent of supply
Up to two VCD 204 drives and one locking drive can
be used in tandem. Combined TMS and BRV signal.
The BRV signal is only output when in the end
position - this prevents locking drives and modules
from malfunctioning.
During the learning phase, the activated stroke is
transferred to the tandem drive via the TMS+
function.
TMS+ / -BRV function
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Type VCD 204/yyy
Power supply 24 V DC / ± 20 %
Nominal current 0.35 A
Nominal force 200 N (45 lbf)
Nominal locking force approx. 2000 N (449.6 lbf) (excluding bracket)
Service life >20 000 double strokes
Duty cycle 30 % (With cycle time 10 minutes)
Housing Zinc-diecasting, powdercoated
Ingress protection IP 30
Temp. range 0 ... +60 °C (+32 °F ... + 140 °F)
Emission sound pressure level LpA ≤ 46 dB(A)
/
Nominal stroke length * ** 250 or 350 mm (see type plate)
Additional functions ** Closing edge protection activated (3 stroke repeatings);
Locking relief activated
*Adjustable with PLP 1 ** Programmable with PLP 1 and SCS
Technical data

4/8 5/8
VCD 204-PLP VCD 204-PLP
99.831.09 1.4/02/22 99.831.09 1.4/02/22
Stroke limiting with magnets
When using two VCD 204 on one window, both drives must be electrically connected in order to
set the stroke, although only one drive needs to be switched to the stroke learning mode with the
magnet.
English English
Dimensions
30 mm
(1.18")
41,2 mm
(1.6")
480 mm (18.9")
47 mm
(1.85")
aa
Voltage must continue to
be applied to the drive when
moving in the “CLOSE”
direction. Hold the magnet next
to the drive as shown in the
diagramme (2 sec.) until you hear
a pulsating ton > The drive is now
in learning mode. The magnet
can now be removed and the
drive no longer has to be under
voltage.
Close drive.
1Allow the drive to run
“OPEN” until you reach the
required stroke.
If the stroke is set incorrectly,
the procedure is accidentally
interrupted or the drive
continues to the full stroke
length, please return to point 1
and start again.
STOP
3
appr.100 mm / 3,9'‘
learning mode
appr. 2 sec.
2
Mount the drives mechanical stress-free.
With that, a better load distribution is ensured on all
the drives.
Mounting information
Maintenance and cleaning
Maintenance work is only allowed when the device is in
a de-energized condition! Inspection and maintenance
has to be carried out according to D+H maintenance
notes. Only original D+H spare parts may be used.
Repair is to be carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder Maik Schmees
CEO CTO
28.02.2022
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal

4/8 5/8
VCD 204-PLP VCD 204-PLP
99.831.09 1.4/02/22 99.831.09 1.4/02/22
Stroke limiting with magnets
When using two VCD 204 on one window, both drives must be electrically connected in order to
set the stroke, although only one drive needs to be switched to the stroke learning mode with the
magnet.
English English
Dimensions
30 mm
(1.18")
41,2 mm
(1.6")
480 mm (18.9")
47 mm
(1.85")
aa
Voltage must continue to
be applied to the drive when
moving in the “CLOSE”
direction. Hold the magnet next
to the drive as shown in the
diagramme (2 sec.) until you hear
a pulsating ton > The drive is now
in learning mode. The magnet
can now be removed and the
drive no longer has to be under
voltage.
Close drive.
1Allow the drive to run
“OPEN” until you reach the
required stroke.
If the stroke is set incorrectly,
the procedure is accidentally
interrupted or the drive
continues to the full stroke
length, please return to point 1
and start again.
STOP
3
appr.100 mm / 3,9'‘
learning mode
appr. 2 sec.
2
Mount the drives mechanical stress-free.
With that, a better load distribution is ensured on all
the drives.
Mounting information
Maintenance and cleaning
Maintenance work is only allowed when the device is in
a de-energized condition! Inspection and maintenance
has to be carried out according to D+H maintenance
notes. Only original D+H spare parts may be used.
Repair is to be carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder Maik Schmees
CEO CTO
28.02.2022
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal

99.831.09 1.4/02/22 99.831.09 1.4/02/22
English English
VCD 204-PLP VCD 204-PLP
6/8 7/8
Connection
1 drive
max. 2 drives
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy-PLP
Mot. a
Mot. b
Junction box
(BN) brown
(YE) yellow
(GN) green
(WH) white
(PK) pink
(GY) grey
Pin Assigment
Mot. b
(BN)
Mot. a
(WH)
Standard Optional signals
max. 50 V / 0.5 A
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SZ (no))
GY (SZ+SA (o))
PK (SA (no))
-SA-SZ
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SKS)
GY (SKS)
-SKS
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SGI)
GY (SGI)
-SGI
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
WH (+24 V)
YE (TMS+)
BN (–)
GN (n.c.)
WH (+24 V)
YE (TMS+)
BN (–)
GN (n.c.)
VCD 204/yyy
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
VCD 204/yyy
With loop option
Standard
Options see above
max. 2 drives
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy-PLP
(BN)
(YE)
(WH)
Junction box
Mot. a
Mot. b
Protect against
short circuit
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
(BN)
(YE)
(WH)
Junction box
Mot. a
Mot. b
Protect against
short circuit
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
With loop option
1 Antrieb / 1 drive /
1 motorisation / 1 motore
max. 2 Antriebe / max. 2 drives /
max. 2 motorisations / máx. 2 motores
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
max. 2 Antriebe / max. 2 drives /
max. 2 motorisations / máx. 2 motores
Gegen Kurzschluss sichern /
Protect against short circuit /
Protéger contre les courts-circuits /
Proteger contra cortacircuitos
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-DS
Option - Durchgeschliffen (DS) /
Option – loopthrough (DS) /
Option – Bouclé (DS) /
Opcional – Lijado (DS)
Gegen Kurzschluss sichern /
Protect against short circuit /
Protéger contre les courts-circuits /
Proteger contra cortacircuitos
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
GN (n.c.)
GN (n.c.)

99.831.09 1.4/02/22 99.831.09 1.4/02/22
English English
VCD 204-PLP VCD 204-PLP
6/8 7/8
Connection
1 drive
max. 2 drives
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy-PLP
Mot. a
Mot. b
Junction box
(BN) brown
(YE) yellow
(GN) green
(WH) white
(PK) pink
(GY) grey
Pin Assigment
Mot. b
(BN)
Mot. a
(WH)
Standard Optional signals
max. 50 V / 0.5 A
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SZ (no))
GY (SZ+SA (o))
PK (SA (no))
-SA-SZ
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SKS)
GY (SKS)
-SKS
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
GN (SGI)
GY (SGI)
-SGI
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
WH (+24 V)
YE (TMS+)
BN (–)
GN (n.c.)
WH (+24 V)
YE (TMS+)
BN (–)
GN (n.c.)
VCD 204/yyy
WH (Mot. a)
YE (TMS+/BRV)
BN (Mot. b)
VCD 204/yyy
With loop option
Standard
Options see above
max. 2 drives
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy-PLP
(BN)
(YE)
(WH)
Junction box
Mot. a
Mot. b
Protect against
short circuit
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
(BN)
(YE)
(WH)
Junction box
Mot. a
Mot. b
Protect against
short circuit
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-PLP
With loop option
1 Antrieb / 1 drive /
1 motorisation / 1 motore
max. 2 Antriebe / max. 2 drives /
max. 2 motorisations / máx. 2 motores
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
max. 2 Antriebe / max. 2 drives /
max. 2 motorisations / máx. 2 motores
Gegen Kurzschluss sichern /
Protect against short circuit /
Protéger contre les courts-circuits /
Proteger contra cortacircuitos
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
Mot. b
TMS+ /
BRV
Mot. a
(BN)
(YE)
(WH)
VCD 204/yyy
(BN)
(YE)
(WH)
Mot. b
TMS+ /
BRV
Mot. a
VCD 204/yyy-DS
Option - Durchgeschliffen (DS) /
Option – loopthrough (DS) /
Option – Bouclé (DS) /
Opcional – Lijado (DS)
Gegen Kurzschluss sichern /
Protect against short circuit /
Protéger contre les courts-circuits /
Proteger contra cortacircuitos
Mot. a
Mot. b
Abzweigdose /
Junction box /
Boîte de dérivation /
Caja de conexión
GN (n.c.)
GN (n.c.)

99.831.09 1.4/02/22
D+H Mechatronic AG
Georg-Sasse-Str. 28-32
, Germany22949 Ammersbek
: +49 239Tel. 40-605 65
: +49Fax 40-605 65 254
E-Mail: info@dh-partner.com
www.dh-partner.com
© 2022 D+H Mechatronic AG, Ammersbek
Rights to technical modifications reserved /
100 % Recycled paper
Other manuals for VCD 204
3
Table of contents
Other D+H DC Drive manuals

D+H
D+H CDP 1500 BSY+ User manual

D+H
D+H CDC 200/600 User manual

D+H
D+H ZA 35 User manual

D+H
D+H KA 66-SW User manual

D+H
D+H ZA 105-K User manual

D+H
D+H KA 34-BSY+ User manual

D+H
D+H KA 66-TW User manual

D+H
D+H LDx-1400-1-PLP User manual

D+H
D+H VCD-0204-0x50-5-ACB-M User manual

D+H
D+H SHD 54/450-V User manual
Popular DC Drive manuals by other brands

DeVilbiss
DeVilbiss QS-5001 Service bulletin

ITOH DENKI
ITOH DENKI POWER MOLLER 24 CBM-103FN manual

Sony
Sony SDX-D500C Operator's guide

National Instruments
National Instruments 9512 C Series Getting started

DART Controls
DART Controls 65E Series instruction manual

Infineon
Infineon EiceDRIVER 6ED Series Application note