E2S D1xL1FV100-A User manual

INSTRUCTION MANUAL
D1xL1 & D1xL2
Loudspeaker
Class I, Zone 1, 2, 21 & 22
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 1 of 6
D1xL1F
D1xL2F
D1xL2H
1) Product Table
Unit Type Code
Input
Power (Watts)
Max I/P Volts
Sound
Pressure Level
dB(A)
Max
Rated
Pink
Noise
@ 1W
D1xL1FV100-A
100V Line
15
100
113
106
D1xL1FV070-A
70V Line
15
70
D1xL1FR008-A
8 Ohm
15
10.95
D1xL1FR016-A
16 Ohm
15
15.49
D1xL2FV100-A
100V Line
25
100
118
108
D1xL2FV070-A
70V Line
25
70
D1xL2FR008-A
8 Ohm
25
14.14
D1xL2FR016-A
16 Ohm
25
20
D1xL2HV100-A
100V Line
25
100
121
111
D1xL2HV070-A
70V Line
25
70
D1xL2HR008-A
8 Ohm
25
14.14
D1xL2HR016-A
16 Ohm
25
20
Frequency Range: 400Hz to 8000Hz
The table shows the input current taken by the various Loudspeakers.
Nominal current at nominal voltage.
Table 1: Electrical Ratings.
2) Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS
ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES
FROM ENCLOSURE.
EQUIPMENT MUST NOTBE INSTALLED WITH THE HORN FACING
UPWARDS OF HORIZONTAL
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS
PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING HAZARD - CLEAN
ONLY WITH A DAMP CLOTH
ATEX/IECEx & UKEx INSTALLATIONS: IF TEMPERATURE
EXCEEDS 70°C AT ENTRY OR 80°C AT BRANCHING POINT USE
SUITABLE RATED CABLE AND GLANDS
ATTENTION
ATMOSPHÈRES DANGEREUSES :
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES.
ÉQUIPEMENT NE DOIT PAS ETRE INSTALLE AVEC LE KLAXON
TOURNEE VERS LE HAUT DE HORIZONTAL.
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
ATEX/IECEx & UKEx INSTALLATIONS : SI LA TEMPÉRATURE
DÉPASSE 70 °C À L'ENTRÉE OU 80 °C AU POINT DE
BRANCHEMENT, UTILISER UN CÂBLE ET DES JOINTS
D'ÉTANCHÉITÉ APPROPRIÉS

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 2 of 6
3) Marking & Rating Information
The D1xL1 & D1xL2 Loudspeakers comply with the following
standards for hazardous locations:
3.1 Class/Division Ratings for US & Canada
Standards
UL1203 & CSA C22.2 No 30 Ed. 4
Class Division Ratings for US (NEC)
Model No:
Rating
D1xL1-V100-A/
D1xL1-V070-A/
D1xL1-R008-A/
D1xL1-R016-A
D1xL2-V100-A/
D1xL2-V070-A/
D1xL2-R008-A/
D1xL2-R016-A
Class Division Ratings for Canada (CEC)
Model No:
Rating
D1xL1-V100-A/
D1xL1-V070-A/
D1xL1-R008-A/
D1xL1-R016-A
D1xL2-V100-A/
D1xL2-V070-A/
D1xL2-R008-A/
D1xL2-R016-A
Class Zone Ratings for US (NEC)
Model No:
Rating
D1xL1-V100-A/
D1xL1-V070-A/
D1xL1-R008-A/
D1xL1-R016-A
D1xL2-V070-A/
D1xL2-R008-A/
D1xL2-R016-A
D1xL2-V100-A
Class Zone Ratings for Canada (CEC)
Model No:
Rating
D1xL1-V100-A/
D1xL1-V070-A/
D1xL1-R008-A/
D1xL1-R016-A
D1xL2-V070-A /
D1xL2-R008-A /
D1xL2-R016-A
D1xL2-V100-A
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
3.2 ATEX / IECEx & UKEx Ratings
Standards
Model No:
Rating
D1xL1-V070-A/
D1xL1-R008-A/
D1xL1-R016-A
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T86°C Db Ta 55°C to +75°C
D1xL1-V100-A
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T92°C Db Ta 55°C to +75°C
D1xL2-V070-A/
D1xL2-R008-A/
D1xL2-R016-A
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +55°C
Ex tb IIIC T91°C Db Ta 55°C to +75°C
D1xL2-V100-A
Ex db IIC T4 Gb Ta -55°C to +75°C
Ex db IIC T5 Gb Ta -55°C to +70°C
Ex db IIC T6 Gb Ta -55°C to +50°C
Ex tb IIIC T98°C Db Ta -55°C to +75°C
See Product table for electrical ratings of each unit model
Certificate No.
DEMKO 19ATEX2141X
IECEx ULD 19.0008X
UKEx UL UL21UKEX2132X
Epsilon x
Equipment Group
and Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 3 of 6
4) Zones, Gas Group, Category and Temperature
Classification
The units can be installed in locations with the following conditions:
Area Classification Gas
Zone 1
Explosive gas air mixture likely to occur in normal
operation.
Zone 2
Explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist for
a short time.
Gas Groupings
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1
450oC
T2
300oC
T3
200oC
T4
135oC
T5
100ºC (D1xL2-V100-A up to 70°C ambient)
T6
85ºC (D1xL1 up to 60°C ambient, D1xL2 up to 55°C
ambient)
Area Classification Dust
Zone 21
Explosive dust air mixture likely to occur in normal
operation.
Zone 22
Explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only exist for
a short time.
Dust Groupings
Group IIIA
Combustible Dusts
Group IIIB
Non-Conductive Dusts
Group IIIC
Conductive Dusts
Equipment Category
2G, 2D
Equipment Protection Level
Gb, Gc, Db, Dc
Maximum Surface Temperature for Dust Applications
86°C (D1xL1-V070-A, D1xL1-R008-A, D1xL1-R016-A)
92°C (D1xL1-V100-A)
91°C (D1xL2-V070-A, D1xL2-R008-A, D1xL2-R016-A)
98°C (D1xL2-V100-A)
Ambient Temperature Range
-55°C to +75°C (-67°F to +167°F)
IP Rating
IP66 to EN60529
4 / 4X / 3R / 13 to UL50E / NEMA250
5) Specific Conditions of Installation
ATEx/IECEx & UKEx Installations:
The cable entries have two M20 x 1.5 6H entry thread and a
installation is made using cable
glands, only suitably rated ATEx/IECEx or UKEx certified cable
glands must be used. They must be suitable for the type of
cable being used and also meet the requirements of the
current installation standards EN 60079-14 / IEC60079-14.
If the installation is made using conduit, openings must have a
sealing fitting connected as close as practical to the wall of the
enclosure, but in no case more than the size of the conduit or
50mm, whichever is the lesser.
Any unused cable entries must be closed with suitably rated
ATEx/IECEx or UKEx certified blanking plugs.
NEC / CEC Installations:
The cable entries have two M20 x 1.5 6H entry thread and a
glands, only suitably rated and certified cable glands must be
used. They must be suitable for the type of cable being used
and also meet the requirements of the current installation
standards for NEC and CEC.
If the installation is made using conduit, openings must have a
Any unused cable entries must be closed with suitably rated
and certified blanking plugs.
Class Zone Installation only:
For high ambient temperatures the cable entry temperature
may exceed 60ºC or the cable branching point temperature
may exceed 60ºC and therefore suitable heat resisting
cables and cable glands must be used, with a rated service
temperature at least as stated below:
All Installations:
The plastic horn is not anti-static and the metallic enclosure
has a non-conductive coating. These may generate an ignition-
capable level of electrostatic charges under certain extreme
conditions. The user should ensure that the equipment is not
installed in a location where it may be subjected to external
conditions that might cause a build-up of electrostatic charges
on non-conducting surfaces.
Max Ambient Temp (°C)
45
50
55
60
65
70
75
D1xL1-V070-A, D1xL1-V100-A,
D1xL1-R008-A, D1xL1-R016-A,
Min. Rating (°C)
70
75
80
85
90
95
100
D1xL2-V070-A, D1xL2-V100-A,
D1xL2-R008-A, D1xL2-R016-A,
Min. Rating (°C)
70
75
80
85
90
95
Table 2a: ATEx / IECEx & UKEx Min. Ratings of Cables & Cable Glands.
Max Ambient Temp (°C)
35
40
45
50
55
60
65
70
75
D1xL1-V070-A, D1xL1-V100-A,
D1xL1-R008-A, D1xL1-R016-A,
Min. Rating (°C)
60
65
70
75
80
85
90
95
D1xL2-V070-A, D1xL2-V100-A,
D1xL2-R008-A, D1xL2-R016-A,
Min. Rating (°C)
60
65
70
75
80
85
90
95
100
Table 2b: Class Zone Min. Ratings of Cables & Cable Glands.

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 4 of 6
(Appropriate
cable glands to
be customer
supplied)
Flameproof
Cover
M4 Grub
Screw
6) Specific Conditions for Safe Use
Flameproof threaded joints and cemented joints are not permitted to
be repaired.
7) Product Mounting and Access
7.1 Mounting
Fig 1: Mounting Locations
7.2 Installation procedure
a. Secure the D1x unit to a flat surface via the three 7mm
fixing holes in the mounting bracket.
b. Remove the explosionproof cover of the alarm horn by
unscrewing it, taking care not to damage the
explosionproof threads in the process (Refer to section
7.4).
c. Fit an M20/NPT suitably rated cable gland or conduit entry
into the hole in the enclosure and connect the field wiring
to the appropriate terminals as shown in D190-06-201.
The power supply terminals are duplicated so that units
may be connected in parallel. An end of line monitoring
resistor may be fitted to units (see section 10). If the
second and third M20/NPT entries are not used, suitably
rated stopping plugs must always be fitted.
d. Replace the explosionproof cover of the loudspeaker,
taking care not to damage the explosionproof threads.
Tighten fully.
7.3 Hornless Variants
7.4 Access to the Explosionproof Enclosure
Fig 2: Accessing the enclosure
On completion of the installation the flameproof threaded joint should
be inspected to ensure that they are clean and that they have not
been damaged during installation.
Ensure the O-ring seal is in place and undamaged.
When fitting the flameproof cover ensure the thread is engaged
correctly. Fully tighten the cover all the way, ensure no gap is visible
between the cover and base of the sounder enclosure.
D1xS1F
D1xS2F
D1xS2H

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 5 of 6
8) Installation Requirements
8.1 Safe Installation Requirements
Warning High voltage may be present,
risk of electric shock.
DO NOT open when energised,
disconnect power before opening.
The sounder must only be installed by suitably qualified personnel in
accordance with the latest issues of the relevant standards.
8.2 Cable Selection and Connections
When selectingthe cable size,consideration must be given to the input
current that each unit draws (see table 1), the number of sounders on
the line and the length of the cable runs. The cable size selected must
have the necessary capacity to provide the input current to all the
sounders connected to the line.
A single wire with a cross sectional area of up to 2.5mm²/ AWG14 can
be connected to each terminal way or if an input and output wire is
required two wires can be connected to each terminal way when
crimped with a ferrule. If more than one wire is fitted into a terminal a
ferrule should be used to secure the wires. When connecting wires to
the terminals greatcare should be taken to dress the wire so that when
the cover is inserted into the chamber the wires do not exert excess
pressure on the terminal blocks.
D1xL2 and D1xL1 8 ohm and 16 ohm low impedance loudspeakers
have dual input terminals on the PCB assembly for input and output
wiring. A cable of up to 4.0mm² can be connected to each terminal.
Wire insulation needs to be stripped 8mm. Wires may be fitted
securely with crimped ferrules. Terminal screws need to be tightened
down with a tightening torque of 0.45 Nm / 3.5 Lb-in.
Line In: 0.2 - 2.5mm2/ AWG24 - AWG14
Low Impedance: 0.2 - 4mm2/ AWG24 - AWG12
Figure 3: Wire Preparation.
When connecting wires to the terminals great care should be taken to
dress the wires so that when the cover is inserted into the chamber
the wires do not exert excess pressure on the terminal blocks. This is
particularly important when using cables with large cross-sectional
areas such as 2.5mm².
8.3 Earthing
Figure 4: Earth Locations.
8.4 Cable Glands, Blanking Elements & Adapters
Ingress Protection
Adapters
The D1x Loudspeaker range can be supplied with the following types
of adapters:
M20 to M25
It is important to note that stopping plugs cannot be fitted onto
adapters, only directly onto the M20 entries.
Any other adapters used must be suitably rated and certified.
9) Wiring
The cable connections are made into the terminal blocks on the PCB
assembly located in the explosionproof enclosure. See section 7.4 of
this manual for access to the explosionproof enclosure.
Refer to Wiring Schematic D190-06-201 Configs. 1a -2c for Line in
Loudspeakers and Config. 3 for Low impedance wiring details.
Internal Earth
Marked with G
External Earth
8mm

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-201-IS
Issue 1
16-03-2022
Sheet 6 of 6
10) End of Line Monitoring (DC Units)
On D1xL2 and D1xL1 Loudspeakers, DC line monitoring can be used
if required. Both the Line In units and the Low Impedance units have
blocking capacitors fitted. It should be noted that each loudspeaker
has a 1M ohm bleed resistor connected across the blocking capacitor
and this should be taken into account when selecting the value of the
end of line monitoring resistance.
The end of line monitoring resistor can be connected across the
terminals on the end of line unit.
On Line in units the end of line resistor used must have a minimum
resistance value of 4k7 ohms and a minimum wattage of 2.5 watts
On low impedance units the end of line resistor used must have a
minimum resistance value of 2k ohms and a minimum wattage of 0.5
watts or a minimum resistance value of 500 ohms and a minimum
wattage of 2 watts. On the low impedance units care must be taken
with the polarity of the monitoring voltage. If an end of line resistor is
fitted to a unit the links on the printed circuit boards of all loudspeakers
in the line must be cut for the dc blocking capacitors to be in circuit in
order to dc monitor the line (see Fig 5).
Fig. 5 Low Impedance Line Monitoring Link
11) Maintenance, Overhaul and Repair
Maintenance, repair and overhaul of the equipment should only be
carried out by suitably qualified personnel in accordance with the
current relevant standards:
For ATEx/IECEx or UKEx:
EN60079-19/IEC60079-19
Explosive atmospheres Equipment repair, overhaul and
reclamation
EN 60079-17/IEC60079-17
Explosive atmospheres Electrical installations inspection
and maintenance
Units must not be opened while an explosive atmosphere is present.
If opening the unit during maintenance operations, a clean
environment must be maintained and any dust layer removed prior to
opening the unit.
Potential electrostatic charging hazard Clean only with a damp
cloth.
DC Line
Monitoring Link

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-201
D.HOWGILL
R.N.POTTS
R.N.POTTS
18/11/20
OF
NTS 13
AINTRODUCTION
D.H 18/11/20
18/11/20
18/11/20
D1xL1 & D1xL2 LINE IN & LOW IMPEDANCE
LOUDSPEAKER WIRING DIAGRAMS
D1xL1
D1xL2
1INTRODUCTION
RSR 16/03/22
-ve
-ve
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
D1xL1V070 & D1xL1V100 Line in Config.: 1a
Optional Line Monitoring
15W: Apply Signal to Common & 15W
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
4K7Ω MIN, 2.5W MIN
MINIMUM VALUE:
R1
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
D1xL1V070 & D1xL1V100 Line in Config.: 1b
Optional Line Monitoring
7.5W: Apply Signal to Common & 7.5W
D1xL1V070 & D1xL1V100 Line in Config.: 1c
Optional Line Monitoring
3W: Apply Signal to Common & 3W
D1xL1V070 & D1xL1V100 Line in Config.: 1d
Optional Line Monitoring
1W: Apply Signal to Common & 1W
+ve
+ve
-ve
-ve
-ve
-ve
-ve
-ve
+ve
+ve
+ve
+ve
+ve
+ve

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-201
D.HOWGILL
R.N.POTTS
R.N.POTTS
18/11/20
OF
NTS 2 3
18/11/20
18/11/20
D1xL1 & D1xL2 LINE IN & LOW IMPEDANCE
LOUDSPEAKER WIRING DIAGRAMS
D1xL1
D1xL2
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
D1xL2V070 & D1xL2V100 Line in Config.: 2a
Optional Line Monitoring
25W: Apply Signal to Common & 25W
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
4K7Ω MIN, 2.5W MIN
MINIMUM VALUE:
R1
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
COM 15W 7.5W 3W 1W
25W 12.5W 6W 2W
R1
D1xL2V070 & D1xL2V100 Line in Config.: 2b
Optional Line Monitoring
12.5W: Apply Signal to Common & 12.5W
D1xL2V070 & D1xL2V100 Line in Config.: 2c
Optional Line Monitoring
6W: Apply Signal to Common & 6W
D1xL2V070 & D1xL2V100 Line in Config.: 2d
Optional Line Monitoring
2W: Apply Signal to Common & 2W
ASEE SHEET 1
D.H 18/11/20
1SEE SHEET 1
RSR 16/03/22
-ve
-ve
-ve
-ve
-ve
-ve
-ve
-ve
+ve
+ve
+ve
+ve
+ve
+ve
+ve
+ve

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-201
D.HOWGILL
R.N.POTTS
R.N.POTTS
18/11/20
OF
NTS 3 3
ASEE SHEET 1
D.H 18/11/20
18/11/20
18/11/20
D1xL1 & D1xL2 LINE IN & LOW IMPEDANCE
LOUDSPEAKER WIRING DIAGRAMS
D1xL1
D1xL2
1SEE SHEET 1
RSR 16/03/22
D1xL1R008, D1xL1R016, D1xL2R008, D1xL2R016 Config.: 3
Low Impedance
Optional Line Monitoring
Apply Signal to +ve & -ve
-ve
-ve
+ve
+ve
R1
-
-
+
+
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
500Ω MIN, 2W MIN OR 2KΩ MIN, 0.5W MIN
MINIMUM VALUES:
R1
For DC Line
Monitoring Cut Link

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐067_Issue_H(D1x).docx‐Page1of2‐QAF_252_Issue_5
EUDeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
AuthorisedRepresentative:E2SWarnsignaltechnikUG
Charlottenstrasse45‐51
72764Reutlingen
Germany
EquipmentType: D1xS1,D1xS2
D1xL1,D1xL2
D1xC1X05,D1xC1X10,D1xC2X05,D1xC2X10
D1xB2XH1,D1xB2XH2
Directive2014/34/EU:EquipmentandProtectiveSystemsforuseinPotentiallyExplosiveAtmospheres(ATEX)‐D1xS1,D1xS2,D1xL1,D1xL2,D1xC1X05,D1xC1X10,
D1xC2X05andD1xC2X10only
NotifiedBodyforEUtypeExamination(ModuleB):ULInternationalDemkoA/S
Borupvang5A
2750Ballerup
Denmark
EU‐typeExaminationCertificate(ModuleB):DEMKO19ATEX2141X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:2813
Unit6,HawardenIndustrialPark,Hawarden,Deeside,CH53US,UK
QualityAssuranceNotification(ModuleD):SIRA05ATEXM342
Provisionsfulfilledbytheequipment:II2GExdbIICT6…T3GB
II2DExtbIIICT82C…145CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2014/35/EU:LowVoltageDirective(LVD)
Standardsapplied:EN60947‐1:2007+A2:2014
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1992+A2:2013‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐067_Issue_H(D1x).docx‐Page2of2‐QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐067_Issue_H
QualityAssuranceManagerDateandPlaceofIssue:London,10/02/2022
EUDeclarationofConformity
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐097_Issue_A(D1xUKCA).docx‐Page1of2‐
QAF_252_Issue_5
UKCADeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
EquipmentType: D1xS1,D1xS2
D1xL1,D1xL2
D1xC1X05,D1xC1X10,D1xC2X05,D1xC2X10
DirectiveUKSI2016:1107(asamendedbyUKSI2019:696)–Schedule3A,Part1:ProductorProtectiveSystemIntendedforuseinPotentiallyExplosiveAtmospheres
(UKCA)
NotifiedBodyforUKtypeExamination(ModuleB):ULInternational(UK)Ltd
NotifiedBodyNo.:0843
Unit1‐3HorizonKingslandBusinessPark,WadeRoad,
Basingstoke,HampshireRG248AHUK
UK‐typeExaminationCertificate(ModuleB):UL21UKEX2132X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:0518
RakeLane,Eccleston,ChesterCH49JN,UK
QualityAssuranceNotification(ModuleD):CSAE22UKQAN0046
Provisionsfulfilledbytheequipment:II2GExdbIICT6…T3GB
II2DExtbIIICT82C…145CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2014/35/EU:LowVoltageDirective(LVD)
Standardsapplied:EN60947‐1:2007+A2:2014
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1992+A2:2013‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐097_Issue_A(D1xUKCA).docx‐Page2of2‐
QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐097_Issue_A
QualityAssuranceManagerDateandPlaceofIssue:London,24/02/2022
UKCADeclarationofConformity
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

Page left Intentionally blank
This manual suits for next models
11
Table of contents
Other E2S Speakers manuals