E2S E2xL15R User manual

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D209-00-101-IS-SC Issue C20-01-21 Sheet 1 of 6
INSTRUCTION MANUAL
E2xL15R, E2xL15F, E2xL25R, E2xL25F Loudspeakers
For use in Hazardous Locations
1) Warnings
•DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
•DO NOT OPEN WHEN ENERGISED
•POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
•HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
Avertissement:
•NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
•NE PAS OUVRIR ENERGIE
•DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
•HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
2) Rating & Marking Information
2.1 ATEX / IECEx certification
The E2xL15 and E2xL25 loudspeakers comply with the
following standards:
EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06)
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
Certificate No. DEMKO 06ATEX 0421554X
IECEx ULD 14.0012X
The E2xL15 loudspeaker is rated as follows:
The E2xL25 loudspeaker is rated as follows:
CE Marking
Zones, Gas / Dust Groups and Temperature
Classification
When connected to an approved system the E2X alarm horn
may be installed in:
Zone 2 explosive gas air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
Zone 22 explosive dust air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
May be used with gases in groups:
Group IIA propane
Group IIB ethylene
Group IIC hydrogen / acetylene
Having a temperature classification
(for Gas applications) of:
T1 450ºC
T2 300ºC
T3 200ºC (E2xL15 only)
T4 135ºC (E2xL15 only)
May be used with Dust types:
Group IIIA combustible flyings
Group IIIB non-conductive dust
Group IIIC conductive dust
Maximum Surface Temperature for Dust Applications:
100ºC
85ºC (E2xL25 only up to 40ºC ambient)
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –
Classification of areas. Explosive dust atmospheres
E2xL15R / E2XL25R E2xL15F E2xL25R
2813
II 3G Ex nA IIC T4 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC T85°C Dc Ta -20°C to +55°C
II 3G Ex nA IIC T2 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC 85°C Dc Ta -20°C to +40°C
II 3D Ex tc IIIC 100°C Dc Ta -20°C to +55°C

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D209-00-101-IS-SC Issue C20-01-21 Sheet 2 of 5
2.2 NEC Class / Zone ratings US
The E2xL15 and E2xL25 loudspeakers comply with the
following standards:
UL 60079-0-2013
UL 60079-15-2013
UL 60079-31-2015
The E2xL15 loudspeaker is rated as follows:
Class I Zone 2 AEx nA IIC T4 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC T85°C Dc Ta -20°C to +55°C
The E2xL25 loudspeaker is rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC 85°C Dc Ta -20°C to +40°C
Zone 22 AEx tc IIIC 100°C Dc Ta -20°C to +55°C
Installation must be carried out in compliance with the
National Electric Code.
2.3 CEC Class / Zone ratings Canada
The E2xL15 and E2xL25 loudspeakers comply with the
following standards:
CAN/CSA C22.2 No. 60079-0:2015
CAN/CSA C22.2 No. 60079-15:2016
CAN/CSA C22.2 No. 60079-31:2015
The E2xL15 loudspeaker is rated as follows:
Ex nA IIC T4 Gc Ta -20°C to +55°C
Ex tc IIIC T85°C Dc Ta -20°C to +55°C
The E2xL25 loudspeaker is rated as follows:
Ex nA IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 85°C Dc Ta -20°C to +40°C
Ex tc IIIC 100°C Dc Ta -20°C to +55°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.4 NEC & CEC Class / Division Ratings for US / Canada
The E2xL15 and E2xL25 loudspeakers comply with the
following standards:
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The E2xL15 loudspeaker is rated as follows:
Class I, Div 2, ABCD T3C Ta -20°C to +55°C
Class I, Div 2, ABCD T4 Ta -20°C to +40°C
Class II, Div 2, FG T6 Ta -20°C to +55°C
Class III T6 Ta -20°C to +55°C
The E2xL25 loudspeaker is rated as follows:
Class I, Div 2, ABCD T2C Ta -20°C to +55°C
Class I, Div 2, ABCD T2D Ta -20°C to +40°C
Class II, Div 2, FG T5 Ta -20°C to +55°C
Class II, Div 2, FG T6 Ta -20°C to +40°C
Class III, Div 1&2 Ta -20°C to +55°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.5 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating per EN60079-0: IP64
IP rating per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 13
To maintain the ingress protection rating, the two off cable
entries must be fitted with suitably rated, certified cable entry
and/or blanking devices during installation.
2.6 Electrical Ratings
3) Special Conditions of Use
When used for a Group III application, the surface of the
enclosure may store electrostatic charge and become a
source of ignition in applications with a low relative humidity
<~30% relative humidity where the surface is relatively free of
surface contamination such as dirt, dust, or oil.
Guidance on protection against the risk of ignition due to
electrostatic discharge can be found in EN TR50404 and IEC
TR60079-32.
End user shall adhere to the manufacturer’s installation and
instruction when performing housekeeping to avoid the
potential for hazardous electrostatic charges during cleaning,
by using a damp cloth.
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated,
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the enclosure.
Equipment with the flare horn shall not be installed with the
flare higher than horizontal (to avoid accumulation of dust).
The equipment incorporates metal parts isolated from earth,
having capacitance values exceeding the limits permitted in
the standards of certification. Mounting bracket – 10.33pF.
Model No. Input Wattage Max. I/P Volts
E2xL15FV070 /
E2xL15RV070
70V Line 15 70
E2xL25FV070 /
E2xL25RV070
70V Line 25 70
E2xL15FV100 /
E2xL15RV100
100V Line 15 100
E2xL25FV100 /
E2xL25RV100
100V Line 25 100
E2xL15FR008 /
E2xL15RR008 /
8 Ohm 15 10.95
E2xL25FR008 /
E2xL25RR008 /
8 Ohm 25 14.14
E2xL15FR016 /
E2xL15RR016 /
16 Ohm 15 15.49
E2xL25FR016 /
E2xL25RR016 /
16 Ohm 25 20

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D209-00-101-IS-SC Issue C20-01-21 Sheet 3 of 5
4) Location and Mounting
The location of the loudspeaker should be made with due
regard to the area over which the warning signal must be
audible. They should only be fixed to services that can carry
the weight of the unit.
The E2x loudspeaker should be secured to any flat surface
using the three 7mm fixing holes on the stainless steel U
shaped mounting bracket. See Figure 1. The required angle
can be achieved by loosening the two large bracket screws in
the side of the unit, which allow adjustment of the
loudspeaker in steps of 18°. On completion of the installation
the two large bracket adjustment screws on the side of the
unit must be fully tightened to ensure that the unit cannot
move in service.
Fig. 1 Fixing Location for Loudspeaker L25 Flare
Fig. 1 Fixing Location for Loudspeaker L15 Flare
Fig. 1 Fixing Location for Loudspeaker Radial
5) Access to the Enclosure
To access the enclosure, remove the four M4 posi pan head
screws, M4 spring and plain washers and withdraw the cover.
Fig. 2 Accessing the Enclosure.
To replace cover, check that the ‘O’ ring seal is in place.
Carefully push the cover in place. Insert and tighten down M4
screws, spring and plain washers in the order shown above
and tighten down.
6) Selection of Cable. Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given
to the input current that each unit draws (see Table 1), the
number of sounders on the line and the length of the cable
runs. The cable size selected must have the necessary
capacity to provide the input current to all of the sounders
connected to the line.
The dual entries can be ordered with one of the following
options:
2-off M20 x 1.5 thread
2-off ½” NPT thread
1-off M20 x 1.5 & 1-off ½” NPT thread
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated,
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the enclosure.
For ambient temperatures over +40ºC the cable entry
temperature may exceed +70ºC or the cable branching
temperature may exceed +80ºC. Therefore suitable heat
resisting cables and cable glands must be used as per table
below
Ambient Temp.
40ºC
45ºC
50ºC
55ºC
Min. Rating of cables
and cable glands
90ºC 95ºC 100ºC 105ºC
Warning –Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Warning – High voltage may be present,
risk of electric shock. DO NOT open when
energised, disconnect power before
opening.
(Appropriate cable entry devices
to be customer supplied)
Cover
M4 Cover
Screw
M4 Spring
Washer
M4 Plain
Washer

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D209-00-101-IS-SC Issue C20-01-21 Sheet 4 of 5
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
7) Cable Connections
Electrical connections are to be made into the terminal blocks
on the PCBA located in the enclosure. See section 5 of this
manual for access to the enclosure.
Wires having a cross sectional area between 0.5 mm² to
2.5mm² can be connected to each terminal way. If an input
and output wire is required the 2-off Live/Neutral or +/-
terminals can be used. If fitting 2-off wires to one terminal
way the sum of the 2-off wires must be a maximum cross
sectional area of 2.5mm². Strip wires to 8mm. Wires may also
be fitted using ferrules. Terminal screws need to be tightened
down with a tightening torque of 0.45 Nm / 4 Lb-in. When
connecting wires to the terminals great care should be taken
to dress the wires so that when the cover is inserted into the
chamber the wires do not exert excess pressure on the
terminal blocks. This is particularly important when using
cables with large cross sectional areas such as 2.5mm².
8) Line In Wiring
A 10-way terminal block is provided on the Line in
loudspeakers. There are 2-off Common, 2-off 15W/25W, 2-off
7.5W/12.5W, 2-off 3W/6W, 2-off 1W/2W and 2-off Earth
terminals in total.
8.1 L15 Wiring Diagrams
Fig. 3 L15 Line in Diagram
Fig. 4 L15 Line in Terminals
8.2 L25 Wiring Diagrams
Fig. 5 L25 Line in Diagram
Fig. 6 L25 Line in Terminals
8.3 Line Monitoring (Line in Units Only)
On E2xL15 & E2xL25 loudspeakers, DC line monitoring can
be used if required. All Line in Loudspeakers have a blocking
diode fitted in their supply input lines. It should be noted that
each loudspeaker has a 1M ohm bleed resistor connected
across the blocking capacitor and this should be taken into
account when selecting the value of the end of line
monitoring resistance. The end of line monitoring resistor can
be connected across the terminals on the end of line unit. If
an end of line resistor is used it must have the following
values:
70V Line in Loudspeaker:
Minimum resistance 3K9 Ohms Minimum Power 0.5W
Minimum resistance 1K Ohms Minimum Power 2.0W
100V Line in Loudspeaker:
Minimum resistance 15K Ohms Minimum Power 0.5W
Minimum resistance 3K9 Ohms Minimum Power 2.0W
The resistor must be connected directly across the terminals.
Whilst keeping its leads as short as possible, a spacing of at
least 1/16” (1.58mm) must be provided through air and over
surfaces between uninsulated live parts.
1W 3W 7.5W 15W C
2W 6W 12.5W 25W C

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D209-00-101-IS-SC Issue C20-01-21 Sheet 5 of 5
15W COM
25W COM
9) Low Impedance Wiring
9.1 L15 Wiring Diagrams
A 4-way terminal block is provided on the Low Impedance
Loudspeakers. There are 2-off Common and 2-off 15W/25W
terminals in total.
Fig. 7 L15 Low impedance Diagram
Fig. 8 L15 Low Impedance Terminals
9.2 L25 Wiring Diagrams
Fig. 9 L25 low Impedance Diagram
Fig. 10 L25 Low Impedance Terminals
10) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19
IEC60079-19
Explosive atmospheres - Equipment repair,
overhaul and reclamation
EN 60079-17
IEC60079-17
Explosive atmospheres - Electrical
installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.