Hazardous Voltage
Will cause severe injury or death
Working on or near energized circuits
poses a serious risk of electrical shock.
De-energize all circuits before installing
or servicing this equipment and follow
all prescribed safety procedures
YEAR
WARRANTY
Warranty
See document No. 3A1502 at
www.cooperbussmann.com/surge
for limited warranty details.
Indoor use only
35mm
DIN-Rail
90mm L x 36mm W x 73mm H
Torque 4 N•m
System installation
Class II IEC 61643-11...
Type 2 EN 61643-11...
There is no distance required
from the SPD to any earthed
conductive surface.
Module replacement
Green =
Good
Red =
Replace
Visual indication status
Green
Green =
Good
RedRed =
Replace
Remote contact signaling
(modules installed)
Mounting
Green
Remove/test
Remote OK
Testing contact signaling
(modules removed)
IEC 61643-11 Class II, two-pole SPDs for
TN and TT 230/400V IEC applications
BSPM2275TN(R) and BSPH2275TT(R)
Fusing
Conductors
Remote contact signaling
System type TN TT
L-N N-PE
Voltage UNTol: 0V...UC230/400V 230/400V
Voltage UC
[L N] 275V~ 275V~
[N PE] 275V~ 255V~
fN50/60Hz
Ifi —100Arms
Max. fuse 125A gG
ISCCR 50kArms —
Imax 40kA
Operating environment -40°C to +80°C, 5%-95% RH
IPE <0.15mA <5µA
Types: W/O remote BSPM2275TN BSPH2275TT
W/ remote BSPM2275TNR BSPH2275TTR
Replacement
modules
[L N] — BPM275IEC —
[L PE] BPM275IEC —
[N PE] BPM275IEC — BPSNPEIEC
Ports 1
IP rating IP20 built-in
L x W x H 90mm x 36mm x 73mm
Fusing and minimum
conductors
F1 A gG S2/mm2S3/mm2F2 A gG
25 4 6 —
35 4 6 —
40 4 6 —
50 6 6 —
63 10 10 —
80 10 10 —
100 16 16 —
125 16 16 —
>125 16 16 125
Wiring
TN (-C) -S connection TT connection
**
S3
S2
* Module BPM275IEC
***
S3
S2
* Module BPM275IEC
** Module BPSNPEIEC