Eaton TC 48 User manual

RR
www.comoso.com

The Symbol calls attention to an operating procedure, practice, or the
like, which, if not correctly performed or adhered to, could result in
personal injury or damage to or destruction of part or all of the
product and system. Do not proceed beyond a warning symbol until
the indicated conditions are fully understood and met.
Installers
System Designer
Expert User
Read Chapter 1, 2
Read All Chapters
Read Page 12
NOTE:NOTE:
It is stronglyrecommended that aprocess should
incorporate a LIMITCONTROL likeL91 which willshut down
the equipment ata preset processcondition in orderto
preclude possible damageto products orsystem.
Some programming parametersshown in thismanual may not
be available oncurrently offered models.
It is stronglyrecommended that aprocess should
incorporate a LIMITCONTROL likeL91 which willshut down
the equipment ata preset processcondition in orderto
preclude possible damageto products orsystem.
Some programming parametersshown in thismanual may not
be available oncurrently offered models.
Information in this user's manual is subject to change without
Copyright September 2007, Eaton Corporation, all rights reserved.
No part of this publication may be reproduced, transmitted,
transcribed or stored in a retrieval system, or translated into any
language in any form by any means without the written permission
of Eaton Corporation.
2
This manual isapplicable for theproducts with software
version 23 andlater version.
This manual isapplicable for theproducts with software
version 23 andlater version.
www.comoso.com

3
ContentsContents
Chapter 1 OverviewChapter 1 Overview
1-1 General -------------------------5
1-2 Ordering Code ---------------8
1-3 Keys and Displays ---------9
1-4 Menu Overview -------------11
1-5 Parameter Descriptions ---12
Page No
Chapter 2 InstallationChapter 2 Installation
2-1 Unpaking ----------------------19
2-2 Mounting ----------------------19
2-3 Wiring precautions ----------21
2-4 Power Wiring -----------------24
2-5 Sensor Installation
Guidlines----------------------24
2-6 Sensor Input Wiring ---------25
2-7 Control Output Wiring ------25
2-8 Alarm Wiring -----------------27
Chapter 3 ProgrammingChapter 3 Programming
3-1 Lockout ------------------------28
3-2 Signal Input -------------------28
3-3 Control Outputs --------------29
3-4 Alarm ---------------------------34
3-5 Configure User Menu -------35
3-6 Ramp ---------------------------36
3-7 Dwell Timer -------------------37
3-8 PV Shift ------------------------38
3-9 Digital Filter -------------------39
3-10 Failure Transfer -------------40
3-11 Auto-tuning ------------------41
3-12 Manual tuning ---------------42
3-13 Manual Control -------------43
Chapter 4ApplicationsChapter 4Applications
Chapter 5 Calibration --------47Chapter 5 Calibration
Chapter 6 Specifications ----48Chapter 6 Specifications
Page No
4-1 Heat Only Control with
Dwell Timer ------------------45
4-2 Cool Only Control ------------46
AppendixAppendix
A-1 Error Codes ------------------54
A-2 Warranty ----------------------55
www.comoso.com

Figures &TablesFigures &Tables Page No
Figure 1.1 Fuzzy Control Advantage ----------------------------------------------------------------6
Figure 1.2 Front Panel Description -----------------------------------------------------------------10
Figure 1.3 Display of Initial Stage -------------------------------------------------------------------10
Figure 2.1 Mounting Dimensions -------------------------------------------------------------------20
Figure 2.2 Lead Termination for TC 96---------------------------------------------22
Figure 2.3 Lead Termination for TC 48-------------------------------------------------------------22
Figure 2.4 Rear Terminal Connection for TC 96------------------------------------------------22
Figure 2.5 Rear Terminal Connection for TC 48------------------------------------------------23
Figure 2.6 Power Supply Connections ------------------------------------------------------------24
Figure 2.7 Sensor Input Wiring ----------------------------------------------------------------------25
Figure 2.8 Output 1 Relay or to Drive Load---------------------------------------------------25
Figure 2.9 Output 1 Relay or to Drive Contactor---------------------------------------------26
Figure 2.10 Output 1 Pulsed Voltage to Drive SSR----------------------------------------------26
Figure 2.11 Output 1 Linear Current ---------------------------------------------------------------27
Figure 2.12 Alarm Output to Drive Load ----------------------------------------------------------27
Figure 2.13 Alarm Output to Drive Contactor ----------------------------------------------------27
Figure 3.1 Conversion Curve for Linear Type Process Value ---------------------------------29
Figure 3.2 Heat Only ON-OFF Control ------------------------------------------------------------30
Figure 3.3 Output 2 Deviation High Alarm --------------------------------------------------------33
Figure 3.4 Output 2 Process Low Alarm ----------------------------------------------------------33
Figure 3.5 RAMP Function ---------------------------------------------------------------------------36
Figure 3.6 Dwell Timer Function --------------------------------------------------------------------37
Figure 3.7 PV Shift Application ----------------------------------------------------------------------38
Figure 3.8 Filter Characteristics ---------------------------------------------------------------------39
Figure 3.9 Effects of PID Adjustment -------------------------------------------------------------44
Figure 4.1 Heat Control Example -------------------------------------------------------------------45
Figure 4.2 Cooling Control Example ---------------------------------------------------------------46
Table 1.1 Display Form of Characters ------------------------------------------------------------10
Table 3.1 Heat-Cool Control Setup Value ---------------------------------------------------------29
Table 3.2 PIDAdjustment Guide --------------------------------------------------------------------43
Table A.1 Error Codes and Corrective Actions --------------------------------------------------54
4
www.comoso.com

Chapter 1OverviewChapter 1Overview
1-1 General1-1 General
The Fuzzy Logic plus PID microprocessor-based controller series,
incorporate two bright, easy to read 4-digit LED displays,indicating
process value and set point value. The FuzzyLogic technology
enables a process to reach a predetermined set point in the
shortest time, with the minimum of overshoot duringpower-up or
external load disturbance.
The TC48 is a 1/16 DIN size panelmount controller. The TC96 is a
1/8 DIN size panel mount controller. These units are powered by
11-26 or 90-250 VDC /VAC supply, incorporating a 2 amp control
relay output as standard. The units are fullyprogrammable for
PT100 and thermocouple types J,K, T, E, B, R, S, N, Lwith no need
to modify the unit. The input signal isdigitized by using a 18-bit
A to D converter. Its fast sampling rate allows the unit tocontrol
fast processes.
By using proprietary Fuzzy modified PID technology, the control
loop will minimize the overshoot and undershoot in a shortest
time. The following diagram is a comparisonof results with and
without Fuzzy technology.
5
www.comoso.com

6
PID control when properly tuned
PID + Fuzzy control
Warm Up Load Disturbance
Set
point
Temperature
Time
High AccuracyHigh Accuracy
The series are manufactured with custom designedASIC(Application
Specific Integrated Circuit ) technology which contains a 18-bitA to
D converter for high resolution measurement ( true 0.1 F resolution
for thermocouple and PT100 ) and a 15-bit Dto Aconverter for linear
current or voltage control output. TheASIC technology provides
improved operating performance, low cost, enhanced reliability and
higher density.
°
Fast Sampling RateFast Sampling Rate
The sampling rate of the input Ato D converter reaches 5 times/second.
The fast sampling rate allows this series to control fast processes.
Fuzzy ControlFuzzy Control
The function of Fuzzy control is to adjust PID parameters from time to
time in order to make manipulation output value more flexible and
adaptive to various processes. The results is to enable a process to
reach a predetermined set point in the shortest time, with the minimum
of overshoot and undershoot during power-up or external load
disturbance.
Figure 1.1
Fuzzy Control
Advantage
Figure 1.1
Fuzzy Control
Advantage
www.comoso.com

Auto-tuneAuto-tune
The auto-tune function allows the user to simplifyinitial setup for a
new system. Aclever algorithm is provided to obtain an optimal set
of control parameters for the process, and itcan be applied either as
the process is warming up ( cold start )or as the process has been
in steady state ( warm start ).
Lockout ProtectionLockout Protection
According to actual security requirement, one of four lockoutlevels
can be selected to prevent the unit from beingchanged by
unauthorized personnel.
Bumpless TransferBumpless Transfer
Bumpless transfer allows the controller to continue to control by
using its previous value as the sensor breaks. Hence, theprocess
can be controlled temporarily in open loop mode.
Soft-start RampSoft-start Ramp
The ramping function is performed during power up as well as any
time the set point is changed. It can ramp up or ramp down.
The process value will reach the set point with a predetermined
constant rate.
Digital FilterDigital Filter
A first order low pass filter with a programmable time constant is used
to improve the stability of process value. This is particularly useful in
certain applications where the process value is too unstable to be read.
SEL FunctionSEL Function
The units have the flexibility for user to select those parameters which
are most significant to him and put these parameters in the front of
display sequence. Up to 8 parameters can be selected to allow the
user to build his own display sequence.
7
www.comoso.com

8
Power InputPower Input
4: 90 - 250 VAC,
50/60 HZ
5: 11 - 26 VAC or
VDC
4: 90 - 250 VAC,
50/60 HZ
5: 11 - 26 VAC or
VDC 0: None0: None
CommunicationsCommunications
1: Standard Input
Thermocouple:
J, K, T, E, B, R,
S, N, L
RTD: PT100 DIN,
PT100 JIS
1: Standard Input
Thermocouple:
J, K, T, E, B, R,
S, N, L
RTD: PT100 DIN,
PT100 JIS
Signal InputSignal Input
1: Relay rated 2A/240VAC
2: Pulsed voltage to drive SSR,
5V/30mA
3: Isolated 4 - 20mA / 0 - 20mA
1: Relay rated 2A/240VAC
2: Pulsed voltage to drive SSR,
5V/30mA
3: Isolated 4 - 20mA / 0 - 20mA
Output 1Output 1
0: None
1: Form C relay 2A/240VAC
0: None
1: Form C relay 2A/240VAC
AlarmAlarm
TC 48-
TC 96-
TC 48-
TC 96-
0: None0: None
Output 2Output 2
1-2 Ordering Code1-2 Ordering Code
0: Panel mount IP50 standard
1: Panel mount IP65 water
resistant gasket installed
0: Panel mount IP50 standard
1: Panel mount IP65 water
resistant gasket installed
OptionsOptions
NOTE: Not all options are currently available with
all models.
www.comoso.com

1- 3 Keys and Displays1- 3 Keys and Displays
KEYPAD OPERATIONKEYPAD OPERATION
SCROLL KEY :
This key is used to select a parameter to be viewed or adjusted.
UP KEY :
This key is used to increase the value of selected parameter.
DOWN KEY :
This key is used to decrease the value of selected parameter.
RESET KEY :
This key is used to:
1. Revert the display to the process value.
2. Reset the latching alarm, once the alarm condition is
removed.
3. Stop the manual control mode, auto-tuning mode, and calibration
mode.
4. Clear communication error and auto-tuning error messages.
5. Restart the dwell timer when the dwell timer has been timed out.
6. Enter the manual control menu during failure mode occurrances.
ENTER KEY : Press for 5 seconds or longer .
Press for 5 seconds to:
1. Enter setup menu. The display shows .
2. Enter manual control mode when manual control mode
is selected.
3. Enter auto-tuning mode when auto-tuning mode is
selected.
4. Perform calibration to a selected parameter during the
calibration procedure.
Press for 6.2 seconds to select manual control mode.
Press for 7.4 seconds to select auto-tuning mode.
Press for 8.6 seconds to select calibration mode.
SCROLL KEY :
UP KEY :
DOWN KEY :
RESET KEY :
ENTER KEY :
R
9
www.comoso.com

Table1.1 Display Form ofCharactersTable1.1 Display Form ofCharacters
AEINSX
BFJOTY
CGKPUZ
cHLQV
?
DhMRW=
Figure 1.2 Front Panel DescriptionFigure 1.2 Front Panel Description
Upper Display, to display process value,
menu symbol and error code etc.
Lower Display,
to display set point value,
parameter value or
control output value etc.
4 Buttons for control setup
and set point adjustment.
Output 1
Indicator
Output 2
Indicator
Alarm
Indicator Process Unit Indicator
Manual
Mode
Indicator
Auto-tuning
Indicator
The lower display shows program no. 6
for TC 48 with version 24.
The program no. for TC 96 is 11.
.
Display program code of the product
for 2.5 seconds.
Figure 1.3
Display of InitialStage
Figure 1.3
Display of InitialStage
OP1OP1 OP2OP2 ALMALM
CCFF
MAN
AT
TC 48
R
10
OP1OP1 OP2OP2 ALMALM
CCFF
MAN
AT
TC 48
R
www.comoso.com

1- 4 Menu Overview1- 4 Menu Overview
LOCK
INPT
UNIT
DP
INLO
SP1L
INHI
SP1H
SHIF
FILT
OUT1
O1TY
O1FT
O1HY
CYC1
PB
TI
TD
OFST
RAMP
RR
OUT2
O2TY
O2FT
O2HY
CYC2
CPB
DB
ALFN
ALMD
ALHY
ALFT
COMM
ADDR
BAUD
DATA
PARI
STOP
RELO
REHI
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
SP2
SP3
INPT
UNIT
PB
DP
TI
TD
CYC1
ADDR
PV, SV
H_ _ _ ADLO
ADHI
RTDL
CJLO
RTDH
CJHI
5 sec. 6.2 sec. 7.4 sec. 9.8 sec.
User
menu
User
menu Setup
menu
Setup
menu Manual
Mode
Manual
Mode Calibration
Mode
Calibration
Mode
*2 *1
Applying these modes will break the control
loop and change some of the previous
setting data. Make sure that the system
is able to operate in these modes.
The flow chart shows a complete listing
of all parameters. For actual application
the number of available parameters
depends on setup conditions, and should
be less than that shown in the flow chart.
You can select up to 8 parameters to put
in the user menu by using SEL1~SEL8
at the bottom of setup menu.
Release , then press for 2 seconds
minimum, but not more than 3 seconds, to
enter the calibration menu.
The user menu shown in the flow chart
corresponds to the default settings for
SEL parameters SEL1 to SEL8. SP3
will be hidden if NONE is selected for
ALFN. SP2 will be hidden if alarm function
is not selected for OUT2. Unused
parameters will be hidden even if they are
selected by SEL parameters.
*1:
*2:
Press for
5 seconds to
perform calibration.
8.6 sec.
C_ _ _
Release
then press
for 5 seconds
to start
auto-tuning
mode.
Press
for 5 seconds
to start
manual control.
Auto-tuning
Mode
Auto-tuning
Mode
*3:
*3
11
www.comoso.com

1-5 Parameter Descriptions1-5 Parameter Descriptions
Parameter
Notation Default
Value
Select parameters to be
locked
0 : No parameter
is locked
1 : Setup data are
locked
2 : Setup data and
User data except Set
point are locked
3 : All data are locked
LOCK 0
Parameter Description Range
0
1
2
3
4
5
6
:
:
:
:
:
:
:
T type thermocouple
E type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
J type thermocouple
K type thermocouple
7
13
8
14
9
10
11
12
N type thermocouple
L type thermocouple
PT 100 ohms DIN
curve
PT 100 ohms JIS
curve
4 - 20 mA linear
current input
0 - 20 mA linear
current input
0 - 1V linear voltage
input
:
:
:
:
:
:
:
:0 - 60 mV linear
millivolt input
INPT Input sensor selection 1
(0)
SP2
Set point for output 2
when output 2 performs
alarm function
Low: -19999 High :45536
10.0 C
(18.0F)
SP1 Set point for output 1 Low: SP1L High :SP1H
25.0 C
(77.0 F)
SP3 Set point for alarm or
dwell timer output Low: -19999 High: 45536
10.0 C
(18.0 F)
15
16
17
0 - 5V linear voltage
input
1 - 5V linear voltage
input
0 - 10V linear voltage
input
:
:
:
12
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
UNIT Input unit selection
0
1
2
:
:
:
Degree C unit
Degree F unit
Process unit
0
(1)
DP Decimal point selection
0
1
2
3
1
:
:
:
:
No decimal
point
1 decimal digit
2 decimal digits
3 decimal digits
INLO
INHI
Input low scale value
Input high scale value
-19999
INLO+50
45486
45536
Low:
Low:
High:
High:
-17.8 C
( 0 F )
SHIF PV shift (offset) value -200.0 C
(-360.0 F) 0.0
Low: 200.0 C
( 360.0 F)
High:
High:
93.3 C
(200.0 F)
0
1
2
3
4
5
6
7
8
9
FILT Filter damping time
constant of PV
0 second time
constant
0.2 second time
constant
0.5 second time
constant
1 second time
constant
2 seconds time
constant
5 seconds time
constant
10 seconds time
constant
20 seconds time
constant
30 seconds time
constant
60 seconds time
constant
:
:
:
:
:
:
:
:
:
:
2
SP1L Low limit of set point
value -19999 High: -17.8 C
(0 F)
SP1H High limit of set point
value SP1L High: 537.8 C
(1000 F)
45536
Low:
45536
Low:
13
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
0
O1TY Output 1 signal type
: Relay output
: Solid state relay
drive output
: Solid state relay
output
: 4-20 mA current
module
0
1
2
3
4
5
6
7
0 - 20 mA current
module
0 - 1V voltage
module
0 - 5V voltage
module
1 - 5V voltage
module
80 - 10V voltage
module
:
:
:
:
:
O1FT Output 1 failure transfer
mode
Select BPLS ( bumpless
transfer ) or 0.0 ~ 100.0 % to
continue output 1 control
function if the sensor fails, or
select OFF (0) or ON (1)
for ON-OFF control.
0
O1HY Output 1 ON-OFF control
hysteresis Low: 0.1 High: 50.0 C(90.0 F) 0.1 C
(0.2 F)
CYC1 Output 1 cycle time Low: 0.1 High: 90.0 sec. 18.0
PB Proportional band value 10.0 C
(18.0 F)
Low: 0 500.0 LC
(900.0 LF)
High:
High:
TI
TD
Integral time value
Derivative time value
0
0
100
25.0
Low:
Low:
1000 sec
360.0 sec
High:
High:
OFST Offset value for P control Low: 0 High: 100.0 % 25.0
RAMP Ramp function selection
0 : No Ramp Function
2 : Use unit/hour as
Ramp Rate
1 : Use unit/minute as
Ramp Rate 0
Output 1 function 0
OUT1
0
1
Reverse (heating )
control action
Direct (cooling)
control action
:
:
14
www.comoso.com

RR Ramp rate 0.0
Low: 0 500.0 C
(900.0 F)
High:
Parameter
Notation Default
Value
Parameter Description Range
OUT2 Output 2 function
0 : Output 2 No Function
2 : Deviation High Alarm
3 : Deviation Low Alarm
6 : Process High Alarm
7 : Process Low Alarm
8 : Cooling PID Function
2
O2TY Output 2 signal type 0
0
1
2
3
Relay output
Solid state relay
drive output
Solid state relay
output
4 - 20 mA current
module
:
:
:
:
4
5
6
7
0 - 20 mA current
module
0 - 1V voltage
module
0 - 5V voltage
module
1 - 5V voltage
module
80 - 10V voltage
module
:
:
:
:
:
O2FT
Select BPLS ( bumpless transfer )
or 0.0 ~ 100.0 % to continue
output 2 control function if the
sensor fails, or select ON (0) or
OFF (1) for alarm function.
Output 2 failure
transfer mode 0
CPB Cooling proportional
band value 100
Low: 50 High: 300 %
CYC2 Output 2 cycle time Low: 0.1 High: 90.0 sec. 18.0
O2HY
Output 2 hysteresis
value when output 2
performs alarm
function
Low: 0.1 High: 50.0 C
(90.0 F)
0.1 C
(0.2 F)
15
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
ALFN Alarm function for
alarm output
0 :No alarm function
1 :Dwell timer action
2 :Deviation high alarm
3 :Deviation low alarm
4 :Deviation band out of
band alarm
5 :Deviation band in
band alarm
6 :Process value high
alarm
7 :Process value low
alarm
2
ALMD Alarm operation mode
:
:
:
:
1
2
3
0Normal alarm
action
Latching alarm
action
Hold alarm action
Latching & Hold
action
0
ALHY Hysteresis control of
alarm Low: 0.1 High: 50.0 C
(90.0 F)
:
Alarm failure transfer
mode 0
0
:
1Alarm output OFF as
unit fails
Alarm output ON as
unit fails
ALFT
Heating-cooling dead
band (negative value=
overlap)
0
Low: -36.0 High: 36.0 %
DB
0.1 C
(0.2 F)
COMM Communication
function
0 : No communication
1 : Modbus RTU mode
protocol
1
2:4-20mA retransmission
output
3:0-20mA retransmission
output
:0-5V retransmission
output
4
:1-5V retransmission
output
5
:0-10V retransmission
output
6
16
www.comoso.com

Parameter
Notation Default
Value
Parameter Description Range
BAUD Baud rate of digital
communication 2
:
02.4 Kbits/s baud rate
:
14.8 Kbits/s baud rate
:
29.6 Kbits/s baud rate
:
314.4 Kbits/s baud rate
:
419.2 Kbits/s baud rate
:
528.8 Kbits/s baud rate
:
638.4 Kbits/s baud rate
ADDR Address assignment of
digital communication Low: 1 High: 255
DATA Data bit count of digital
communication
0 : 7 data bits
1 : 8 data bits 1
PARI Parity bit of digital
communication
0 : Even parity
1 : Odd parity
2 : No parity bit
0
STOP Stop bit count of digital
communication
0 : One stop bit
1 : Two stop bits 0
SEL1 Select 1'st parameter for
user menu
:
0
1
2
3
5
6
No parameter selected
2
:LOCK is put ahead
:INPT is put ahead
:UNIT is put ahead
:SHIF is put ahead
7
:PB is put ahead
:TI is put ahead
4:DP is put ahead
RELO Retransmission low
scale value Low: -19999 High: 45536 0.0 C
(32.0 F)
REHI Retransmission high
scale value Low: -19999 High: 45536
100.0 C
(212.0 F)
17
www.comoso.com

Prameter
Notation Default
Value
Parameter Description Range
16
10
11
12
13
14
15
8
9
SEL1 Select 1st parameter for
user menu 2
SEL2 Select 2nd parameter
for user menu 3
Same as SEL1
SEL3 Select 3rd parameter
for user menu 4
Same as SEL1
SEL4 Select 4th parameter
for user menu 6
Same as SEL1
SEL5 Select 5th parameter
for user menu 7
Same as SEL1
SEL6 Select 6th parameter
for user menu 8
Same as SEL1
SEL7 Select 7th parameter
for user menu 10
Same as SEL1
SEL8 Select 8th parameter
for user menu 17
Same as SEL1
17
18
:TD is put ahead
:OFST is put ahead
:RR is put ahead
:O2HY is put ahead
:CYC2 is put ahead
:CPB is put ahead
:DB is put ahead
:ADDR is put ahead
:ALHY is put ahead
:O1HY is put ahead
:CYC1 is put ahead
18
www.comoso.com

2-2 Mounting2-2 Mounting
Make panel cutoutto dimension shownin Figure 2.1.Make panel cutoutto dimension shownin Figure 2.1.
Remove bothmounting clamps andinsert the controllerinto
panel cutout. Reinstall the mountingclamps. Gently tighten
the screws inthe clamp untilthe controller frontpanel is fitted
snugly in thecutout.
Remove bothmounting clamps andinsert the controllerinto
panel cutout. Reinstall the mountingclamps. Gently tighten
the screws inthe clamp untilthe controller frontpanel is fitted
snugly in thecutout.
Chapter 2 InstallationChapter 2 Installation
Dangerous voltages capable of causing death may be
present in this instrument. Before installation or beginning any
cleaning or troubleshooting procedures the power to all
equipment must be switched off and isolated. Units suspected of
being faulty must be disconnected and removed to aproperly
equipped workshop for testing and repair. Component
replacement and internal adjustments must be made by a
qualified maintenance person only.
Dangerous voltages capable of causing death may be
present in this instrument. Before installation or beginning any
cleaning or troubleshooting procedures the power to all
equipment must be switched off and isolated. Units suspected of
being faulty must be disconnected and removed to aproperly
equipped workshop for testing and repair. Component
replacement and internal adjustments must be made by a
qualified maintenance person only.
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt, moisture,
corrosive gases or oil. The ambient temperature of theareas
should not exceed the maximum rating specified in Chapter 6.
Do not use this instrument in areas under hazardous
conditions such as excessive shock, vibration, dirt, moisture,
corrosive gases or oil. The ambient temperature of theareas
should not exceed the maximum rating specified in Chapter 6.
2-1 Unpacking2-1 Unpacking
Upon receipt of the shipment remove the unitfrom the carton and
inspect the unit for shipping damage.
If any damage due to transit , report andclaim with the carrier.
Write down the model number, serial number, and date code for
future reference when corresponding with our service center. The
serial number (S/N) and date code (D/C) are labeled on thebox and
the housing of control.
Upon receipt of the shipment remove the unitfrom the carton and
inspect the unit for shipping damage.
If any damage due to transit , report andclaim with the carrier.
Write down the model number, serial number, and date code for
future reference when corresponding with our service center. The
serial number (S/N) and date code (D/C) are labeled on thebox and
the housing of control.
This instrument is protected throughout by Double
Insulation . To minimize the possibility of fire or shock
hazards, do not expose this instrument to rain or excessive
This instrument is protected throughout by
. To minimize the possibility of fire or shock
hazards, do not expose this instrument to rain or excessive
Double
Insulation
Remove stains from this instrument using a soft,dry cloth.
Don't use harsh chemicals, volatile solvents, such as thinners or
strong detergents to clean the instrument in order toavoid
deformation or discoloration.
Remove stains from this instrument using a soft,dry cloth.
Don't use harsh chemicals, volatile solvents, such as thinners or
strong detergents to clean the instrument in order toavoid
deformation or discoloration.
19
www.comoso.com

92 mm
45 mm
65 mm
Panel
TC 96
TC 48
Figure 2.1 Mounting DimensionsFigure 2.1 Mounting Dimensions
20
45 mm
45 mm
Panel
Cutout
104.8mm
Panel
11.5mm
www.comoso.com
This manual suits for next models
1
Table of contents
Other Eaton Temperature Controllers manuals